MRB on SLAC NCR 226 Excess of Disconnected MCM Channels - PowerPoint PPT Presentation

1 / 14
About This Presentation
Title:

MRB on SLAC NCR 226 Excess of Disconnected MCM Channels

Description:

MRB on SLAC NCR 226 Excess of Disconnected MCM Channels R.P. Johnson November 9, 2004 1. Description of Non-Conformance MCM part number LAT-DS-00898, SN 11378 was ... – PowerPoint PPT presentation

Number of Views:24
Avg rating:3.0/5.0
Slides: 15
Provided by: RobertP59
Category:

less

Transcript and Presenter's Notes

Title: MRB on SLAC NCR 226 Excess of Disconnected MCM Channels


1
MRB on SLAC NCR 226Excess of Disconnected MCM
Channels
  • R.P. Johnson
  • November 9, 2004

2
1. Description of Non-Conformance
  • MCM part number LAT-DS-00898, SN 11378 was found
    to have 151 channels disconnected between the
    amplifiers and the pitch adapter.
  • This MCM had zero non-conductive cracked traces
    (from the visual inspection) and zero dead
    amplifiers.
  • This problem was found Friday, November 5, at
    SLAC while testing 42 MCMs using the new
    electronic pitch-adapter test fixture.
  • Earlier the same week 1 MCM already attached to a
    tray and SSDs at GA was found to have about 300
    disconnected channels.
  • Also, at GA and Pisa 2 trays were found to have
    a disconnection of 1 or more bias lines, which
    may be from the same root cause.

3
Inspections and Tests
  • A new fixture designed at SLAC solves our old
    problem of not being able to test the connections
    to the amplifier inputs until SSDs are attached.
    This became a critical problem when the MCM
    mounting changed from screws to gluing.
  • Initially our assurance was based on
  • Wire bond quality control at Teledyne
  • Visual inspection of all wire bonds and bond feet
    at MIP-2 at Teledyne
  • Sample testing of several preproduction MCMs by
    probing each pitch-adapter trace.
  • After an MCM on Tower-0 was found with 25 cracked
    traces, we did the following
  • Visual inspection for cracks in pitch-adapter
    (and manual probing with a DVM for continuity)
    traces before shipment to Italy. This appears to
    be quite effective, albeit with a rejection rate
    of 14, requiring no more than 8 such cracked,
    nonconductive traces.
  • Tested with 200 thermal cycles whether the
    incidence of non-conductive cracks gets worse (it
    does not).
  • Stepped up existing efforts to get an electrical
    test method developed.

4
The Electrical Test Method
  • Use a conductive, flexible strip (zebra strip) to
    short circuit 100 of the pitch-adapter traces to
    ground.
  • Bias HV is turned off, to protect it.
  • AVDDA must be turned on, but the resistance of
    the zebra strip is high enough that it does not
    draw enough current to cause any problem.
  • Run a charge-injection scan and measure the
    response of each channel.
  • Channels with inputs shorted to ground will look
    dead.
  • Channels not connected to the pitch adapter will
    look alive, unless the amplifier is already dead
    for some other reason.
  • So, if a channel measures good in the normal
    electrical test, with the input floating, AND it
    measures dead with the zebra strip applied, then
    we are certain that it is a good, connected
    channel.
  • If a channel measures good with the zebra strip
    applied, then either
  • it is disconnected from the pitch adapter, or
  • the zebra strip did not make contact with the
    pitch adapter (false negative).

5
Pitch-Adapter Electrical Test Fixture
Designed by Peter Amnuaypayoat
STORAGE CASE BASE
ZEBRA CONNECTOR
SOFTWARE/ ELECTRICAL FIXTURE
MCM WITH PITCH ADAPTER
TEST FIXTURE
CONNECTOR SAVER
GROUND LEAD
6
Disconnected Ch. vs. Cracked Traces
Visual inspection and test data from 41 MCMs.
Note that the number of disconnected channels is
probably a little bit overestimated, due to
occasional false negatives given by the test
fixture. (False positives are not possible,
unless the connection is intermittent.)
7
Disconnected Ch. vs. Cracked Traces
Visual inspection and test data from 41 MCMs.
The 42nd MCM had 151 disconnected and 0 cracked
traces.
8
Bias Disconnects
  • The pitch-adapter electrical test fixture will
    not detect problems with the bias traces.
  • Our visual inspection rejected MCMs with even 1
    cracked nonconductive bias trace, but this does
    not catch all problems.
  • Up to now we relied on
  • 100 electrical test of the PWB.
  • Visual inspection of the bias resistor.
  • Wire-bond QC and visual inspection at MIP-2 at
    Teledyne.
  • Still, there are 2 cases of MCMs in Italy with
    bad (sometimes intermittent) bias connections.
  • Therefore, we are now doing the following
    procedure on all MCMs before shipping to Italy
  • Turn the bias voltage down to 2.5 V, and turn on
    the MCM power.
  • Using a voltmeter, probe each of the 16 bias
    traces past the bend region, and verify that the
    appropriate voltage (2.5 V or 1.5 V) is seen.

9
2. Overstress Analysis Additional Testing
  • We tried out the test fixture on the 4 nonflight
    MCMs that we recently passed through 200 thermal
    cycles from ?30C to 85C.
  • 3 were not bad, with the worse case being 15
    disconnected channels.
  • 4th had 60 to 80 disconnected traces, depending
    on the test trial. The results were variable,
    and we found clear cases of false positives. The
    pressure from the fixture was causing
    reconnections of some of the failed traces.
  • This experiment would be more interesting if we
    had a measurement before the thermal cycles as
    well as after.
  • A more relevant test will be to check the
    connections at MIP-3 (i.e. at Teledyne) and then
    again after thermal cycles and burn-in at SLAC.

10
3. Suspected Root Cause
  • We suspect failure of the wire bonds where they
    connect to the pitch adapter. They are not
    visible (black encapsulant), but we have indirect
    evidence
  • Cracked traces in the visible region of the pitch
    adapters are eliminated by our thorough visual
    scans.
  • Our visual inspection at MIP-2 ensures that the
    wire bonds were there and were initially
    connected (we couldnt fail to see 151
    disconnected or missing bonds!).
  • The MIP-2 visual inspection also rules out that
    any significant number of the disconnected
    channels could be due to pitch-adapter cracks
    close to the cut edge.
  • The very low failure rate of wire bonds on the
    power and digital I/O GTFE connections nearly
    rules out wire-bond failure on the ASIC side of
    the bond.
  • The pitch-adapter substrate is the more difficult
    material to wire bond to.
  • So, we believe that either the bonds failed
    during encapsulation or later during thermal
    cycling. The intermittent ones must have failed
    after encapsulation in order to have the foot
    still so close to the pitch-adapter trace.

11
Impacts to Inventory
  • The 1-in-42 (2.4) occurrence of large numbers of
    disconnected bonds is not a big problem for MCM
    availability.
  • The 14 loss due to gt8 cracked traces is a big
    problem. At that rate we have to review again
    whether we will have enough parts to complete the
    build, given that this is not the only source of
    loss of MCMs (e.g. Tower-0). I suggest that we
    consider raising the maximum number of bad
    channels from 8 to 15. This is the limit used at
    the tray level and corresponds to a worst-case
    inefficiency of 1.

12
5. Corrective Action
  • Test all MCMs with the PA test fixture both at
    MIP-3 and before shipping to Italy. We need to
    manufacture one more fixture.
  • Review and possibly improve the Teledyne
    wire-bonding controls. The present procedure
    calls for the following
  • Plasma clean in Tepla (Recipe 1) prior to wire
    bonding.
  • At the start of each shift, wire bond the test
    pattern on a single die on the wire bond set up
    PCB. Perform 100 destructive pull test. During
    actual wire bonding, perform Non destructive Pull
    Testing (NDPT) on every 3rd unit. NDPT test on 2
    die, 30 wires on a single PCB only.
  • Update and re-release the burn-in and test
    procedure LAT-TD-02367.
  • Verification plan
  • Test our remaining MCMs with the PA fixture asap.
  • Consider doing extra thermal cycles on some
    non-flight MCMs, with tests before and after.

13
6. Effectiveness of Corrective Action
  • The PA test fixture is almost guaranteed to find
    the missing connections, the only exception being
    cases where the pressure from the fixture results
    in a temporary reconnection. This will not
    happen on all or even most of any large number of
    missing connections on a given MCM.
  • There is some concern that the tray-level thermal
    cycles could produce more disconnections.
  • The burn-in procedure thermal cycles are more
    severe in terms of number of cycles (20 vs. 4)
    and range (?30C to 85C vs. ?30C to 55C).
  • This would be the reason to try some more
    extensive thermal cycle testing on non-flight
    MCMs.

14
7. Recommended Disposition
  • Scrap (use for EGSE) the MCM that is the subject
    of NCR 226.
  • Return all MCMs to SLAC that have not been tested
    with the PA fixture and bias-circuit hand
    probing.
  • Begin mounting to trays those MCMs that passed
    the PA and bias probing tests.
Write a Comment
User Comments (0)
About PowerShow.com