Control%20System%20Instrumentation - PowerPoint PPT Presentation

About This Presentation
Title:

Control%20System%20Instrumentation

Description:

Control System Instrumentation Standard Instrument Signals Pneumatic (air pressure): 3 15 psig Electrical: 4 20 mA I/P or E/P transducer Range and Scale ... – PowerPoint PPT presentation

Number of Views:234
Avg rating:3.0/5.0
Slides: 38
Provided by: Preferr376
Category:

less

Transcript and Presenter's Notes

Title: Control%20System%20Instrumentation


1
Control System Instrumentation
2
Standard Instrument Signals
  • Pneumatic (air pressure) 3 15 psig
  • Electrical 4 20 mA
  • I/P or E/P transducer

3
Transducers and Transmitters
Chapter 9
  • Figure 9.3 illustrates the general configuration
    of a measurement transducer it typically
    consists of a sensing element combined with a
    driving element (transmitter).
  • Since about 1960, electronic instrumentation has
    come into widespread use.

4
Sensors The book briefly discusses commonly used
sensors for the most important process variables.
(See text.)
Transmitters
  • A transmitter usually converts the sensor output
    to a signal level appropriate for input to a
    controller, such as 4 to 20 mA.
  • Transmitters are generally designed to be direct
    acting.
  • In addition, most commercial transmitters have an
    adjustable input range (or span).
  • For example, a temperature transmitter might be
    adjusted so that the input range of a platinum
    resistance element (the sensor) is 50 to 150 C.

Chapter 9
5
Chapter 9
6
Chapter 9
7
Range and Scale Factor
8
(No Transcript)
9
Transfer Function Nonlinear Case
10
Chapter 9
11
  • Measurement / Transmission Lags
  • Temperature sensor
  • make as small as possible (location, materials
    for thermowell)
  • Pneumatic transmission lines
  • usually pure time delay, measure experimentally
    (no time delays for electronic lines) less
    common today compared to electronic transmissions.

Chapter 9
12
Transmitter/Controller
Chapter 9
May need additional transducers for Gm if its
output is in mA or psi. In the above case, Gc
is dimensionless (volts/volts).
13
Measurement Errors
  • Systematic errors
  • Drift slowly changing instrument output when
    input is constant.
  • Nonlinearity
  • Hysteresis or backlash
  • Dead band
  • Dynamic error
  • Random errors

14
Chapter 9
Figure 9.15 Nonideal instrument behavior (a)
hysteresis, (b) dead band.
15
Chapter 9
16
Chapter 9
17
Precision, Resolution, Accuracy and Repeatability
  • Precision can be interpreted as the number of
    significant digits in measurement, but more
    accurately it refers to the least significant
    digit which contains valid information, e.g.,
    0.01 in the present case. Therefore, 0.33 is more
    precise than 0.3.
  • Resolution is defined as the smallest change in
    the input that will result in a significant
    change in the transducer output.
  • Repeatability is /- 0.02 in the present case.
  • Accuracy is 0.39-0.250.14, i.e., maximum error.

18
Final Control Elements
  • The most-common manipulated variables to be
    adjusted are (1) energy flow rates, and (2)
    material flow rates.
  • Type (1) transducer heating element
  • Type (2) transducer control valve (pump drive,
    screw conveyer, blower, etc.)

19
Chapter 9
20
(No Transcript)
21
Control Valve Characteristics (Inherent)
22
Chapter 9
23

Chapter 9
24
Pressure Drop Across Control Valve Installed
On-Line
  • In practical applications, one must take other
    flow obstructions into account for actual valve
    performance.

25
(No Transcript)
26
Design Guideline
27
Chapter 9
28
(No Transcript)
29
Design Calculation for a Linear Valve
30
Rangeability (Turn-Down Ratio)
31
Example
32
Installed Valve Characteristics
  • Desired behavior the flow rate is a linear
    function of valve lift.
  • Let us assume that the control valve has linear
    trim and it is necessary to increase the flow
    rate. If ?p through exchanger did not change,
    then valve would behave linearly (true for low
    flow rates), since it takes most of ?p . For
    higher flow rates, ?p through exchanger will be
    important, changing effective valve
    characteristics (valve must open more than
    expected ? nonlinear behavior).

33
Linear Valve Behavior
34
Equal-Percentage Valve Characteristics
35
Chapter 9
36
Chapter 9
37
Control Valve Transfer Function
Write a Comment
User Comments (0)
About PowerShow.com