Context at P8
Last slide presented at LMC early May 2012
gt Delicate operation, 12hrs before getting to
the long 36 hrs recovery
2
21Sept12 - 1.8K unit for sector 81(78)
Faulty Heater 50 of flow generated
stopped, getting below minimum tolerated by CCs
Impossible to re-connect at low pressure without
it!
Decision to fill the pumping line to a pressure
compatible with reconnection at higher pressure
without the heater, But higher pressure means as
well higher temperature and long recovery!
3
Milestones
  • During TS3, several strange effects on some
    instrumentation for this sub-system. Team
    investigating in cavern Friday when complete stop
    of 1.8K unit at 16h. 24VDC power unit found down,
    exchanged (medium term situation since 2010 with
    2-3 failures/year, type test ready, global
    upgrade gt LS1)
  • Restart on tracks with sectors connected when
    400V heater failure stopped it again at 22h. As
    2nd time in 1 year, decision to go slowly without
    it (investigation to be foreseen when possible)
  • 12hrs of delicate operation with control
    algorythm not correctly described, well mastered
    Saturday noon
  • 36hrs of recovery for 2 sectors left without
    cooling for 18hrs

We will validate the 2nd refrigerator in the
coming days, and get
organised for diagnostic and repair of the heater
(window t.b.d)