Title: Discrimination of protection devices on installations
1Discrimination of protection devices on
installations
- Janet Roadway
- Product Manager, Power Breakers
2Topics of Discussion
- Explaining the terminology
- Degrees of discrimination
- Different techniques to achieve discrimination
- Backup protection
- Protection devices
- Any Questions?
3Protection - Basics
- Question Why do we use protection devices????
- Common Ans To prevent Faults
Wrong! Protection whether by fuse, circuit
breaker or relay cannot prevent faults from
happening. Only good design, high quality
components, careful installation, preventative
maintenance along with good working practices can
prevent major faults However, protection devices
can limit the damage and inconvenience caused if
faults occur.
4Protection - Overload
- What do we mean by a fault?
- Overload
- Operating condition in an electrically undamaged
circuit which causes an current to flow in excess
of the full load current - Example Starting condition during DOL start
- If this type of fault continues indefinitely
because of an anomolous operating condition.,
damage begins to occur creating.
5Protection Short Circuit
- What do we mean by a fault?
- Short Circuit
-
- Operating condition in an electrically damaged
circuit where there is an accidental or
intentional connection by a relatively low
resistance between two points of a circuit which
are normally at different voltages - This type of fault can generate high current
flows, arcing and fire if not cleared quickly
6Discrimination
- Coordinate devices to
- Guarantee safety for people and installations
- Identify and exclude only the zone affected by a
problem - Limiting the effects of a malfunction
- Reducing the stress on components in the affected
zone - Ensuring service continuity with good quality
supply voltage - Achieving a valid compromise between reliability,
simplicity and cost effectiveness
7Explaining the terminology
- Discrimination or Selectivity
- To make it possible to isolate a part of an
installation involved in a fault condition from
the overall system such that only the device
located immediately on the supply side of the
fault intervenes
8Discrimination
- Needs
- Fast Fault Detection
- Fast Fault Elimination
- Let-Through Energy Reduction
- High Fault Current Withstanding
9Explaining the terminology
10Degrees of discrimination
- Total Discrimination
- This means that the isolation described occurs
for all fault levels possible at each point of
the circuit
11Degrees of discrimination
t
A
B
Prospective Fault Current Icc
I
12Degrees of discrimination
- Partial Discrimination
- This means that above certain current levels
there is simultaneous operation of more than one
protection device
13Degrees of discrimination
t
A
B
Prospective Fault Current Icc
I
14Discrimination
- Traditional solutions
- Current discrimination
- Time discrimination
- Energy discrimination
- Zone (logical) discrimination
15Discrimination
- Current discrimination
- Discrimination among devices with different trip
threshold setting in order to avoid overlapping
areas. - Setting different device trip thresholds for
different hierarchical levels.
16Discrimination
- Current discrimination
- An example
17Discrimination
- Current discrimination
- Applications
- final distribution network with low
- rated current and low short-circuit current
- ACB chains
- Fault area short circuit and overload
- Discrimination limit current low
- Discrimination levels low
- Devices ACBs, MCCBs and devices with
time/current curves
(contactors with thermal relays, fuses ) - Feasibility discrimination study easy
- Customer cost low
18Discrimination
- Time discrimination
- Discrimination among devices with different trip
time settings in order to avoid overlapping areas - Setting different device trip delays for
different hierarchical levels
19Discrimination
Electronic release
L (Long delay)
S (Short delay)
I (IST)
Setting 0.9 Curve B Setting 1 Curve
A Setting 1 Curve A
Setting 8 Curve D Setting 10 Curve C
- Time discrimination
- An example
E4S 4000 PR111-LSI R4000 E3N 2500 PR111-LSI
R2500 S7H 1600 PR211-LSI R1600
Off Off Setting 10
20Discrimination
- Time discrimination
- Applications low complexity plant
- Fault area short circuit and overload
- Discrimination limit current low, depending
on the Icw of the upstream device - Discrimination levels low, depending on the
network - Devices ACBs, MCCBs and devices with adjustable
time curves - Feasibility discrimination study easy
- Customer cost medium
21Types of Discrimination
- Energy Discrimination
- Many Low Voltage protection devices such as
Circuit breakers and Fuses have the ability to
limit the peak of the current let through them to
a value lower than the prospective short circuit
peak. - Any protective device which clears short circuits
in less than 1/2 cycle of the sinusoidal wave
(i.e 10mS for 50Hz) will current limit to a
certain degree - Energy based discrimination is the only way to
determine true discrimination between
current-limiting devices
22Discrimination
- Energy discrimination
- Discrimination among devices with different
mechanical and electrical behaviour depending on
energy level - It is necessary to verify that the let-through
energy of the circuit-breaker upstream is lower
than the energy value needed to complete the
opening of the CB downstream
23Discrimination
- Energy discrimination
- An example
Time-currents Curve
24Discrimination
- Energy discrimination
- Applications medium complexity networks
- Fault area Short circuit only
- Discrimination limit current medium/high
- Discrimination levels medium, CBs size
dependent - Devices ACBs, MCCBs, MCBs Fuses
- Feasibility discrimination study medium
complexity - Customer cost medium
25Discrimination
- Zone discrimination
- Discrimination among devices in order to isolate
the fault zone keeping unchanged feeding
conditions of maximum number of devices - Zone discrimination is implemented by means of an
electrical interlock between devices
Zone 1
Zone 2
Zone 3
26Discrimination
- Zone discrimination
- Applications high complexity plant
- Fault area short circuit, overload, ground fault
- Discrimination limit current medium,
depending on
Icw - Discrimination levels high
- Devices ACBs, MCCBs with dialogue and control
features - Feasibility discrimination study complex
- Customer cost high
27Explaining the terminology
- Cascading or Backup protection
- Uses supply circuit breakers or fuses with
current limitation effects to protect downstream
devices from damage - The amount of energy let through (i2t) by the
supply device needs to be lower than that which
can be withstood without damage by the device on
the load side - By using this effect it is possible to install
devices downstream that have short circuit
breaking capacities lower than the prospective
short circuit current
28Back-up protection/Cascading
- Back-up protection or Cascading is recognised and
permitted by the 16th Edition of the IEE Wiring
Regulations 434-03-01 and is covered by IEC
364-4-437 standard
29Why Use Back-up Protection?
- Substantial savings can be made on downstream
switchgear and enclosures by using lower short
circuit ratings - Substantial reductions in switchgear volumes can
also result
30What about Discrimination?
- Backup protection should not be confused with
discrimination. - Backup protection does not infer discrimination
can be achieved but in practice, discrimination
is normally achieved up to the maximum breaking
capacity of the downstream device
BACKUP
Discrimination
GO!
WAIT!
CONTINUITY OF SERVICE
FAULT
FAULT DAMAGE
31Practical Example
- Problem
- Installation requires the use of Busbar rather
than cable to distribute electrical power. - Fault level calculations reveal 25kA prospective
fault level at the point of installation of
standard MCB distribution board
32Practical Example
- Solution -
- Using a standard Isolator as the distribution
board incoming device - all the MCBs would need
to be 25kA or above - Using an MCCB as the incoming device such as an
ABB Tmax T3N250TMD100, 6kA S200 MCBs could be
safely used
33A word of caution ...
- Back-up protection can only be checked by
laboratory tests and so only device combinations
specified by the manufacturer can be guaranteed
to provide co-ordination of this type.
34Types of protection available
- Fuses
- Miniature Circuit Breakers
- Moulded Case Circuit breakers
- Air Circuit breakers
35Typical fuse
- Ultra Reliable
- Standard Characteristic
- High current limitation effects
- High threshold on low overloads ( clears
overloads at approx 1.45x rated FLC)
Time (s)
36Fuseless technology
- Two main types-
- Thermomagnetic protection- MCB and lower rated
MCCB plus older type protection relays - Electronic protection Microprocessor based
relays fed from CTs either external to switches
or integral within a circuit breaker
37Thermomagnetic
- Offer thermal longtime overcurrent protection
using Bi-metal technology ( operates at 1.3x FLC) - Uses the magnetic effect of short circuit
currents to offer shorttime short circuit
protection
Thermal curve
Magnetic curve
38Electronic Relays
- Overcurrent functions such as-
- Long time overcurrent
- Short time instantaneous protection
- Short time time delayed protection
- Ground fault or Earth fault protection
39Electronic Relays
- Overcurrent functions such as-
- Long time overcurrent
- Short time instantaneous protection
- Short time time delayed protection
- Ground fault or Earth fault protection
40Protection releases general features
41Data logger a professional built-in fault
recorder.
-
- Data logger a professional built-in
fault recorder. - Standard in PR122 and PR123
- Recording of 8 measurements (currents and
voltages) - Configurable trigger (i.e. During a fault)
- Sampling frequency up to 4.800kHz
- Sampling time up to 27s
- Output data through SD-Pocket or TestBus2.
- Exclusive from ABB SACE.
42Conclusion
- So what is the secret to achieving a successful
discrimination study - The secret is to be aware of the capability of
the technology you are using and to design your
installation within the limits of the protection
you have chosen
43(No Transcript)
44Protection releases news on standard protection
functions
- Double S
- Used to obtain discrimination in critical
conditions - Double G
- Two different protection curves, one with the
signal coming from internal CTs and the other
from an external toroid - Dual Setting
- Two different set of protection parameters in
order to protect in the best way, two different
network configurations (e.g. normal supply and
emergency supply)
These features are available on PR123/P
45Protection releases news on standard protection
functions
- Double S
- low setting on S protection function due to the
settings on MV circuit-breaker - The circuit-breaker on LV side of the LV-LV trafo
needs high settings due to the inrush current
46Protection releases news on standard protection
functions
Without double S
47Protection releases news on standard protection
functions
With double S
48Protection releases news on standard protection
functions
- Double G
- Its possible to protect the network, with the
same protection release, against earth fault both
upstream and downstream the circuit-breaker - Restricted Earth Fault the fault is upstream the
LV circuit-breaker
49Protection releases news on standard protection
functions
- Double G
- Its possible to protect the network, with the
same protection release, against earth fault both
upstream and downstream the circuit-breaker - Restricted Earth Fault the fault is upstream the
LV circuit-breaker - Unrestricted Earth Fault the fault is downstream
the LV circuit-breaker
50Protection releases news on standard protection
functions
- Double G
- The combination of both Unrestricted and
Restricted Earth Fault protection is named
Source Ground Return. The new PR123/P is able
to detect and to discriminate both earth faults - If the fault is downstream the LV circuit-breaker
the PR123/P will trip Emax circuit-breaker
51Protection releases news on standard protection
functions
- Double G
- The combination of both Unrestricted and
Restricted Earth Fault protection is named
Source Ground Return. The new PR123/P is able
to detect and to discriminate both earth faults - If the fault is downstream the LV circuit-breaker
the PR123/P will trip Emax circuit-breaker - If the fault is upstream the LV circuit-breaker
the PR123/P will trip the MV circuit-breaker
52Protection releases news on standard protection
functions
- Dual setting
- It allows to program two different protection
parameter sets in order to adapt them to the
different network configurations - The most representative example is a network with
supply by the utility and by emergency generator - With dual setting the discrimination between CBs
is guaranteed in both network conditions
53Protection releases news on standard protection
functions
- Dual setting
- Normal network condition
- CB A gtgtgt closed
- CB B gtgtgt open
- Discrimination is guaranteed between A and C
54Protection releases news on standard protection
functions
- Dual setting
- Emergency network condition
- CB A gtgtgt open
- CB B gtgtgt closed
- Discrimination is not guaranteed between B and C,
due to the low settings (protection of the
generator) of C protection functions
55Protection releases news on standard protection
functions
- Dual setting
- Emergency network condition
- CB A gtgtgt open
- CB B gtgtgt closed
- Discrimination is guaranteed between B and C
thanks to the second set of protection parameters
56Protection releases advanced protection functions
Residual current
RC
D
Protection against directional short-circuit with
adjustable time-delay
Protection against phase unbalance
U
Protection against overtemperature (check)
OT
Protection against undervoltage
UV
Protection against overvoltage
OV
Protection against residual voltage
RV
Protection against reverse active power
RP
Thermal memory for functions L and S
M
Underfrequency
UF
Overfrequency
OF
57Protection releases measurements functions
Current (phases, neutral, earth fault).
Accuracy 1,5
Voltage (phase-phase, phase-neutral, residual).
Accuracy 1
Power (active, reactive, apparent) Accuracy
2,5
Power factor Accuracy 2,5
Frequency and peak factor Accuracy 0,1Hz
Energy (active, reactive, apparent,
meter) Accuracy 2,5
Harmonics calculation (display of waveforms and
RMS spectrum up to 40th _at_50Hz)
58Protection releases measurements functions
Current (phases, neutral, earth fault).
Accuracy 1,5
Voltage (phase-phase, phase-neutral, residual).
Accuracy 1
Power (active, reactive, apparent) Accuracy
2,5
Power factor Accuracy 2,5
Frequency and peak factor Accuracy 0,1Hz
Energy (active, reactive, apparent,
meter) Accuracy 2,5
Harmonics calculation (display of waveforms and
RMS spectrum up to 40th _at_50Hz)