Miniature Circuit Breakers (MCB) Multi 9 - PowerPoint PPT Presentation

About This Presentation
Title:

Miniature Circuit Breakers (MCB) Multi 9

Description:

Title: Miniature Circuit Breakers (MCB) Author: Training Division Last modified by: DJOKO LARAS BT Created Date: 4/18/2000 11:20:34 AM Document presentation format – PowerPoint PPT presentation

Number of Views:2187
Avg rating:3.0/5.0
Slides: 19
Provided by: Train69
Category:

less

Transcript and Presenter's Notes

Title: Miniature Circuit Breakers (MCB) Multi 9


1
Miniature Circuit Breakers (MCB)Multi 9
2
Definition
Main functions
  • Symbol
  • Protect cables against overloads and short
    circuits
  • Let the current flow without overheating on
    cables
  • Open and close a circuit under rated current
  • Protect against insulation faults (see earth
    leakage protection module)

Miniature circuit switch trip unit breaker
(MCB) 4
3
Definition
A Multi 9 circuit breaker has
  • A mechanical system to open and close the
    circuit
  • A bimetal strip to act against overloads
  • A magnetic trip to act against short circuits

Miniature circuit switch trip unit breaker
(MCB) 4
4
Definition
Main performances
  • It has standardized modular dimensions
  • 125Ao 50 kA o 440 V CA

It fits in your pocket... 4
5
Definition
  • Multi 9 standardo Multi 9 switchgear comes in
    9 mm pitch 4
  • The modular design meets 2 criteria
  • o mounting on a 35 mm symmetrical rail
  • dimensions - modules in widths of 17.5 mm
    0.5 - 0 - external part 45 mm - depth between
    55 and 70 mm

44 maxi
21.3
81
45maxi
35
width
60
10 maxi
symmetrical rail
external part
depth
6
The technology
Active parts
C60N
NC100 / NC125
terminal
terminal
bimetral strip
fixed contact
movingcontact
strip braid
moving contact
strip braid
magnetictrip
magnetic trip
strip braid
bimetal strip
load side terminal
load side terminal
4
7
Overload protection
  • A bimetal strip is used o to protect the
    cable against overloadso symbol
  • principle of the bimetal in a Multi 9
    circuit breaker 4

NC45
NC100 / NC125
bimetal
tripping bar
tripping bar
bimetal
screw calibration
strip braid
8
Overload protection
  • Thermal tripping curve
  • the "thermal" part of the tripping curve must
    be in accordance with the standard

t (s)
tripping
no tripping
destruction of bimetal
accuracy
LegendIn rated currentInd no tripping
currentId tripping current 4
I/In
In
Ind
Id
9
Overload protection
  • Temperature derating o our circuit breakers
    do not have temperature compensationo if the
    calibration temperature is different from the
    ambient temperature derating is required

Simultaneous multi-pole tripping 4
10
Short-circuit protection
Short-circuit current is given as RMS or
peak(Isc or Îsc)RMS Root Mean Square in
symmetrical DC(with PF I) Short-circuit
protection must limit thermal stress in the cable
in order to prevent cable damage (which may reach
vaporization of the copper in some cases)
Comments slide 29
11
Short-circuit protection
The arc in Multi 9 circuit breakers
NC45
NC100 / NC125
arcing horn
arcing horn
"By-pass" technique for the protection of
sensitive partsof the circuit breaker
DCbreaking is difficult
"By-pass" technique for the protection of
sensitive parts of the circuit breaker (magnetic
trip)
2 breaking techniques used by Multi 9 4
12
Short-circuit protection
Magnetic tripping curve
destruction of the solenoid
t (s)
tripping
no tripping
LegendInd no tripping currentId tripping
current
I/In
Ind
Id
Our curves are instantaneous tripping curves 4
13
The magnetic tripping levels with high inrush
currentlike LV/LV transformers
  • C Curveo 5 and 10 In control and protection
    of circuits with high short-circuit current in
    industrial and domestic distributions
  • D and K curves tripping betweno tripping 10
    to 14 In more particulary adopted for
    installations with high inrush currents like
    LV/LV transformers
  • Z curveo 2.4 to 3.6 In protection
    against electronic circuits
  • MA curveo 12 In protection only
    against short-circuit and high inrush
    currents such as motors, coil 4
  • B curve
  • o 3 and 5 In protectionlow short-circuit current
    generators

M
14
Marking
  • Side panel marking
  • Front panel marking

Circuit breaker marking is governed by strict
rules in accordance with the standards and
decisions made by the manufacturer 4
15
Choosing a circuit breaker
In conclusion
  • A Multi 9 circuit breaker is determined byo
    ratingo breaking capacity
  • number of poleso voltageo tripping curve
  • standardo frequencyo type of load 4

16
Auxiliaries C60
  • SD alarm switch
  • MX OF shunt trip o MN undervoltage release
  • 4 types of auxiliaries for our Multi 9 circuit
    breakerso OF indication switch

MXOF
OF
SD
C60
MN
44/3
51/3
54/3
52/3
53/3
54 mm maxi
The information is transmitted via a mechanical
link C60/NC100 and NC125 auxiliaries are not
compatible 4
17
Auxiliaries NC100 - NC125
  • SD alarm switcho MX OF shunt trip o MN
    undervoltage release
  • 4 types of auxiliaries for our Multi 9 circuit
    breakerso OF indication switch

NC100H
MXOF or Vigi
MN or
OF
SD
33/3
34/3
35/3
27/3
36/3
The information is transmitted via a mechanical
link C60/NC100 and NC125 auxiliaries are not
compatible 4
18
End presentation
Write a Comment
User Comments (0)
About PowerShow.com