Title: SEPAM Communications Troubleshooting


1
SEPAM Communications Troubleshooting
2
Power
  • Communications module not powered

3
Power
  • Communications module not powered

4
Terminating Jumper
5
Protocol
6
Modbus Wiring
  • 2-Wire RS-485
  • connects to and connects to -
  • 4-Wire RS-485
  • s and s are swapped
  • TX gt RX, TX- gt RX-, etc.

7
Modbus Configuration
  • Modbus Address, Parity, Baud Rate

8
Incorrect Sepam Port selection
  • Sepam 80 has dual comm and remote module ports

9
ION Master Connections
  • To communicate to an ION meter there are two
    communication port settings that need to be made.
  • Comm port on the meter needs to be set to Modbus
    Master
  • Modbus Master Options Module must have the comm
    port assigned to ModbusGate Connection

10
ION Master Connections (cont)
11
ION Master Connections (cont)
12
ION Master Connections (cont)
13
Common Wrench Errors
  • Wrench 1 (most common)
  • Typically CCA63x (CT module) is absent
  • I/O module is absent
  • Wrench 2
  • Typically caused by faulty wiring between remote
    module connection.
  • Wrench 3
  • MET148-2 (Temp Module) module is not available
  • Wrench 4
  • MSA141 (Analog Module) is not available
  • DSM303 (Remote Display) is not available
  • Wrench 5
  • MCS025 (Sync-Check) is not available
  • Wrench 10
  • CPU overload (Sepam 80 only) typically caused by
    excessively large Logipam program

14
Wrench 1 (Most Common)
15
Wrench 1
  • Normally caused by
  • CT module not attached to relay
  • I/O card is configured in the software but is not
    attached to relay
  • If you are unable to connect with SFT2841 it
    could indicate a major fault with the base unit
  • On Sepam 80 it could indicate a faulty memory
    cartridge

16
Verifying Cause of Error
  • IF you are able to connect with the software

17
Questions?