BOILER SAFETY VALVES - PowerPoint PPT Presentation

1 / 12
About This Presentation
Title:

BOILER SAFETY VALVES

Description:

BLOWDOWN - THE PRESSURE DROP BETWEEN LIFT AND RESEATING OF THE SAFETY VALVE ... AFTER BEING GAGGED FOR HYDRO. IF LIFTED BY WATER DURING HYDRO WHEN NOT GAGGED ... – PowerPoint PPT presentation

Number of Views:3482
Avg rating:3.0/5.0
Slides: 13
Provided by: steameng
Category:

less

Transcript and Presenter's Notes

Title: BOILER SAFETY VALVES


1
BOILER SAFETY VALVES
  • 62B-206

2
DEFINITIONS
  • LIFT OR POP - REFERS TO THE OPENING OF THE SAFETY
    VALVE
  • BLOWDOWN - THE PRESSURE DROP BETWEEN LIFT AND
    RESEATING OF THE SAFETY VALVE
  • RESEAT - CLOSING OF THE SAFETY VALVE WITHOUT
    CHATTERING

3
DEFINITIONS CONT
  • SIMMERING - STEAM THAT LEAKS BY THE SEAT AND DISK
    PRIOR TO THE LIFTING OF THE SAFETY VALVE.
    ACCEPTABLE CONDITION WITHIN 1 OF LIFTING
    PRESSURE.
  • CHATTERING - THE RAPID POPPING AND RESEATING OF
    THE SAFETY VALVE

4
DEFINITIONS CONT
  • GAG - A MECHANICAL DEVICE PLACED ON THE SAFETY TO
    PREVENT THE SAFETY FROM LIFTING DURING TESTING
    AND BOILER HYDROSTATIC TESTS

5
REQUIRED TESTING
  • IAW PMS
  • WHEN REMOVED OR REWORKED
  • AFTER BEING GAGGED FOR HYDRO
  • IF LIFTED BY WATER DURING HYDRO WHEN NOT GAGGED
  • ANY SIGNS OF TAMPERING

6
TESTING HOW ITS DONE
  • LIGHT OFF THE BOILER
  • PLACE GAGS ON TOP OF BOILER TO WARM AND EXPAND
  • PLACE THE BOILER ONLINE WITH EQUIPMENT NECESSARY
    TO SUPPORT SETTING SAFETIES

7
ONLINE
ECONO- MZER
MAIN STEAM STOP
OPEN
BOILER
LOCKED OPEN
AUX STEAM STOP
OPEN
8
TESTING CONT
  • ENSURE BOILER WATER CHEMISTRY IS WITHIN STANDARDS
  • WHEN STEAM PRESSURE 100 -200 PSI BELOW LOWEST
    SAFETY VALVE PLACE GAGS ON SAFETIES. (EXCEPTIONS
    DO NOT GAG HIGHEST DRUM SAFETY)

9
TESTING CONT
  • TEST/SET HIGHEST SET DRUM VALVE
  • REMOVE GAG NEXT LOWER SET VALVE AND TEST/SET.
  • REMOVE GAG FROM SUPERHEATER SAFETY TEST/SET
    SUPERHEATER SAFETY.
  • ONCE PILOT VAVLE SET, TEST PILOT SUPHERHEATER
    COMBO.

10
MLOCS
  • HAND EASING GEAR - CHECK CLEANLINESS,
    LUBRICATION, CABLES PULLEYS AND GEARBOXES FREE TO
    MOVE
  • FORK LEVER - CHECK CLEARANCE USUALLY 1/16 SET
    IAW MANUFACTURES TECHNICAL MANUAL

11
MLOCS
  • LOCKS AND SEALS - CHECK FOR SIGNS OF TAMPERING
  • VISUAL

12
BOILER SAFETY VALVES