Title: Applied Harmonics Control of Harmonics
1Applied HarmonicsControl of Harmonics
2IEEE Standard 519-1992
Harmonic Distortion Evaluations
- Limit harmonic current injections from end users
so that harmonic voltage distortion is tolerable. - Limit harmonic voltage (responsibility of
utility).
3customer under study
utility system
PCC
IL
other customers
customer under study
utility system
PCC
IL
other customers
4- End users are limited at PCC in terms of
- individual harmonic components and
- total demand distortion
- Utility is mainly responsible for limiting
voltage distortion at PCC - Evaluations
- Measurement of currents injected by load (over
one week period) - Calculation of frequency response of system
impedances (using harmonic calculation software)
5(No Transcript)
6Table 6.1 Harmonic voltage distortion limits in
of nominal fundamental- frequency voltage
7Table 6.2 Harmonic current limits
8- Ih is rms magnitude of individual harmonic
current - Isc is the short-circuit current at PCC
- IL is the fundamental component of the maximum
demand current (average max demand over 12
months) - Individual limits apply to odd-order harmonics,
even order limits are at 25 of indicated value
9- For power converters with more than 6 pulses,
where q pulse number, multiply limits in table
6.2 by
10Controlling harmonics
- Control only when harmonics create a problem.
Types of problems - load harmonic currents are too large
- path for harmonic currents is too long
electrically (too much impedance) producing
voltage distortion or communication-line
interference - response of system magnifies one or more harmonics
11Options for control
- Reduce magnitude of harmonic currents from load
- Add filters to do one or more of these
- short out (siphon off) the harmonic
- block harmonic currents from entering part of the
system - supply the harmonics locally
- Modify the frequency response of the system by
filters or other means
12Reducing load harmonic current
- Sometimes transformer connections can be changed,
for example - phase shift on some transformers supplying
6-pulse converters - delta windings block triplen currents
- zig-zag transformers can supply triplens
13Zig-zag transformer
14Zig zag transformer
- Place the transformer to supply balanced triplen
harmonics (and any other zero-sequence currents)
to load - This will unload zero sequence currents on
circuits upstream of the ZZ transformer, with
little or no effect downstream - Fault study results may be affected
15Placement of ZZ transformer
a
b
c
I3
n
3I3
Unloads the neutral conductor upstream
16Filtering
- Shunt passive filter short-circuit harmonic
currents close to their source - Series passive filter block harmonic currents
from power delivery system (may cause large load
voltage distortion) - Active shunt filter electronically supply
low-order harmonics to a nonlinear load (used
with simple passive filters for higher frequency
components).
17Passive Filters
- Shunt passive filters are
- notch filters, tuned to a specific harmonic
frequency, or - high-pass filters
high-pass filter
notch filter
18Modifying system frequency response
- Add a shunt filter to the system
- Add a reactor (e.g., in series with a pf
correction capacitor) to de-tune system - Change pf correction capacitor size or placement,
or remove capacitor bank entirely
19Where to control harmonics
- On utility system or end-user facility
- utility system is more difficult to filter unless
we can move or change the size of or reconnect a
capacitor - end-user system may be easier to filter if we can
access the feeder(s) where the harmonic currents
are being produced
20Filters
- In-line reactors (or chokes) for ASD
- Isolation transformers can help
- Isolation transformers can be reconnected with
different phase shifts
ASD
M
Xs
Xt
reactor 0-5 on ASD kVA
21Isolation transformers X5
480 V bus
M
ASD
M
ASD
Approximates a 12-pulse converter with 6-pulse
converters by putting half on Delta-Delta
transformers and the half on Delta-Y. 12-pulse
has Ih 0 for h 5, 7
22Harmonic studies
- Perform harmonic studies when
- a problem occurs, to find a solution
- planning large capacitor bank installation on
either utility or industrial system - planning installation of large nonlinear load
such as adjustable speed motor drives (ASD) - designing a harmonic filter or converting a
capacitor to a harmonic filter