Title: EN 54-16


1
EN 54-16
  • Compliant Installation of Voice Alarm Systems

2
When does EN54-16 Apply?
  • Construction Products Directive CPD
  • CPD EN54 is mandatory for fire detection and
    alarm systems in all EU member states
  • 2008 issue of two new parts of EN54
  • Part 16 voice alarm systems
  • End of co-existence period March 2011
  • Part 24 loudspeakers for voice alarm systems
  • End of co-existence period April 2011
  • End of co-existence period conflicting
    national standards must be withdrawn

3
When does EN54-16 Apply?
  • System depending
  • EN 54-16 must be applied
  • When the voice alarm system is controlled by the
    fire detection system
  • Application not necessary
  • When the voice alarm system is a stand-alone
    system (triggered manually) or
  • controlled by others that fire detection systems
  • When must voice alarm be applied?
  • National requirements

4
Approved VA Systems
  • Certification
  • The voice alarm system must be certified on
    EN54-16 by a notified body
  • Notified bodies can be found on the EU Web sites
  • Certificate of the notified body contains
  • Certificate number
  • Approved system components
  • Approved options

5
Approved VA Systems
  • Indication of Approval
  • Certificate number
  • at least on one main part of the VA system
  • in the accompanied documents
  • Applicable options
  • in the accompanied documents

6
EN 54-16 Compliant Design
  • Access Levels
  • Mandatory Function
  • Mandatory Indications

7
Access Levels
  • Access Level 1
  • Public areas or
  • Areas with unrestricted access for persons having
    a general responsibility for safety supervision
  • E.g. in a technical room
  • Manual controls shall be accessible without
    special procedures
  • E.g. not by opening a door

8
Access Levels
  • Access Level 2
  • Access restricted by special procedures
  • Access by
  • mechanical key (locked technical room)
  • code of at least 3 sequential operations
  • access cards
  • Access for Persons
  • with specific responsibility for safety and
  • Authorised and trained on operating

9
Mandatory Indications
  • Must be in Access Level 1 always
  • VA condition, especially EMERGENCY
  • Indication on a remote microphone by programmed
    fault receipt (acknowledge) button (SX on SM)
  • General Fault
  • Indication on a remote microphone by programmed
    fault receipt (acknowledge) button (SX on SM)
  • System Fault
  • Indication on a remote microphone by programmed
    fault receipt (acknowledge) button (SX on SM)

10
Mandatory Indications
  • Must be in Access Level 1 always
  • Fuse Rupture
  • Indication on a remote microphone by programmed
    fault receipt (acknowledge) button for all amps
  • Fault in Signal Path between System components
  • Only for SX-2000 indication by programmed fault
    receipt (acknowledge) button
  • Earth Leakage
  • For outgoing wires (e.g. speaker lines,
    microphones)
  • Only necessary if not implemented in other fault

11
Mandatory Functions
  • Must be in Access Level 1 always
  • Lamp Test (Button)
  • To test the mandatory indications
  • Fault Acknowledge (Button)
  • In TOA VA systems always combined with fault
    indications

12
Options
  • Mandatory Indications
  • Faults in VA Zones
  • One fault indicator per VA zone
  • Fault in the connection to the fire detection
    system
  • A separate indicator must be provided

13
Options
  • Access Level
  • Manual Silencing 2
  • Manual Reset of the VA condition 2
  • VA condition output n.a.
  • VA manual control 2
  • Emergency microphones 2
  • Redundant power amplifiers n.a.
  • Audible warning of VA condition 1, 2
  • VA manual control 2
  • Phased evacuation 2

14
Options
  • Available on TOA VA Systems
  • Manual Silencing SX, VX
  • Button on emergency microphone
  • VX acivating dummy text (silence)
  • SX stopping emergency pattern or sequence
  • Manual Reset of the VA condition SX, VX, VM
  • Emergency reset button
  • VA condition output SX, VX, VM
  • Control output
  • VA manual control SX, VX, VM
  • Manual assignment of emergency messages to
    emergency zones

15
Options
  • Available on TOA VA Systems
  • Emergency microphones VX, VX, VM
  • Fireman microphone, emergency microphone (VX, SX)
  • Redundant power amplifiers SX, VX, VM
  • Standby amplifiers
  • Audible warning of VA condition VM
  • Buzzer tone when emergency was activated
  • Phased evacuation SX
  • When phases can be controlled manually or by fire
    detection system