Title: COMPLEX BUILDING AUTOMATION PRODUCTS
1- COMPLEX BUILDING AUTOMATION PRODUCTS
INTRODUCTION
COMPLEX (BEIJING) TECHNOLOGY CO,.LTD ADD No.7
YANCHENGYUAN CHAOYANG PROVINCE BEIJING CHINA TEL
86 10 81779551 FAX 86 10 81779551-803
MAILSEVER_at_COMPLEXAUTO.COM WEB
WWW.COMPLEXAUTO.COM
2- BACnet Communications controllers
- Network Temperature controller and valves
- Temperature ?Humidity sensor and transmitter
3BACnet Communications controllers
- FC controller
- BIMS software (BACnet Communications )
- BACnet display
- BACnet router?Repeater and others
4 5FC-322N Programmable ViewLogic Controller
- ? Capable
- Eight 10-bit universal inputs, eight binary
inputs,six binary outputs,and six - 8-bit analogoutputs
- ? Interoperable
- BACnet-compliant on MS/TP lan at up to 76.8Kbps
- ? Versatile
- Fully programmable for central plant systems, air
handing units ,other - control and process equipment.
- ? Reliable
- Extensive onboard filtering, with all program
data backed up in nonvolatile - flash memory.
- ? Ratings
- Listed Underwriters Laboratory for Open Energy
Management Equipment - (PAZX).under theAU Standard for Safety
916.Listing includes both - Australia and Asia certification.
- EMC Directive 89/336/EEC(European CE Mark)
- FCC Part 15,Subpart J,Class A.
Applications and functions The COMPLEX FC-322N
is a versatile, high-performance
BACnet-compliant field controller designed for of
central plant systems, air handling units, large
terminal units, and similar control and
seamlessly with your BACnet system. It
communicates at up to 76.8Kbps on a BACnet MS/TP
LAN or can operate as a stand-alone
controller. ALL FC-322N control logic is
programmed with COMPLEXs easy-to-learn graphical
programming language,ViewLogic. This
self-documenting softwares complete function
library enables you to implement entirely
flexible control strategies. A single FC-322N can
contain numerous algorithm loops that control
various parts or multiple pieces of
equipment.Programming and setup data is stored in
non-volatile flash memory, and each FC-322N
contains its own software time schedule,ensuring
stable and reliable operation. The FC-322N
supports the intelligent operation display panel,
which offer convenient data display,setpoint
adjustment, and technician to equipment setup
parameters. The FC-322N is built for high-speed
processing ,with an internal logical loop time of
100msec. Programmable timers alsomaintain a
resolution of 100msec. High-resolution,10-bit
analog inputs are field-adjustable for
thermistor/dry contact, 0-5 VDC,4-20 mA or 0-10
VDC.Analog outputs are switch- selectable for
4-20 mA or 0-10 VDC.For equipment monitoring, and
onboard LED for each binary output/input
indicates ON/OFF status, and a separate LED
indicates communication activity on the MS/TP
LAN. CMOS circuitry,a four layer circuit board
with separate ground plane, and extensive
hardware software,and power-supply filtering
ensure reliable and stable operatio. The CMOS
processor uses an internal watchdog,and power
supply voltage is monitored to provide automatic
shutdown and data backup.
6- Technical Data
- Power 24 VAC _at_ 20VA. Utilizes a half-wave
rectifier, which allows a single transformer to
power Multiple VLCs. One leg of 24VAC connects to
earth (panel) ground. - Univeral Inputs 8 universal inputs with 10-bit
resolution. Inputs 0-7 are jumper-selectable for
thermistor/dry contact, 0-5 VDC,4-20mA or 0-10
VDC. - Binary inputs 8 binary inputs. Only dry contact
input, and onboard LED for binary inputs - Binary Outputs 6 relay outputs,each contact
rated at 277VAC,2A. - Analog Outputs 6 analog outputs with 8-bit
resolution. Each is jumper-selectable for 0-10VDC
or 4-20mA. 4-20mA outputs are sourced by the VLC.
Connected loads must return to the VLC ground,
4-20mA max.load resistance is 1,000 ohms. 0-10VDC
min.load resistance is 500ohms. - 24VDC Outputs Two terminals provide up to
350mA(total)of 24 VDC to power transducers. - Processor memory AVR processor with onboard
flash memory and RAM. - Terminations Removable header-type screw
terminals accept 14-24 AWG wire. - Environmental -17-70?.0-95RH,non-condensing.
- Communications BACnet MS/TP LAN up to 76.8Kbps.
- BACnet conformance An application specific
controller (ASC).tested and approved by BTL. See
Protocol implementation Conformance Statement
(PLCS) .
Dimensionmm
MODEL
Description FC-322N controller
8universal inputs 8 binary inputs 6 binary
outputsr 6 analog outputs(0-10V or 4-20mA).
7FC controller FC controller FC controller FC controller
PICTURE NAME Model Description
controller FC-322N 8 universal inputs(NTC 10K,Dry contact,0-10V,4-20mA,0-5V) 8 binary inputs (Dry contact) 6 binary outputs(Dry contact,contact rated at 250VAC,3A) 6 analog outputs(0-10V or 4-20mA).
controller FC-321N 8 universal inputs(NTC 10K,Dry contact,0-10V,4-20mA,0- 5V) 8 binary inputs (Dry contact) 12 binary outputs(BO0-BO5 are Dry contact),contact rated at 250VAC,3A. (BO6-BO11) is DC12V voltage output..need to connect the relay .(12VDC)
controller FC-312N 8 universal inputs(NTC 10K,Dry contact,0-10V,4-20mA,0-5V) 4 binary outputs(Dry contact,contact rated at 250VAC,3A) 3 analog outputs(0-10V or 4-20mA).
controller FC-301N 8 universal inputs(NTC 10K,Dry contact,0-10V,4-20mA,0-5V) 6 binary outputs(BO0-BO3 are Dry contact),contact rated at 250VAC,3A. (BO4-BO5) is DC12V voltage output..need to connect the relay (12VDC)1 analog outputs(0-10V)
controller IBAC-304N 4 universal inputs(NTC 10K,Dry contact,0-10V,4-20mA,0-5V) 4 binary outputs(Dry contact,contact rated at 250VAC,3A) 2 analog outputs (0-10V)
controller FC-302D 4 universal inputs(NTC 10K,Dry contact,0-10V,4-20mA,0-5V) 6 binary outputs(Dry contact,contact rated at 250VAC,3A) 2 analog outputs (0-10V) LED diaplay
8- BIMS softwar
- (BACnet Communications )
9BIMS software BIMS software BIMS software
NAME Model Description
BACView software BIMS-S 128 point,1CD,1 softdog(USB port),1 operational manual
BACView software BIMS-M 512 point,1CD,1 softdog(USB port),1 operational manual
BACView software BIMS-L1 1024 point,1CD,1 softdog(USB port),1 operational manual
BACView software BIMS-L2 4096 point,1CD,1 softdog(USB port),1 operational manual
BACView software BV-UNL 60000 point,1CD,1 softdog(USB port),1 operational manual
BACView software BIMS-Debug Development version programming tools and display, that no historical data
10 11SimView BACnet operation panel
- ? Capable
- Supports 40 BACnet values, include analog input,
analog output , binary - input ,binary output ,analog value and binary
value . - ? Interoperable
- BACnet-compliant on MS/TP lan at up to 76.8Kbps
- ? Reliable
- Extensive onboard filtering, with all program
data backed up in nonvolatile - flash memory.
- ? Fast
- Internal logic loop of 100msec
- ? Ecomomical
- Simple, low cost solution for field-level
integration of BACnet device. - ? Ratings
- Listed Underwriters Laboratory for Open Energy
Management Equipment - (PAZX).under the AU Standard for Safety
916.Listing includes both - Australia and Asia certification.
- EMC Directive 89/336/EEC(European CE Mark)
- FCC Part 15,Subpart J,Class A.
Applications and functions The COMPLEX Simview
is a versatile, high-performance
BACnet-compliant field controller operation penal
designed for of central plant systems, air
handling units, large terminal units, and similar
control and seamlessly with your BACnet system.
The BACnet field opration panel (Simview) is
the next-generation BACnet-compliant global
controller from Hysine. Simview can connect to a
BACnet MS/TP work or operate in a stand-alone
capacity. each Simview supports field controllers
on one BACnet MS/TP LANs. MS/TP is a simple
twisted-pair bus with a configurable speed to
76.8 Kbps. The Simview independently executes
global direct digital control(DDC) algorithms to
orchestrate the operation of field controllers o
its MS/TP LANs. DDC is programmed at a BACview
operator terminal with Hysines easy-to-use,
Windows-based graphical programming environment ,
ViewLogic. Revolutionary features like an
extensive application library, drag-and-drop DDC
edits, dynamic real-time data updates, and
self-documentation save time and ease the setup
process.The Simview can access available data as
BACnet objects and properties from throughout
BACnet internetwork, making its operational
status and contrl data available to other BACnet
devices in the same way. This enables an
unmatched level of interoperability with other
site systems. CMOS circuitry,a four layer
circuit board with separate ground plane, and
extensive hardware software,and power-supply
filtering ensure reliable and stable operatio.
The CMOS processor uses an internal watchdog,and
power supply voltage is monitored to provide
automatic shutdown and data backup. The VLCs
supports the Simview intelligent operation
display panel, which offer convenient data
display,setpoint adjustment, and technician to
equipment setup parameters.
12- Technical Data
- Power 24 VAC _at_ 5VA. Utilizes a half-wave
rectifier, which allows a single transformer to
power Multiple VLCs. One leg of 24VAC connects to
earth (panel) ground. - Battery Replaceable 3.0V lithium battery
provides up to 1.5 years(cumulative) real-time
clock(without external power supply). Standby
battery life is 10 years. Coin-cell type BR1225
or equivalent. - Schedule one time schedule with ten time segment
set - Show BACnet Value show 40 BACnet values, include
analog input, analog output, binary input, binary
output , analog value and binary values. - Processor memory AVR processor with onboard
flash memory and RAM. - Dimensions (112mm)H (140mm)W (38mm)D
- Terminations Removable header-type screw
terminals accept 14-24 AWG wire. - Environmental -17-70?.0-95RH,non-condensing.
- Communications BACnet MS/TP LAN up to 76.8Kbps.
- BACnet conformance An application specific
controller (ASC).tested and approved by BTL. See
Protocol implementation Conformance
Statement(PLCS). - Ratings
- Listed Underwriters Laboratory for Open Energy
Management Equipment (PAZX).under the AU Standard
for Safety 916.Listing includes both Australia
and Asia certification. - EMC Directive 89/336/EEC(European CE Mark)
- FCC Part 15,Subpart J,Class A.
Dimensionmm
MODEL
Description SIMVIEW
40 BACnet value show, include AI,
BI,AO,BO,AV or BV 8 row LCD show, can show
Chinese or English data
13- BACnet router?Repeater and others
14BACnet router?Repeater and others BACnet router?Repeater and others BACnet router?Repeater and others
NAME MODEL Description
BACnet Router BACRouter-32 Modbus communications network to BACnet MS / TP bus Up to 32 TCU controller
MS/TP Bus repeater BACRepeater-10 MS/TP Bus extension 1,000 m
BACnet Modbus Converter BG-Modbus Modbus 232 or 485, BACnet MS/TP Bus connections 100 BV variable, 100AV variable
BACnet self define Converter BG-Self self define the agreement 232 or 485, MS/TP Bus connections 100 BV variable, 100AV variable
15Network Temperature controller and valves
16Network Temperature controller Network Temperature controller Network Temperature controller Network Temperature controller
NO. MODEL NAME Description
1 ITEC-2P/L/N Network fan coil controller 2 pipe, Modbusnetworking, LCD display
2 ITEC-4P/L/N Network fan coil controller 4 pipe, Modbusnetworking, LCD display
3 ITEC-FM/BM Communications router Modbus communications network to BACnet MS / TP bus Up to 16 TCU controller
4 VZ4-215-x 2-way spring reset switch DN15,1/2",300kPa, x1,AC 220Vx2,AC 24V
5 VZ4-220-x 2-way spring reset switch DN20,3/4",150kPa, x1,AC 220Vx2,AC 24V
6 VZ4-225-x 2-way spring reset switch DN25,1", 120kPa, x1,AC 220Vx2,AC 24V
7 VZ4-315-x 3-way spring reset switch DN15,1/2",300kPa, x1,AC 220Vx2,AC 24V
8 VZ4-320-x 3-way spring reset switch DN20,3/4",150kPa, x1,AC 220Vx2,AC 24V
9 VZ4-325-x 3-way spring reset switch DN25,1", 120kPa, x1,AC 220Vx2,AC 24V
1710 VZ5-215-x 2-way spring reset switch DN15,1/2",300kPa, x1,AC 220Vx2,AC 24V
11 VZ5-220-x 2-way spring reset switch DN20,3/4",300kPa, x1,AC 220Vx2,AC 24V
12 VZ5-225-x 2-way spring reset switch DN25,1", 300kPa, x1,AC 220Vx2,AC 24V
13 VZ5-315-x 3-way spring reset switch DN15,1/2",300kPa, x1,AC 220Vx2,AC 24V
14 VZ5-320-x 3-way spring reset switch DN20,3/4",3050kPa, x1,AC 220Vx2,AC 24V
15 VZ5-325-x 3-way spring reset switch DN25,1", 300kPa, x1,AC 220Vx2,AC 24V
18Temperature ?Humidity sensor and transmitter
- Duct temperature / Humidity sensors /
transmitters - Walling temperature / Humidity sensors /
transmitters - Pipe temperature / Humidity sensors / transmitters
19- Duct temperature / Humidity sensors /
transmitters
20Duct temperature / Humidity sensors / transmitters Duct temperature / Humidity sensors / transmitters Duct temperature / Humidity sensors / transmitters Duct temperature / Humidity sensors / transmitters
PICTURE NAME MODEL Description
Duct temperature sensors CTSD-NIP2 NTC 10K, probe 200mm
Duct temperature sensors CTSD-P1P2 PT100, probe 200mm
Duct temperature sensors CTSD-P2P2 PT1000, probe 200mm
Duct temperature transmitter CTSD-P2D211/DC DC 24V4-20mA0-50? 2-wire PT1000
Duct temperature transmitter CTSD-P2D212/DC DC 24V4-20mA0-100? 2-wire PT1000
Duct temperature transmitter CTSD-P2D213/DC DC 24V4-20mA0-200? 2-wire PT1000
Duct temperature transmitter CTSD-P2D311/AC AC or DC 24V0-10V or 4-20mA 0-50?3-wirePT1000
Duct temperature transmitter CTSD-P2D312/AC AC or DC 24V0-10V or 4-20mA 0-100? 3-wire PT1000
Duct temperature transmitter CTSD-P2D313/AC AC or DC 24V0-10V or 4-20mA 0-200? 3-wire PT1000
Duct temperature transmitter CTSD-P2D310/AC AC or DC 24V0-10V or 4-20mA -20-60? 3-wirePT1000
Duct temperature transmitter CHSD-00D3/AC AC or DC 24V0-10V or 4-20mA Accuracy 5 3-wire
Duct temperature / Humidity transmitter CTHSD-N1D311/AC AC or DC 24V0-10V or 4-20mA0-50? Accuracy 5 3-wire
Duct temperature / Humidity transmitter CTHSD-N1D310/AC AC or DC 24V0-10V or 4-20mA-20-60? Accuracy 5 3-wire
21- Walling temperature / Humidity sensors /
transmitters
22walling temperature / Humidity sensors / transmitters walling temperature / Humidity sensors / transmitters walling temperature / Humidity sensors / transmitters walling temperature / Humidity sensors / transmitters
PICTURE NAME MODEL Description
ROOM temperature sensors CTSW-N1P NTC10K thermistor
ROOM temperature sensors CTSW-P1P PT100 Platinum Resistance
ROOM temperature transmitters CTSW-P2D3/AC AC or DC 24V0-10V or 4-20mA 0-50? 3-wire PT1000
ROOM temperature transmitters CTSW-P2D1/DC DC24V4-20mA0-50? 2-wire PT1000
ROOM temperature transmitters CHSW-00D3/AC AC or DC 24V0-10V or 4-20mA Accuracy 5 2-wire
ROOM temperature /Humidity transmitters CTHSW-00D31/AC AC or DC 24V0-10V or 4-20mA0-50? Accuracy 5 3-wire
ROOM temperature /Humidity transmitters CTHSW-00D30/AC AC or DC 24V0-10V or 4-20mA-20-60? Accuracy 5 3-wire
23- Immersion temperature / Humidity sensors /
transmitters
24Immersion temperature / Humidity sensors / transmitters Immersion temperature / Humidity sensors / transmitters Immersion temperature / Humidity sensors / transmitters Immersion temperature / Humidity sensors / transmitters
PICTURE NAME MODEL Description
Pipe temperature sensors CTSP-N1P1 NTC 10K, probe 100mm
Pipe temperature sensors CTSP-P1P1 PT100, probe 100mm
Pipe temperature sensors CTSP-P2P1 PT1000, probe 100mm
Pipe temperature sensors CTSP-N1P2 NTC10K , probe 100mm
Pipe temperature sensors CTSP-P1P2 PT100, probe 200mm
Pipe temperature sensors CTSP-P2P2 PT1000, probe 200mm
Pipe temperature transmitters CTSP-P2D112/DC DC 24V4-20mA0-100? 2-wire PT1000, probe 100mm
Pipe temperature transmitters CTSP-P2D212/DC DC 24V4-20mA0-200? 2-wire PT1000, probe 100mm
Pipe temperature transmitters CTSP-P2D213/DC DC 24V4-20mA0-100? 2-wire PT1000,??200mm
Pipe temperature transmitters CTSD-P2D132/AC AC or DC 24V0-10V or 4-20mA 0-100? 3-wire PT1000, probe 100mm
Pipe temperature transmitters CTSD-P2D133/AC AC or DC 24V0-10V or 4-20mA 0-200? 3-wire PT1000 , probe 100mm
Pipe temperature transmitters CTSD-P2D231/AC AC or DC 24V0-10V or 4-20mA 0-100? 3-wire PT1000 , probe 200mm
Pipe temperature transmitters CTSD-P2D233/AC AC or DC 24V0-10V or 4-20mA 0-200? 3-wire PT1000, probe 200mm