Title: Cleanroom Energy Benchmarking Results
1(No Transcript)
2LBNLs high-tech buildings initiative a wide
breadth of activities
2
3Energy intensive high-tech buildings
3
4 Cleanrooms The Opportunity
- Up to 100x more energy-intensive than typical
buildings (Class-1 cleanroom can be up to 600
ac-h) - Promising Measures
- Govern ventilation by performance rather than
rules of thumb - Improved process load projection
- More efficient HVAC
- Low-pressure-drop design
4
5 Current cleanroom activities
- Benchmarking and Best Practices
- Fan-filter unit test procedure
- Demand-controlled filtration
- Minienvironments
Cleanroom Measured Electricity End-use
5
6 We see a wide range of efficiencies For example
cleanroom recirculation systems
Choice of air delivery strategy strongly
influences energy intensity
Avg Pressurized Plenum
Ducted FFU
6
7 Wide range of efficiencies For example make-up
air systems
Choices in the design of air systems strongly
influences energy intensity
7
8 Wide range of efficiencies For example
fan-filter units
- Efficiencies vary by a factor-of-four
- Need for test standards
8
9 Working with benchmark results
- Benchmarking Best Practices
- Wide variation in performance
- Benchmarking results being reviewed to identify
best practices - Efficiency opportunity was found at each
benchmarking site (see case study reports)
Chiller performance ranged from 0.5 to 5 kW/ton
over range of 5 to 50 tons
Air-change rates suggest possible reduction
without compromising process)
9
10 Laboratories the opportunity
- Labs are up to 5x as energy-intensive as typical
buildings fume hoods use gt3x as much energy as
typical home - Promising Measures
- Low-pressure-drop design
- Ventilation and hood flows governed by
performance rather than rules of thumb
Berkeley Hood installed at UCSF
10
11Laboratories - current LBNL activities
- Benchmarking and Best Practices
- Laboratories for the 21st Century
- High-Performance Fume Hood
- Working towards CAL/OSHA acceptance
- Side-by-side testing including non-standard
dynamic tests - Demonstrations in three industrial settings
LBNLs Geoffrey Bell performing dynamic
side-by-side tests comparing 6-foot Berkeley Hood
with a standard hood.
11
12What are the big opportunities?
- Right sizing systems
- Low pressure drop systems
- Low face velocity in air handlers
- Low pressure drop filters
- Large duct/plennum
- Air change rates
- Lower airflow in fume hoods
- Variable speed chillers
- Minimize or eliminate reheat
- Free cooling for process loads
- Energy efficient Uninterruptable Power Supplies
- Recirculation air setback
12
13LBNL high-tech buildings website