Title: Essentials of Fire Fighting,
1- Essentials of Fire Fighting,
- 5th Edition
Chapter 16 Fire Detection, Alarm, and
Suppression Systems Firefighter I
2Chapter 16 Lesson Goal
- After completing this lesson, the student shall
be able to operate various fire detection, alarm,
and suppression systems and operate at fires in
protected properties following the policies and
procedures set forth by the authority having
jurisdiction (AHJ).
3Specific Objectives
- 1. List functions of fire detection, alarm, and
suppression systems. - 2. Discuss general automatic sprinkler
protection and types of coverage. - 3. Describe control valves and operating valves
used in sprinkler systems.
(Continued)
4Specific Objectives
- 4. Describe major applications of sprinkler
systems. - 5. Discuss operations at fires in protected
properties. - 6. Operate a sprinkler system control valve.
(Skill Sheet 16-I-1)
(Continued)
5Specific Objectives
- 7. Manually stop the flow of water from a
sprinkler. (Skill Sheet 16-I-2) - 8. Connect hoseline to a sprinkler system FDC.
(Skill Sheet 16-I-3)
6Functions of Fire Detection, Alarm, Suppression
Systems
- To notify occupants of facility to take necessary
evasive action to escape dangers of hostile fire
- To summon organized assistance to initiate or
assist fire control activities
(Continued)
7Functions of Fire Detection, Alarm, Suppression
Systems
- To initiate automatic fire control, suppression
systems, sound alarm - To supervise fire control, suppression systems to
ensure operational status maintained
(Continued)
8Functions of Fire Detection, Alarm, Suppression
Systems
- To initiate wide variety of auxiliary functions
involving environmental, utility, process controls
(Continued)
9Automatic Sprinkler Protection
- Consists of series of sprinklers arranged so
system will automatically distribute sufficient
quantities of water directly onto fire - Water supplied to sprinklers through system of
piping
(Continued)
10Automatic Sprinkler Protection
- Sprinklers can extend from exposed pipes or
protrude through ceiling or walls from hidden
pipes - Sprinkler coverage complete or partial
(Continued)
11Automatic Sprinkler Protection
- Standards used as guides for installing sprinkler
protection in most occupancies - Sprinkler system should be listed by nationally
recognized testing laboratory - Automatic sprinkler systems fail to operate only
in rare instances
12Effects of Sprinkler Systems on Life Safety
- Safety of building occupants enhanced by presence
of sprinkler system because it discharges water
directly onto fire while still relatively small
(Continued)
13Effects of Sprinkler Systems on Life Safety
- Because fire extinguished/controlled in early
growth stage, combustion products limited - Sprinklers also effective in other situations
- There are times when sprinklers alone are not as
effective
14Control Valves
- Part of every sprinkler system
- Used to turn off water supply to system in
order to replace sprinklers, perform maintenance,
interrupt operations
(Continued)
15Control Valves
- Located between source of water supply, sprinkler
system - Usually located immediately under sprinkler alarm
valve, dry-pipe or deluge valve, or outside
building near sprinkler system it controls
(Continued)
16Control Valves
- Either secured in open position with chain and
padlock or electronically supervised to make sure
not inadvertently closed
17Indicating Control Valves
- Show at glance whether open or closed
- Outside stem and yoke (OSY) valve
(Continued)
18Indicating Control Valves
- Post indicator valve (PIV)
(Continued)
19Indicating Control Valves
- Wall post indicator valve (WPIV)
(Continued)
20Indicating Control Valves
- Post indicator valve assembly (PIVA)
21Operating Valves
- Alarm test valve
- Inspectors test valve
- Main drain valve
22Wet-Pipe Systems
- Used in locations where temperatures below 40F
(4C) not expected - Simplest type of automatic fire sprinkler system
(Continued)
23Wet-Pipe Systems
- Generally require little maintenance
- Contain water under pressure at all times
- Connected to public/private water supply so fused
sprinkler immediately discharges water spray,
actuates alarm
(Continued)
24Wet-Pipe Systems
- Usually equipped with alarm check valve installed
in main riser adjacent to where feed main enters
building - Newer versions may have a backflow prevention
check valve and electronic flow alarm.
(Continued)
25Wet-Pipe Systems
- May be equipped with retarding device as part of
alarm check valve
26Dry-Pipe Systems
- Used in locations where piping may be subjected
to temperatures below 40F (4C)
(Continued)
27Dry-Pipe Systems
- Have pitched (sloped) pipes to help drain water
in system back toward main drain - Replace water in sprinkler piping with air under
pressure
(Continued)
28Dry-Pipe Systems
- Designed so small amount of air pressure above
dry-pipe valve will hold back much greater water
pressure on water supply side of dry-pipe valve - Equipped with electric or hydraulic
alarm-signaling equipment
(Continued)
29Dry-Pipe Systems
- Larger systems may have several-minute delay
while air expelled from system
30Preaction Systems
- Dry systems that employ deluge-type valve, fire
detection device, closed sprinklers - Used when especially important to prevent water
damage, even if pipes broken
(Continued)
31Preaction Systems
- Will not discharge water into sprinkler piping
except in response to smoke- or heat-detection
system actuation - Sound alarm to give warning before opening of
sprinklers
32Deluge Systems
- Similar to dry-pipe system in no water in
distribution piping before system activation - Differ from dry-pipe systems in sprinklers have
no fusible links, do not function as fire
detection devices
(Continued)
33Deluge Systems
- Designed to quickly supply large volume of water
to protected area - Sometimes used to discharge foam/other
extinguishing agents in occupancies containing
flammable liquids, other volatile fuels
34Residential Systems
- Installed in one- and two-family dwellings
- Designed to give occupants of dwelling chance to
escape, prevent total involvement in room of
origin - Employ quick-response sprinklers
(Continued)
35Residential Systems
- Use several types of piping systems
- Must have pressure gauge, flow detector, means
for draining and testing system - Can be either connected directly to public water
supply or to dwellings domestic water system
(Continued)
36Residential Systems
- Require control valve to turn off water to
sprinkler system and to domestic water system if
connected if sprinkler system supplied
separately from domestic water system, sprinkler
control valve must be supervised in open position
(Continued)
37Residential Systems
- Operate in same manner as other wet-pipe/dry-pipe
systems - May be equipped with fire department connection
(FDC) FDC may be 1½-inch (38 mm) connection
38Important Factors in Occupancies With Activated
Sprinkler Systems
- Early-arriving pumper should connect to FDC in
accordance with preincident plan - Firefighters should make every effort to supply
adequate water to operating sprinkler system
(Continued)
39Important Factors in Occupancies With Activated
Sprinkler Systems
- Water supply may have to be conserved to supply
sprinkler system - Sprinkler system control valves must be open
(Continued)
40Important Factors in Occupancies With Activated
Sprinkler Systems
- Sprinkler control valves should not be closed
until fire officers convinced further operations
will simply waste water, produce heavy water
damage, hamper progress of final extinguishment
(Continued)
41Important Factors in Occupancies With Activated
Sprinkler Systems
- When a sprinkler control valve closed,
firefighter with portable radio should be
stationed at valve in case it needs to be
reopened - In some departments, SOP to plug open sprinklers
rather than shut entire system down
(Continued)
42Important Factors in Occupancies With Activated
Sprinkler Systems
- Pumpers should not be disconnected from FDC until
after extinguishment confirmed by thorough
overhaul - Sprinkler equipment should be restored to service
before leaving premises
(Continued)
43Important Factors in Occupancies With Activated
Sprinkler Systems
- Firefighters may be required to stop flow of
water from single sprinkler that has been
activated
44Summary
- Many of the buildings to which firefighters are
called for emergency operations are protected
partially or fully by automatic fire detection
and/or suppression systems.
(Continued)
45Summary
- Firefighters need to familiarize themselves with
the types of systems installed in their area of
responsibility. They should also learn the
locations of these systems as well as the
capabilities and limitations of each type of
system.
46Review Questions
- 1. What are the functions of fire detection,
alarm, and suppression systems? - 2. What are the two general types of sprinkler
coverage? - 3. What is the function of control valves?
-
(Continued)
47Review Questions
- 4. What is the difference between a wet-pipe
system and a dry-pipe system? - 5. When should sprinkler control valves be
closed? -