TXV Kits
  • How to apply a TXV kit to an evaporator coil
    Initial installation

2
Coil Preparation
  • Relieve the pressure from the coil by loosening
    the 13/16 nut 1 turn only.
  • Remove the nut and discard the black seal

3
Coil Preparation
  • Remove the check piston and discard

4
Coil Preparation
  • Use a tube cutter to remove the spin closure on
    the suction line

5
Coil Preparation
  • Remove the tailpiece clamped to the exterior

6
Suction Line Connection
  • Slide back the suction line grommet before
    brazing
  • Insert the TXV equalizer line with flare nut into
    the grommet
  • Then insert the suction line tubing (line set)

7
Suction Line Connection
  • Braze suction line tubing (line set) to the
    suction line field connection on coil

8
Expansion Valve Connection
  • Connect expansion valve outlet to flowrator body.
    Make sure Teflon seal is in place

9
Expansion Valve Connection
  • Slide the 13/16 nut into position. Braze
    tailpiece to the liquid tube (line set)

10
Expansion Valve Connection
  • AFTER THE TAILPIECE HAS COOLED, position the
    white Teflon seal and hand tighten the nut

11
Expansion Valve Connection
  • Torque the 13/16 nut to 10-30 ft/lb

12
Expansion Valve Connection
  • Connect equalizer tube with 1/4 flare nut to
    suction line fitting on the suction manifold
    (internal to the case)

13
Expansion Valve Connection
  • Torque to 8-10 ft/lb
  • Dress the tube to avoid rubbing and replace the
    grommet

14
Expansion Valve Connection
  • Secure expansion valve bulb to suction line
    (exterior to the case) with banding straps
    provided at the 10 oclock or 2 oclock position
  • IMPORTANT Insulate the bulb and adjacent area

15
Wrap Up
  • Finally Check for leaks

16