Applied Harmonics Control of Harmonics - PowerPoint PPT Presentation

1 / 22
About This Presentation
Title:

Applied Harmonics Control of Harmonics

Description:

Applied Harmonics Control of Harmonics * * IEEE Standard 519-1992 Limit harmonic current injections from end users so that harmonic voltage distortion is tolerable. – PowerPoint PPT presentation

Number of Views:135
Avg rating:3.0/5.0
Slides: 23
Provided by: Charle385
Learn more at: https://sc.edu
Category:

less

Transcript and Presenter's Notes

Title: Applied Harmonics Control of Harmonics


1
Applied HarmonicsControl of Harmonics
2
IEEE Standard 519-1992
Harmonic Distortion Evaluations
  • Limit harmonic current injections from end users
    so that harmonic voltage distortion is tolerable.
  • Limit harmonic voltage (responsibility of
    utility).

3
customer under study
utility system
PCC
IL
other customers
customer under study
utility system
PCC
IL
other customers
4
  • End users are limited at PCC in terms of
  • individual harmonic components and
  • total demand distortion
  • Utility is mainly responsible for limiting
    voltage distortion at PCC
  • Evaluations
  • Measurement of currents injected by load (over
    one week period)
  • Calculation of frequency response of system
    impedances (using harmonic calculation software)

5
(No Transcript)
6
Table 6.1 Harmonic voltage distortion limits in
of nominal fundamental- frequency voltage
7
Table 6.2 Harmonic current limits
8
  • Ih is rms magnitude of individual harmonic
    current
  • Isc is the short-circuit current at PCC
  • IL is the fundamental component of the maximum
    demand current (average max demand over 12
    months)
  • Individual limits apply to odd-order harmonics,
    even order limits are at 25 of indicated value

9
  • For power converters with more than 6 pulses,
    where q pulse number, multiply limits in table
    6.2 by

10
Controlling harmonics
  • Control only when harmonics create a problem.
    Types of problems
  • load harmonic currents are too large
  • path for harmonic currents is too long
    electrically (too much impedance) producing
    voltage distortion or communication-line
    interference
  • response of system magnifies one or more harmonics

11
Options for control
  • Reduce magnitude of harmonic currents from load
  • Add filters to do one or more of these
  • short out (siphon off) the harmonic
  • block harmonic currents from entering part of the
    system
  • supply the harmonics locally
  • Modify the frequency response of the system by
    filters or other means

12
Reducing load harmonic current
  • Sometimes transformer connections can be changed,
    for example
  • phase shift on some transformers supplying
    6-pulse converters
  • delta windings block triplen currents
  • zig-zag transformers can supply triplens

13
Zig-zag transformer
14
Zig zag transformer
  • Place the transformer to supply balanced triplen
    harmonics (and any other zero-sequence currents)
    to load
  • This will unload zero sequence currents on
    circuits upstream of the ZZ transformer, with
    little or no effect downstream
  • Fault study results may be affected

15
Placement of ZZ transformer
a
b
c
I3
n
3I3
Unloads the neutral conductor upstream
16
Filtering
  • Shunt passive filter short-circuit harmonic
    currents close to their source
  • Series passive filter block harmonic currents
    from power delivery system (may cause large load
    voltage distortion)
  • Active shunt filter electronically supply
    low-order harmonics to a nonlinear load (used
    with simple passive filters for higher frequency
    components).

17
Passive Filters
  • Shunt passive filters are
  • notch filters, tuned to a specific harmonic
    frequency, or
  • high-pass filters

high-pass filter
notch filter
18
Modifying system frequency response
  • Add a shunt filter to the system
  • Add a reactor (e.g., in series with a pf
    correction capacitor) to de-tune system
  • Change pf correction capacitor size or placement,
    or remove capacitor bank entirely

19
Where to control harmonics
  • On utility system or end-user facility
  • utility system is more difficult to filter unless
    we can move or change the size of or reconnect a
    capacitor
  • end-user system may be easier to filter if we can
    access the feeder(s) where the harmonic currents
    are being produced

20
Filters
  • In-line reactors (or chokes) for ASD
  • Isolation transformers can help
  • Isolation transformers can be reconnected with
    different phase shifts

ASD
M
Xs
Xt
reactor 0-5 on ASD kVA
21
Isolation transformers X5
480 V bus
M
ASD
M
ASD
Approximates a 12-pulse converter with 6-pulse
converters by putting half on Delta-Delta
transformers and the half on Delta-Y. 12-pulse
has Ih 0 for h 5, 7
22
Harmonic studies
  • Perform harmonic studies when
  • a problem occurs, to find a solution
  • planning large capacitor bank installation on
    either utility or industrial system
  • planning installation of large nonlinear load
    such as adjustable speed motor drives (ASD)
  • designing a harmonic filter or converting a
    capacitor to a harmonic filter
Write a Comment
User Comments (0)
About PowerShow.com