Title: ENERGY CONVERSION ONE (Course 25741)
1ENERGY CONVERSION ONE (Course 25741)
- Chapter Two
- TRANSFORMERS
- continued
2Equivalent Circuit of Transformer
- Major Items to be considered in Construction of
Transformer Model - Copper losses (in primary Secondary winding)
I² - Eddy current losses (in core) V²
- Hysteresis losses (in core) a complex nonlinear
function of applied V - Leakage flux fLP fLS, these fluxes
produce - self-inductance in primary secondary coils
3Equivalent Circuit of Transformer
- Exact Eq. cct. Model for Real Transformer
- Copper losses modeled by resistances Rp Rs
- As discussed before
- fpfmfLp fp total av. Primary flux
- fSfmfLS fS total av. Secondary flux
- where fm flux linking both P S
- fLp primary leakage flux
- fLS secondary leakage flux
- The average primary ( Secondary) flux, each,
is divided into two components as - mutual flux leakage flux
4Equivalent Circuit of Transformer
- Based on application of these components,
Faradays law for primary circuit can be
expressed as - Vp(t)Np dfp/dt Np dfM/dt Np dfLp/dt or
- Vp(t)ep(t) eLp(t) similarly for secondary
- Vs(t)Ns dfs/dt Ns dfM/dt Ns dfLs/dt or
- Vs(t)es(t) eLs(t)
- primary secondary voltages due to mutual flux
- ep(t) Np dfM/dt es(t) Ns
dfM/dt
5Equivalent Circuit of Transformer
- Note ep(t)/Np dfM/dt es(t)/Ns
- ep(t)/es(t) Np / Ns a
- while eLp(t) Np dfLp/dt eLs(t) Ns dfLs/dt
- if ? permeance of leakage flux path
- fLp(p Np) ip fLs(p Ns) is
- eLp(t) Np d/dt (p Np) ip Np²p dip/dt
- eLs(t) Ns d/dt (p Ns) is Ns²p dis/dt
- DefiningLp Np²p primary leakage inductanc
- Ls Ns²p secondary leakage
inductance
6Equivalent Circuit of Transformer
- eLp(t)Lp dip/dt
- eLs(t)Ls dis/dt
- Therefore leakage flux can be modeled by primary
secondary leakage inductances in equivalent
electric circuit - Core Excitation that is related to the flux
linking both windings (fm flux linking both P
S) should also be realized in modeling - im (in unsaturated region) e (voltage applied
to core) - and lag applied voltage by 90? modeled by an
inductance Lm (reactance Xm) - Core-loss current ieh is voltage applied It
can be modeled by a resistance Rc across primary
voltage source - Note these currents nonlinear therefore Xm
Rc are best approximation of real excitation
7Equivalent Circuit of Transformer
- The resulted equivalent circuit is shown
- Voltage applied to core input voltage-internal
voltage drops of winding
8Equivalent Circuit of Transformer
- to analyze practical circuits including
Transformers, it is required to have equivalent
cct. at a single voltage - Therefore circuit can be referred either to its
primary side or secondary side as shown
9Equivalent Circuit of Transformer
- Approximate Equivalent Circuits of a Transformer
- in practice in some studies these models are more
complex than necessary - i.e. the excitation branch add another node to
circuit, while in steady state study, current of
this branch is negligible - And cause negligible voltage drop in Rp Xp
- Therefore approximate eq. model offered as
-
10Equivalent Circuit of TransformerApproximate
transformer models
- a- referred to primary
- b- referred to secondary
- c- with no excitation branch referred to p
- d- with no excitation branch referred to s
11Determination of Transformer Eq. cct. parameters
- Approximation of inductances resistances
obtained by two tests - open circuit test short circuit test
- 1- open circuit test transformers secondary
winding is open circuited, primary connected to
a full-rated line voltage, Open-circuit test
connections as below
12Determination of Transformer Eq. cct. parameters
- Input current, input voltage input power
measured - From these can determine p.f., input current, and
consequently both magnitude angle of excitation
impedance (RC, and XM) - First determining related admittance and
Susceptance - GC1/RC BM1/XM ? YEGC-jBM1/RC -1/XM
- Magnitude of excitation admittance referred to
primary circuit YE IOC/VOC - P.f. used to determine angle,
- PFcos?POC/VOC . IOC
- ?cos?1 POC/VOC . IOC
13Determination of Transformer Eq. cct. parameters
- Thus YE IOC/VOC IOC / VOC
- Using these equations RC XM can be
- determined from O.C. measurement
-
14Determination of Transformer Eq. cct. parameters
- Short-Circuit test the secondary terminals of
transformer are short circuited, and primary
terminals connected to a low voltage source - Input voltage adjusted until current in s.c.
windings equal to its rated value
15Determination of Transformer Eq. cct. parameters
- The input voltage, current and power are again
measured - Since input voltage is so low during
short-circuited test, negligible current flows
through excitation branch - Therefore, voltage drop in transformer attributed
to series elements - Magnitude of series impedances referred to
primary side of transformer is ZSE VSC/
ISC , PFcos?PSC/VSC ISC - ?cos?1 PSC/VSC ISC
- ZSE VSC / ISC VSC/ ISC
- series impedance ZSE is equal to
- ZSEReqjXeq (RP a²RS) j(XPa²XS)
- It is possible to determine the total series
impedance referred to primary side , however
difficult to split series impedance into primary
secondary components although it is not
necessary to solve problem - These same tests may also be performed on
secondary side of transformer
16Determination of Transformer Eq. cct. parameters
- Determine Equivalent cct. Impedances of a 20 kVA,
8000/240 V, 60 Hz transformer - O.C. S.C. measurements shown?
- P.F. in O.C. is
- PFcos?POC/VOCIOC
- 400 W/ 8000V x 0.214A
- 0.234 lagging
-
O.C. test (on primary) S.C. test (on primary)
VOC8000V VSC489V
IOC0.214A ISC2.5 A
POC400W PSC240W
17Determination of Transformer Eq. cct. parameters
- excitation impedance
- YEIOC/VOC
- 0.214 A / 8000 V
- 0.0000268
- 0.0000063 j 0.0000261 1/RC- j 1/XM
- Therefore
- RC1/ 0.0000063 159 kO
- XM 1/0.000026138.4 kO
18Determination of Transformer Eq. cct. parameters
- PF in sc test
- PFcos? PSC/VSCISC240W/ 489x2.50.196
lagging - Series impedance
- ZSEVSC/ISC
- 489 V/ 2.5 A 195.6
- 38.4 j 192 O
- The Eq. resistance reactance are
- Req38.4 O , Xeq192 O
19Determination of Transformer Eq. cct. parameters
- The resulting Eq. circuit is shown below
20The Per Unit System For Modeling
- As seen in last Example, solving cct. containing
transformers requires tedious operation to refer
all voltages to a common level - In another approach, the need mentioned above is
eliminated impedance transformation is avoided - That method is known as per-unit system of
measurement - there is also another advantage, in application
of per-unit as size of machinery Transformer
varies its internal impedances vary widely, thus
a 0.1 O cct. Impedance may not be adequate
depends on devices voltage and power ratings
21The Per Unit System For Modeling
- In per unit system the voltages, currents,
powers, impedance and other electrical quantities
not measured in SI units system - However it is measured and define as a decimal
fraction of some base level - Any quantity can be expressed on pu basis
- Quantity in p.u.
- Actual Value / base value of quantity
22The Per Unit System For Modeling
- Two base quantities selected other base
quantities can be determined from them - Usually voltage, power
- Pbase,Qbase, or Sbase Vbase Ibase
- Zbase Vbase/Ibase
- YbaseIbase/Vbase
- Zbase(Vbase)² / Sbase
- In a power system, bases for power voltage
selected at a specific point, power base remain
constant, while voltage base changes at every
transformer
23The Per Unit System For Modeling
- Example A simple power system shown in Figure
below - Contains a 480 V generator connected to an ideal
110 step up transformer, a transmission line, an
ideal 201 step-down transformer, and a load
24The Per Unit System For Modeling Example
- Impedance of line 20j60O,impedance of load
- Base values chosen as 480 V and 10 kVA at
genertor - (a) Find bas voltage, current, impedance, and
power - at every point in power system
- (b) convert this system to its p.u.
equivalent cct. - (c) Find power supplied to load in this
system - (d) Find power lost in transmission line
- (a) At generator IbaseSbase/Vbase
110000/48020.83 A - Zbase1Vbase1/Ibase1480
/20.8323.04 O - Turn ratio of transformer T1 , a1/10 0.1 so
base voltage at line Vbase2Vbase1/a480/0.14800
V
25The Per Unit System For Modeling Example
- Sbase210 kVA
- Ibase210000/48002.083 A
- Zbase24800 V/ 2.083 A 2304 O
- Turn ratio of transformer T2 is a20/120, so
voltage base at load is - Vbase3Vbase2/a 4800/20 240 V
- Other base quantities are
- Sbase310 kVA
- Ibase310000/24041.67 A
- Zbase3240/41.67 5.76 O
26The Per Unit System For Modeling Example
- (b) to build the pu equivalent cct. Of power
system, each cct parameter divided by its base
value - VG,pu
- Zline,pu(20j60)/23040.0087j0.0260 pu
- Zload,pu
- Per unit equivalent cct of PWR. SYS. Shown below
-
27The Per Unit System For Modeling Example
- (c) current flowing in
- IpuVpu/Ztot,pu
-
pu - Per unit power of load
- Pload,pu Ipu²Rpu(0.569)²(1.503)0.487
- actual power supplied to load
- PloadPload,puSbase0.487 x 100004870 W
- (d) power loss in line
- Pline loss,pu Ipu²Rline,pu(0.569)²(0.0087)0.002
82 - Pline Pline loss,pu Sbase (0.00282)(10000)28.2
W