Title: Control%20System%20Instrumentation
1Control System Instrumentation
2Standard Instrument Signals
- Pneumatic (air pressure) 3 15 psig
- Electrical 4 20 mA
- I/P or E/P transducer
3Transducers and Transmitters
Chapter 9
- Figure 9.3 illustrates the general configuration
of a measurement transducer it typically
consists of a sensing element combined with a
driving element (transmitter). - Since about 1960, electronic instrumentation has
come into widespread use.
4Sensors The book briefly discusses commonly used
sensors for the most important process variables.
(See text.)
Transmitters
- A transmitter usually converts the sensor output
to a signal level appropriate for input to a
controller, such as 4 to 20 mA. - Transmitters are generally designed to be direct
acting. - In addition, most commercial transmitters have an
adjustable input range (or span). - For example, a temperature transmitter might be
adjusted so that the input range of a platinum
resistance element (the sensor) is 50 to 150 C.
Chapter 9
5Chapter 9
6Chapter 9
7Range and Scale Factor
8(No Transcript)
9Transfer Function Nonlinear Case
10Chapter 9
11- Measurement / Transmission Lags
- Temperature sensor
- make as small as possible (location, materials
for thermowell) - Pneumatic transmission lines
- usually pure time delay, measure experimentally
(no time delays for electronic lines) less
common today compared to electronic transmissions.
Chapter 9
12Transmitter/Controller
Chapter 9
May need additional transducers for Gm if its
output is in mA or psi. In the above case, Gc
is dimensionless (volts/volts).
13Measurement Errors
- Systematic errors
- Drift slowly changing instrument output when
input is constant. - Nonlinearity
- Hysteresis or backlash
- Dead band
- Dynamic error
- Random errors
14Chapter 9
Figure 9.15 Nonideal instrument behavior (a)
hysteresis, (b) dead band.
15Chapter 9
16Chapter 9
17Precision, Resolution, Accuracy and Repeatability
- Precision can be interpreted as the number of
significant digits in measurement, but more
accurately it refers to the least significant
digit which contains valid information, e.g.,
0.01 in the present case. Therefore, 0.33 is more
precise than 0.3. - Resolution is defined as the smallest change in
the input that will result in a significant
change in the transducer output. - Repeatability is /- 0.02 in the present case.
- Accuracy is 0.39-0.250.14, i.e., maximum error.
18Final Control Elements
- The most-common manipulated variables to be
adjusted are (1) energy flow rates, and (2)
material flow rates. - Type (1) transducer heating element
- Type (2) transducer control valve (pump drive,
screw conveyer, blower, etc.)
19Chapter 9
20(No Transcript)
21Control Valve Characteristics (Inherent)
22Chapter 9
23Chapter 9
24Pressure Drop Across Control Valve Installed
On-Line
- In practical applications, one must take other
flow obstructions into account for actual valve
performance.
25(No Transcript)
26Design Guideline
27Chapter 9
28(No Transcript)
29Design Calculation for a Linear Valve
30Rangeability (Turn-Down Ratio)
31Example
32Installed Valve Characteristics
- Desired behavior the flow rate is a linear
function of valve lift. - Let us assume that the control valve has linear
trim and it is necessary to increase the flow
rate. If ?p through exchanger did not change,
then valve would behave linearly (true for low
flow rates), since it takes most of ?p . For
higher flow rates, ?p through exchanger will be
important, changing effective valve
characteristics (valve must open more than
expected ? nonlinear behavior).
33Linear Valve Behavior
34Equal-Percentage Valve Characteristics
35Chapter 9
36Chapter 9
37Control Valve Transfer Function