Diversified Air Systems,Inc.Firetrace
Technology
  • Call today 800-264-8958

2
What is Firetrace?
  • Suppression for the micro-environment
  • Pneumatic heat detection
  • Fire suppression system
  • Total flooding OR Local application
  • Detection and suppression at the ignition point

3
Its All About the TUBE
  • Linear, pneumatic flame detection
  • Bursts at 212F (100C)
  • Tubing can be the detector the piping network
  • Tubing is durable and flexible
  • Tubing is not conductive or corrosive
  • Good for harsh chemical environments

4
Direct System
Direct Low Pressure System
5
Direct System
  • Effects of high air velocity may impact discharge
  • Must be careful with locating tubing discharge
    is at tubing burst point
  • Limited to 50 ft furthest point from cylinder
    system can have well over 200 ft of total tubing
  • 1 lb / 3lb / 6lb / 12lb Clean Agent Assemblies
  • 2.5lb and 5lb Dry Chemical Assemblies

6
Characteristics of the Firetrace Detection Tubing
  • Commercial Name FT 1992 Thermoplas
  • Physical Appearance 6mm OD red tube
  • Change in Physical state Melts _at_ 194 C (381.2
    F)
  • Bulk Density 17g / meter (5.18g/ft)
  • Dielectric Strength (DIN 53481)kV/mm dry 40
  • Thermal Decomposition Above 300 C (572 F)
  • Temperature at Burst 100-115 C _at_ 150 psi
  • (212-239 F _at_ 150 psi)

7
The Burst
8
Direct Low Pressure (DLP) System
  • Tubing is used as a detector and delivery of
    agent from cylinder
  • Valve is a X-over only to allow for connection of
    the tubing to cylinder
  • 4 ports on this valve for gauge, P/S, Ball Valve
    and cylinder

Max 3.3 ft / layer
  • Discharge time is limited due to the x-sectional
    area of the ball valve orifice.

9
DLP (Direct Low Pressure) System
10
OPTIONS
  • PRESSURE SWITCH
  • Monitors pressure in the tubing and in cylinder
  • Can use one on cylinder and as many as needed on
    tubing network
  • Used for
  • Building alarm tie-in
  • Power lock-out or shunt trip
  • Fan/damper control
  • Auxiliary controls