Title: 2003 IBC
12003 IBC Structural Provisions, Scope and
Organization with Florida AmendmentsCourse No.
0004824
- Based on the 2003 International
- Building Code
2Course Introduction
3Welcome
4Overview
- Scope
- Highlights
- Florida Amendments
5Objectives
- Explain the organization of the various chapters.
- Identify and explain key code concepts of each.
- Explain the primary differences between the
various chapters.
6Chapter 11 Accessibility
- 2005 Supplement Changes
- Reformat Table 11 - 9.2
- Figure 28 Remove the arrow on the bottom of the
middle figure.
7Part 1 Chapter 12 Interior Environment
8Scope
- Establishes minimum conditions for the interior
environment of a building, including the size of
spaces, light, ventilation and noise intrusion.
9Performance Methods
- Ventilation (s. 1203).
- Mechanical ventilation. As per the FMC or
national ventilation through windows, doors,
louvers or other openings to the outside minimum
openable area must be 4 of the floor area. (s.
1203.4) - Bathrooms. Rooms containing bathtubs, showers,
spas, etc. must be mechanically ventilated as per
the FMC. (s. 1203.4.2.1)
10Performance Methods
- Temperature Control. (s. 1204)
- Interior spaces intended for human occupancy must
be provided with active or passive space heating
system capable of maintaining indoor temperature
of 68oF. (s. 1204.1)
11Performance Methods
- Sound Transmission. (1207)
- Air-borne sound common interior walls, partitions
and floor/ceiling between adjacent dwelling units
and between dwellings units etc. must have stc
not less than 50 for air-borne noise as per ASTM
E90. (s. 1207.2) - Structural Borne Sound. Floor/ceiling assemblies
between dwelling units etc. must have an impact
insulation class (IIC) of not less than 50 per
ASTM E 492. (s. 1207.3)
12Performance Methods
- Lighting. (s. 1205)
- Natural light by means of exterior glazed opening
(8 floor area) (s.1205.2) or - Artificial light (10 footcandles/107 lux). (s.
1205.3) - Stairway illumination within dwelling units and
exterior (minimum of 1 footcandle /10 lux) (s.
1205.4)
13Prescriptive Methods
- Interior Space Dimensions Habitable spaces.
(s. 1208) - Minimum room width (not less than 7 feet in any
plan dimension). (s. 1208.1) - Minimum ceiling height (7feet 6 inches),
bathrooms, toiletrooms, kitchens, storage rooms,
and laundry rooms (not less than 7 feet) (s.
1208.2) - Room area. At least one room (? 120 ft 2), other
rooms (? 70 ft 2), and kitchen (? 50 ft 2). (s.
1208.3)
14Prescriptive Methods
- Surrounding materials. (s. 1210)
- Floor.
- Must be a smooth, hard, nonabsorbent surface that
extends upward onto the walls at least 6 inches
in other than dwelling units toilet and bathroom
floors. (s.1210.1) - Walls.
- Within 2 feet of urinals and water closets, must
have smooth, hard nonabsorbent surface to a
height of 4 feet above the floor. Exception
toilet rooms not accessible to the public and
have not more than one water closet. (s. 1210.2)
15Prescriptive Methods
- Surrounding materials.
- Showers.
- Shower compartments and walls above bath tubs
with installed shower heads must be finished with
a smooth nonabsorbent surface to a height not
less than 70 inches above the inlet. (s. 1210.3)
16Chapter 13 Energy Efficiency
17Note
- Similar to the 2001 FBC with the exception of
Commercial Building Compliance which has been
updated to the ASHRAE 90.1-99. (For more
information, recommend reading the Energy Code
Training Course.)
18Chapter 13 Energy Efficiency
- Section 13-301 Change to read as shown
- ASTM C835-95 (1999) Standard Test Method for
Total Hemispherical Emittance of Surfaces From
20o C to 400o C 404.1.C.1 Table 6C-2
19Chapter 13 Energy Efficiency
Appendix 13-D Form 600A-Central Change to read as
shown
COMPONENT DESCRIPTION COMPONENT DESCRIPTION AREA BASE WINTER POINT MULT BASE WINTER POINTS
C E I L I N G Under Attic Or Single Assembly 0.64 2.13
C E I L I N G BASE CEILING AREA EQUALS AREA DIRECTLY UNDER CEILING, AS BUILT AREA EQUALS ACTUAL CEILING SQUARE FOOTAGE BASE CEILING AREA EQUALS AREA DIRECTLY UNDER CEILING, AS BUILT AREA EQUALS ACTUAL CEILING SQUARE FOOTAGE BASE CEILING AREA EQUALS AREA DIRECTLY UNDER CEILING, AS BUILT AREA EQUALS ACTUAL CEILING SQUARE FOOTAGE BASE CEILING AREA EQUALS AREA DIRECTLY UNDER CEILING, AS BUILT AREA EQUALS ACTUAL CEILING SQUARE FOOTAGE
Portions of Table not shown unchanged.
20Part 2 Chapter 14 Exterior Walls
21Scope
- Provides the minimum requirements for exterior
wall coverings including the minimum regulations
for materials and various wall veneers.
22Performance Requirements Highlights
- Weather protection. (s. 1403.2)
- Flashing where applicable water-resistive
barrier behind the exterior veneer, if necessary,
with the exception for concrete or masonry walls
and means for draining water that enters the
assembly exceptions if proven through testing.
(s. 1405.3) - Modifies 1403.2 to require all exterior finishes
to be applied in accordance with manufacturers
specifications or installation instructions.
23Performance Requirements Highlights
- Vapor retarder.
- Exception other approved means, and concrete and
masonry exterior walls constructed as per
Chapters 19 and 21.(s.1403.3)
24Performance Requirements Highlights
- 1403.9 Drained wall assembly over mass wall
assembly. Where wood frame or other types of
drained wall assemblies are constructed above
mass wall assemblies, flashing or other approved
drainage system shall be installed as required by
s. 1405.3.
25Performance Requirements Highlights
- 1404.2 Water-resistive barrier. Exterior walls of
frame construction receiving a veneer shall be
provided with a water-resistive barrier. A The
water resistive barrier shall be a minimum of one
layer of No. 15 asphalt felt, complying with ASTM
D 226 for Type 1 felt, shall be attached to the
sheathing, with flashing as described in Section
1405.3, in such a manner as to provide a
continuous water-resistive barrier behind the
exterior wall veneer.
26Performance Requirements Highlights
- 1404.2.1 Where cement plaster (stucco) is to be
applied to lath over frame construction, measures
shall be taken to prevent bonding between the
cement plaster and the water resistive barrier. A
bond break shall be provided between the water
resistive barrier and the cement plaster (stucco)
consisting of one of the following - 1. Two layers of an approved water resistant
barrier or (continued)
27Performance Requirements Highlights
- ( cont.)
- 2. One layer of an approved water resistant
barrier over an approved plastic house wrap, or - 3. Other approved methods or materials applied in
accordance with the manufacturers installation
instructions.
28Performance Requirements Highlights
- Materials. (s.1404)
- Water resistive barriers one layer No. 15
asphalt felt as per ASTM D 226 for Type I felt
aluminum siding, AAMA 14 oz vinyl siding, ASTM
D3679 fiber cement siding, ASTM C 1186.
(s.1404.2) - Wall covering/installation. (s. 1405)
- Table 1405.2, minimum thickness of weather
coverings.
29(No Transcript)
30Performance Requirements Highlights
- Flashing. (s. 1405.3)
- At all perimeters of exterior doors and windows,
penetrations, exterior wall intersections with
roofs, porches, decks, etc. - Exterior windows and doors (s. 1405.12)
31Prescriptive Highlights
- Combustible materials on the exterior side of
exterior walls (s. 1406) - Veneers.
- Anchored masonry veneer must be as per Section
6.1 and 6.2 of ACI 530/ASCE 5/TMS 402 MCM system
limitation.(1405.5) - Aluminum siding must be designed as per Chapter
23 and AAMA 1402.(s1404.5.1) - Vinyl siding must be in accordance with ASTM D
3679. (s. 1405.13) - Fiber cement siding must conform to ASTM C
1186.(s1404.10)
32Florida Amendments
- Provisions have been added to include
requirements for buildings located in the HVHZ. - A provision with exceptions has been added for
the control of and inspection for termites. - Seismic provisions have been removed.
- Responsibility for floodplain management
construction standards has been delegated to
local jurisdictions.
33Part 3 Chapter 15 Roof Assemblies and Rooftop
Structures
34Scope
- Regulates the materials, design, construction
and quality of roofs and roof structures for all
buildings and structures.
35Performance Highlights
- Weather protection. (s. 1503)
- Roof decks must be covered as required by the
code. (s. 1503.1) - Flashing must be installed at wall and roof
intersections. (s. 1503.2) - Editorial corrections to Table 1503.2
- Metal flashing must be corrosion resistant. (s.
1503.2.1) - Roof drainage as per the Plumbing Volume. (s.
1503.4)
36Performance Highlights
- Wind resistance of roofs. (s. 1504.1)
- Roof decks and covering must be designed for wind
loads as per Chapter 16. Roof system with
building modified bitumen, fully adhered or
mechanically attached, single-ply through
fastened metal panel roof systems, etc. must be
tested to FM4450, FM4470, UL 580 or UL 1897. (s.
1504.3.1)
37Performance Highlights
- Materials. (s. 1506)
- Metal panel roof system, test to UL 580 or ASTM E
1592. (s1504.3.2) - Product identification. Roof covering materials
delivered in a package must be labeled. (s.
1506.4)
38Prescriptive Highlights
- Asphalt shingles. (s. 1507.2.5)
- Slope 212 or greater. (Table 1507.2)
- Slope 212 up to 412 double underlayment
required. (Table 1507.2) - Metal roof panels. (s. 1507.4)
- Apply to solid or closely fitted deck except as
designed. (s.1507.4.1) - Slope 812 minimum for lapped, nonsoldered seams
without sealant. - Slope ½12 minimum for lapped, nonsoldered seams
with sealant. - Slope ¼12 minimum for standing seams.(1507.4.2)
39Prescriptive Highlights
- Sections 1507.3.7, 1507.3.8, and 1507.3.9
modified to correct name of standard. - FRSA/TRIRTI 07320.
40Prescriptive Highlights
- Metal roof panels continued.
- Standards.
- Roof covering systems with supporting structural
members as per Chapter 22. (1507.4.3) - Metal-sheet roof coverings installed over
structural decking shall comply with Table
1507.4.3. - Attachments as per manufacturers recommendations
or s. 1507.4.4 - Underlayment as per manufacturers
recommendations. (s1507.4.5)
41Prescriptive Highlights
- High wind attachment.
- For areas where the basic wind speed is 110 mph
or greater, fastening method must be tested as
per ASTM D 3161 modified to meet wind speeds of
110 mph, or TAS 107. - Clay and concrete tile.
- Deck slope as per FRSA/RTI 07320.
- Underlayment ASTM D 226 Type II ASTM D 2626
ASTM D 1970 or ASTM D 6380.
42Prescriptive Highlights
- High wind attachment continued.
- Low-slope roofs. Underlayment shall be a minimum
of two layers. - High-slope roofs Underlayment shall be a minimum
of one layer. - Fasteners corrosion resistant and not less than
11 gage, or 5/16 in head. Attachment as per
FRSA/RTI installation manual.
43Prescriptive Highlights
- Reroofing. Must comply with Chapter 15. (s.
1510) - Section 1507.2.8 high wind attachment.
- gt 110 mph underlayment must be applied with
corrosion resistant fasteners as per
manufacturer. - Fasteners must be applied along the overlap at a
maximum spacing of 36 inches on center. - Section 1507.2.9.2.
- Open valley.
- Closed valley.
- Section 1507.2.9.3.
- Drip edge.
- Overlap minimum 2 inches.
44Prescriptive Highlights
- Reroofing continued.
- Structural components must be able to support the
new materials as required by the manufacturer.
(s. 1510.2) - Do not use 4 fasteners per strip shingle or two
fasteners per individual shingle. - Must also comply with the FEBC.
45Florida Amendments
- Florida specific changes were made to numerous
sections. - Changes were made to remove snow and seismic
provisions. - Revised s. 1503.2.1 Location of flashing, to
provide exception for hip and ridge junction and
around roof openings. - Renumbered Table 1507.2.9.2 as Table 1503.2 and
renamed the table Metal Flashing Material for
consistency with the 2001 FBC. - Section 1503.4.2, added provisions for scuppers
similar to those of the 2001 FBC. - Added Section 1503.6, Protection against decay
and termites. Similar to 2001 FBC. - Provisions have been added governing structures
located in the HVHZ.
46- Section 1507.9.2 Change to read as shown
- 1507.9.2 Deck slope. Wood shakes shall only be
used on slopes of four three units vertical in 12
units horizontal (33-percent slope) or greater.
47Florida Amendments
- Florida specific changes were made to numerous
sections continued. - Section 1504.6 Physical properties, was amended
to add ASTM G 153. - Section 1507.2.3 Underlayment. Asphalt shingle
was amended to allow ASTM D Type II and ASTM D
4869 Type II. - Section 1507.2.6.1 was added to require nail
components of plastic cap nails to meet the
corrosion resistance requirement of s. 1507.2.6.
- Section 1507.2.7 Attachment, was revised to
allow special fastening methods for asphalt
shingle as per TAS 107. - Section 1507.2.9.1 was amended to provide
specific installation requirements for Base and
Counter Flashing.
48Florida Amendments
- Florida specific changes were made to numerous
sections continued. - Section 1507.2.9.3 Drip edge, was revised to
allow drip edge at eaves to be installed either
over or under the underlayment with the condition
that if installed over the underlayment, there
shall be a minimum of 2 in. width of roof cement
installed over the drip edge flange. - Section 1507.3.1 Deck requirements, clay and
concrete tile, was revised to allow concrete and
clay tile to be installed over structurally
spaced sheathing boards as specifically designed
and tested as per s. 1609.7.2.
49Florida Amendments
- Florida specific changes were made to numerous
sections continued. - Section 1507.3.2 Deck slope, clay and concrete
tile, was amended to require installation as per
FRSA/RTI 07320. - Section 1507.3.3 Underlayment, clay and concrete
tile, was revised to require compliance with ASTM
D 1970 or ASTM D 6380. - Section 1507.3.5 Underlayment, clay and concrete
tile, was revised to require compliance with ASTM
C 1492. - Section 1507.3.7 Attachment s.1507.3.8
application, clay and concrete tile, was revised
to require compliance with FRSA/RTI 07320.
50Florida Amendments
- Florida specific changes were made to numerous
sections continued. - Section 1507.4.4 Attachment, metal panels, was
revised to allow aluminum-zinc coated fasteners
are acceptable for aluminum-zinc coated roofs. - Section 1507.4.5 Underlayment, was added to
require installation as per manufacturers
guidelines. - Sections 1507.5.3 and 1507.6.3 Underlayment,
metal roof shingles and mineral surfaced roll
roofing, were revised to allow compliance with
ASTM D 226 Type II and ASTM D 1970.
51Florida Amendments
- Section 1521.4 Change to read as shown
- 1521.4 Reserved. Not more than 25 of the total
roof area or roof section of any existing
building or structure shall be repaired, replaced
or recovered in any 12 month period unless the
entire existing roofing system or roof section is
replaced to conform to requirements of this code.
52Part 4 Chapter 16 Structural Loads
53Scope
- Prescribes minimum structural loading
requirements for use in the design and
construction of buildings and structures with the
intent to minimize hazard to life and improve the
occupancy capability of essential facilities
after a design level even or occurrence.
54Highlights
- Construction documents. (s.1603)
- Must show size, section, and relative locations
of structural members etc., floor live load, roof
live load, wind design data, special load, and s.
1603.3 live loads posted. (s. 1603.1) - General design requirements. (s. 1604)
- Method strength design, load and resistance
factor design, empirical design, or conventional
construction method, and allowable stress design.
55Highlights
- Loads (s. 1605 -1607)
- Section 1609 wind loads.
- Performance, Chapter 6 of ASCE 7-98
- Prescriptive methods, low rise provisions SSTD
10, WFCM, FCPA, SPPC. (s. 1609.6) - Section 1609.6 is identical to s.1606.2 of the
2001 FBC.
56Highlights
- Section 1609 Change figure title to read as
shown - Figure 1609.6B 1606.6B Main Wind Force Loading
Diagram.
57Florida Amendments
- Removed all seismic provisions.
- Removed all snow provisions.
- Factors E and S have been removed from all
applicable applications. - Provisions for buildings in the HVHZ have been
added.
58Florida Amendments
- Table 1604.3, Deflection limits, was revised to
address members supporting screen surface. - Table 1604.5, Importance factors, was revised to
add screen enclosures. - Section 1605.3.1.1 Load reduction, was revised to
clarify when increase in allowable stress may be
permitted for consistency with the 2001 FBC. - Section 1609, Wind load, was replaced with
Section 1606 of the 2001 FBC.
59Part 5 Chapter 17 Structural Tests and Special
Inspections.
60Scope
- Gives provisions for quality, workmanship,
testing and labeling of all materials used in the
construction of buildings and structures.
61Performance Highlights
- Approvals (s. 1703)
- Establish provisions and criteria for an
Approved Agency involved in conducting tests or
furnishing inspection services. When such agency
has been approved, - (1) must be independent, (s. 1703.1.1)
- (2) must have adequate equipment, (s.1703.1.2)
- (3) must have experienced personnel. (s. 1703.3)
62Performance Highlights
- Labeling (s. 1703.5)
- Establish criteria for labeling.
- Must be an approved agency.
- The approved agency must test a representative
sample of the product. (s. 1705.1) - The approved agency must maintain records and
must perform periodic inspections. (s.1703.5.2) - Label information (s. 1703.5.3)
- Manufacturers identification
- Model number, etc.
63Performance Highlights
- In-situ load tests (s. 1713)
- Whenever there is a doubt as to the structural
stability of a completed building - An engineering assessment must be required.
- If inadequate, then load tests must be performed.
- Preconstruction load tests (s.1714)
- Requires structural adequacy be predetermined
based on test criteria when the physical
properties of materials and methods of
construction can not be designed by an approved
engineering analysis or they do not comply with
the applicable material design standards listed
in the code.
64Florida Amendments
- Special inspections provisions have been deleted.
- Quality assurance for wind requirements has been
deleted. (Already covered by the Threshold
Buildings law.) - All seismic provisions have been omitted.
65Florida Amendments
- Structural observation provisions have been
deleted. - Section 1714.5 Exterior window and door
assemblies, was completely revised for
consistency with the 2001 FBC. - Glass strength provisions have been added.
Exterior window and door requirements have been
changed.
66Florida Amendments
- 1714.5.2.1 Testing and labeling.
- Editorial correction of spelling of word approval
Approval Approal - Section 1714.5.2.1.1 Change to read as shown
- 1714.5.2.1.1 Test and labeling of skylights.
- Exterior skylights shall be tested by an approved
independent testing laboratory, and shall be
labeled with an approved label identifying the
manufacturer, performance characteristics and
approved product evaluation entity to indicate
compliance with the requirements of the following
specification ( Cont)
67Florida Amendments
- (Cont.)
- AAMA/WDMA 101/IS2/NAFS Voluntary Performance
Specification for Windows, Skylights and Glass
Doors AMA/WDMA 1600/IS7, Voluntary Specification
for Skylights or TAS 202 (HVHZ shall comply with
TAS 202).
68Florida Amendments
- Section 1714.5.3 Change to read as shown
- 1714.5.3 Exterior door assemblies. Exterior door
assemblies not covered by Section 1714.5.2,
1715.4.2 or Section 1714.5.3.1 shall be
tested.(remaining text unchange
69Florida Amendments
- 1714.7 Add a new section to read as shown
- 1714.7 Installation instruction for exterior
windows and doors. Windows and doors shall be
installed in accordance with the manufacturers
installation instruction.
70Part 6 Chapter 18 Soils and Foundations
71Scope
- Provides the minimum requirements for the
design, construction and resistance to water
intrusion of foundation systems for buildings and
other structures.
72Performance Method Highlights
- Foundation and soils inspection (s. 1802)
- In areas likely to have expansive soil, a soil
test are required. (s. 1802.2.2) - If waterproofing is not provided, subsurface soil
investigation is required to determine the depth
the existing ground water table. (s. 1802.2.3) - Pile and pier foundations must be installed on
the basis of a foundation investigation and
report. (s. 1802.2.4) - Soil classification must be based on observation
and any necessary test pits, etc. (s. 1802.3) - Retaining Walls
73Prescriptive Method Continued
- Allowable load-bearing values of soils (s. 1804)
- Table 1804.2 provides for prescriptive
load-bearing values to be used with the allowable
stress design load combination. (s. 1804.2) - Requires calculations for lateral sliding
resistance. (s. 1804.3)
74Prescriptive MethodHighlights
- Section 1803.3 Site grading. Ground immediately
adjacent to the foundation must be sloped away
from the building at a slope of 120. - Section 1805.4.1 The minimum of footings must be
12 inches. - Section 1805.5.7 Pier is permitted to be used to
support light-frame construction not more than
two stories in height.
75Prescriptive MethodHighlights
- Section 1805.8.2 Slab-on-ground must be designed
and constructed in accordance with WRI/CRSI
Design of Slab-on-Ground Foundations or PTI
Design and Construction of Post-Tensioned
Slabs-on-Ground. - Section 1808 Pier and Pile Foundations must be
designed and installed on the basis of a
foundation investigation unless sufficient data
upon which to base the design and the
installation is available.
76Prescriptive Method Continued
- Footing and foundations (s. 1805)
- Must be building on undisturbed soil, compacted
fill materials, or CLSM. (s. 1805.1) - The minimum depth of footings below the
undisturbed ground surface must be 12 inches. (s.
1805.2) - The minimum width must be 12 inches (s.
1805.4.1). - Footing setback from descending slope surface
(Figure 1805.3.1) - Pier (s1805.5.7)
- Slab-on-ground foundations (s1805.8.2)
77Figure 1805.3.1
78Florida Amendments
- All seismic and snow provisions have been
removed. - Responsibility for requirements for flood hazard
areas and grading and fill have been deferred to
the individual jurisdictions.
79Florida Amendments
- Special requirements for buildings in the HVHZ
have been added. - All provisions governing retaining walls have
been replaced with those from the 2001 FBC. - Provisions governing termite protection have been
added from the 2001 FBC.
80Part 7 Chapter 19 - Concrete
81Scope
- Sets the minimum accepted practices that apply
to the design and construction of buildings or
structural components using concrete.
82Performance Highlights
- Specifications for tests and materials (s. 1903)
- ACI 318-02
- Concrete quality, mixing and placing (s. 1905)
- Concrete strength must not be less than 2,500 PSI
(s. 1905.1.1) - Preparation before concrete placement must
include debris removal, forms must be properly
coated, and reinforcement must be clean, etc.
(s.1905.7) - Ready-mixed concrete must be in accordance with
ASTM C 94 or ASTM 685 (s. 1905.8) - Curing. Other than high early strength, concrete
must be maintained above 50oF and in a moist
condition for at least the 1st seven days after
placement. (s. 1905.11)
83Performance Highlights
- Structural plain concrete (s. 1909)
- ACI 318-02 (s 1909.1)
- Limited to continuously supported membranes,
walls, pedestals, etc. (s. 1909.2) - Joints - contraction or isolation joints must be
provided. (s. 1909.3)
84Performance Highlights
85Performance Highlights
- Reinforced Gypsum Concrete. (s. 1915)
- Must comply with ASTM C 317 and ASTM C 956. (s.
1915.1) - Minimum thickness of reinforced gypsum concrete
must be 2 inches or 1 ½ inches when meeting
certain conditions. (s. 1915.2)
86Prescriptive Highlights
- Minimum Slab Provisions (s. 1911)
- Thickness of concrete slabs supported directly on
the ground must not be less than 3 ½ inches. (s.
1911.1) - A 6 mil polyethylene vapor retarder with joint
lapped not less than 6 inches or other approved
equivalent method to retard vapor transmission
through the floor slab. Exception detached
structure accessories to occupancies in R-3 such
as driveways, walks, etc. (s. 1911.1)
87Prescriptive Highlights
- Anchorage to Concrete (s. 1912 and 1913)
- Bolts must conform to ASTM A 307. (s. 1912.1)
- Headed bolts, headed studs and hooks (J or L)
must be designed within the scope per Appendix D
of ACI 318. (s. 1913.1)
88Florida Amendments
- All seismic and snow provisions have been
removed. - Provisions regarding building in the HVHZ have
been added. - Lightweight insulation concrete fill requirements
have been added from the 2001 FBC.
89Florida Amendments
- Special wind provisions for concrete have been
included. - Specific requirements for concrete slabs and
fiber length have been added. - Provisions for gable endwalls have been added.
90Part 8 Chapter 20 - Aluminum
91Scope
- Governs the quality, design, fabrication and
erection of aluminum.
92Highlights
- Structural Aluminum (s. 2002)
- Design, fabrication and assembly of structural
aluminum for buildings or structures must conform
to AAASM35, and Specifications for Aluminum
Structures, Aluminum Design Manual, Part 1-A and
1-B of the Aluminum Association. (s. 2002.1)
93Highlights
- Screen Enclosures (s. 2002.3)
- Actual wall thickness of extruded aluminum
members must not be less than 0.040 inch. (s.
2002.3.1) - Screen density must be a maximum of 20x20 mesh.
(s. 2002.3.2) - Vinyl and acrylic panels must be removable. (s.
2002.3.3) - Design structural members supporting screen
enclosures must be designed to support minimum
wind loads in Table 2002.4. (s. 2002.4)
94Highlights
- Screen Enclosures
- AAF Guide to Aluminum Construction in High Wind
Areas must be accepted as conforming to accepted
engineering practices. (s. 2202.4.1) - Wall panels minimum thickness must not be less
than .024 inch. (2002.5)
95Florida Amendments
- The entire text from Chapter 20 has been
replaced with text from the 2001 Florida Building
Code to reflect the needs of Florida.
96Part 9 Chapter 21 - Masonry
97Scope
- Provides comprehensive and practical
requirements for masonry construction, based on
the latest state of technical knowledge.
98Performance Highlights
- Design Methods (s 2101.2)
- Masonry designed by working stress design
provisions of S. 2101.2.1. - The strength design provisions of s. 2101.2.2 or
- The prestressed masonry provisions of s. 2101.2.3
(Chapters 1 and 4 of ACI 530/ASCE 5/TMS 402)
99Performance Highlights
- Masonry Construction (s. 2104)
- Must comply with the requirements of sections
2104.1.1 through 2104.5 and ACI 530.1/ASCE 6/TMS
602. (s. 2104.1) - Must conform to ASTM C 55 for concrete brick,
ASTM C 73 for calcium silicate face brick, ASTM C
90 for load bearing concrete masonry units or
ASTM C 744 for prefaced concrete and calcium
silicate masonry units. (s. 2103.1) - Mortar must conform to ASTM C 270. (s. 2103.7)
100Performance Highlights
- Glass Unit Masonry (s. 2103.5)
- Must have a minimum average glass face thickness
of 3/16 inch. (s. 2103.5) - The specified thickness of standard units must be
3 7/8 inches. (s. 2110.2.1)
101Prescriptive Highlights
- Empirical Design of Masonry (s. 2109)
- Must comply with Chapter 5 of ACI 530/ASCE 5/TMS
402 or sections 2106 and 2129. (s. 2109.1) - Limited to areas where the wind speed does not
exceeds 110 mph (s. 2109.1.1)
102Prescriptive Highlights
- FCPA Guide to Concrete Masonry Residential
Construction in High Wind Areas Limitation
Group R3 Occupancy for a basic wind speed of 130
mph or less in Exposure B and 110 mph or less in
Exposure C. (1609.1.1.1)
103Florida Amendments
- Provisions governing building in the HVHZ have
been included. - All seismic and snow provisions have been
removed. - References to additional standards have been
added.
104Florida Amendments
- Provisions regulating the bracing of masonry have
been added from the 2001 FBC. - Termite inspection requirements have been
included. - Special wind provisions for masonry have been
included. - Gable endwalls provisions have been added.
105Part 10 Chapter 22 - Steel
106Scope
- Provides the requirements necessary for the
design and construction of structural steel,
cold-formed steel, steel joists, steel cable
structures, steel storage racks and composite
construction.
107Performance Method
- Structural Steel (s. 2205)
- Must be as per ASI-LRED, AISC 335 or AISC-HSS (s.
2205.1). - Cold-formed Steel (s. 2209)
- Must be as per AISI-NASPEC ASCE8 (s. 2209.1)
108Prescriptive Method
- Cold-formed Steel
- Light frame construction (s. 2211)
- Must conform to AISI-NASPEC (s.2210)
- Steel Framing Trusses (s. 2210.3)
- Shear wall for wind resistance (section 2211)
- Type I (segmented) (s. 2211.2)
- Type II (perforated) (s. 2211.3)
109Figure 2202.1
110Figure 2202.1
111Florida Amendments
- Removed all seismic provisions.
- Added special wind provisions for gable ends and
walls from the 2001 FBC. - Added special provisions for the HVHZ.
112Part 11 Chapter 23 - Wood
113Scope
- Provides minimum guidance for the design of
buildings and structures that use wood and
wood-based products in their framing and
fabrication. Alternative methods and materials
can be used where justified by engineering
analysis and testing.
114Performance Method Highlights
- General Design Requirements (s. 2301.2)
- Allowable stress design must resist the
applicable load combination of Chapter 16. (s.
2301.2.1) - Load and resistance factor design (LRFD) must
resist the applicable load combination of Chapter
16. (s. 2301.2.2) - Trusses (s. 2303.4)
- Truss design drawings must be prepared by a
registered design engineer and must provide for
specific information such as slope, depth, span,
etc. (s. 2303.4.1) - Metal plate connected wood trusses must be
manufactured as required by TPI 1. (s. 2303.4)
115Prescriptive Method Highlights
- General Construction Requirements (s. 2304)
- Conventional light-framed wood construction is
limited to areas where the wind speed does not
exceed 100 mph. (s. 2308.2.1) - AFPA Wood Frame Construction Manual for One- and
Two-Family Dwellings. (s. 2308.2.1) - Limitation basic wind speed of 150 mph or less.
- Wall Framing/Bottom Plates. Studs must have full
bearing on a 2 inch thick or larger plate or sill
having a width at least equal to the width of the
stud. (s. 2304.3.1)
116Prescriptive Method Highlights
- General Design Requirements
- Nails and staples must conform to ASTM F 1667.( s
2303.6) - WPPC Guide to Wood Construction in High Wind
Areas. - Limitation (R3 occupancy) basic wind speed 130
mph or less in Exposure B and 110 mph or less in
Exposure C. - SSTD 10 Standard for Hurricane-Resistant
Construction.
117Florida Amendments
- Provisions governing buildings located in the
HVHZ have been added. - All seismic and snow provisions and figures have
been removed. - Detailed requirements for gable endwalls have
been included.
118Florida Amendments
- Tables 2304.7(3), 2304.7.5, and 2304.9.1 modified
to remove Florida Specific Amendments and mirror
base code. - Further requirements of framing have been added.
- Provisions designed to control termite
infestation have been included.
119Florida Amendments
- Provisions governing foam plastic insulation have
been added. - The titles of several tables have been changed to
remove seismic implications.
120Part 12 Chapter 24 Glass and Glazing
121Scope
- Provides information to establish the adequacy
of glazing from the standpoint of life safety and
performance.
122Highlights
- Identification (s. 2403.1)
- Each pane must bear the manufacturers label
designating the type and thickness of the glass
or glazing materials. - Each pane of tempered or laminated glass, except
tempered or laminated spandrell glass, must be
permanently identified by the manufacturer.
123Highlights
- Glass Support Framing (s. 2403.2 and 2403.3)
- Deflection of the edge of the glass perpendicular
to the glass pane must not exceed 1/175 of the
glass edge length or ¾ inch, which ever is less.
(s. 2403.3) - Where one or more sides of any pane of glass is
not firmly supported, or subject to unusual load
conditions, detailed construction documents,
detailed shop drawings and analysis or test data
assuring safe performance for the specific
installation must be prepared by a registered
design professional. (s. 2403.2)
124Highlights
- 2405.5 Unit skylights. Unit skylights shall be
tested and labeled as complying with
101/I.S.2/NAFS Voluntary Performance
Specification for Windows, Skylights and Glass
Doors.
125Highlights
126Highlights
- Wind and Dead Loads on Glass Vertical Glass (s.
2404.1) - Sloped 15 degrees or less
- Curtain and window walls, doors and other
exterior applications must be designed to resist
the wind loads for components and cladding. The
load resistance of glass under uniform load must
be determined as per ASTM E 1300-02.
127Highlights
- Sloped glazing and skylights (s. 2405)
- Unit skylights must be tested and labeled as
complying with 101/I.S.2/NAFS or AAMA/WEMA
1600/IS7. (s. 2405.5) - Hazardous locations
- Glazing must pass the test requirements of CPSC16
CFR1201. (s. 2406.1.1) - Plastic glazing must meet the weathering
requirements of ANSI Z 97. (s. 2406.1.3)
128Florida Amendments
- All provisions governing seismic and snow
requirements have been deleted. - Additional requirements for buildings located in
the HVHZ have been included.
129Florida Amendments
- Detailed requirements for identifying and
labeling glass and lights have been added. - Requirements governing the design and application
of glass and glazing have been modified.
130Part 13 Chapter 25 Gypsum Board and Plaster
131Scope
- Governs the materials, design, construction,
quality and application for both interior and
exterior gypsum board and plaster products.
132Highlights
- Exterior Plaster (s. 2512)
- Cement plaster must not be less than three coats
where applied over metal lath or wire fabric, and
not less than two coats where applied over
masonry. (s. 2512.1) - On wood framed or steel stud construction with
on-grade concrete floor slab system, exterior
plaster must be applied in such a manner as to
cover, but not to extend below, the lath and
paper. (s. 2512.1.1)
133Highlights
- Vertical and Horizontal Assemblies (s. 2504)
- Wood framing.
- Wood supports for lath or gypsum board as well as
wood stripping or furring must not be less than 2
inches nominal thickness in the least dimension.
(s. 2504.1.1) - Lathing and Furring Cement Plaster (STUCCO) (s.
2510) - Installation
- Must be in compliance with ASTM C 926 and ASTM C
1063. (s. 2510.3) - Metal lath and lath attachments must be corrosion
resistant materials. (s. 2510.4)
134Highlights
- Interior Plaster (s. 2511)
- Plastering gypsum plaster or cement plaster must
not be less than three coats where applied over
metal lath or wire fabric lath and not less than
two coats where applied over other bases
permitted by the Code. (s. 2511.1) - Plaster must not be applied directly to fiber
insulation board. (s. 2511.2)
135Highlights
- Shear Wall Construction (s. 2505)
- Wood-framed shear walls sheathed with gypsum
board, lath and plaster are permitted to resist
wind. (s. 2501.1) - Cold-formed steel framed shear walls with gypsum
board are permitted to resist wind loads. (s.
2505.2)
136Highlights
- Gypsum Board Showers and Water Closets (s. 2509)
- When gypsum board is used as a base for tile or
wall panels for tubs, showers or water closet
component walls, water resistance gypsum backing
board must be used as a substrate. (s. 2509.2)
137Florida Amendments
- Provisions governing buildings located in the
HVHZ have been added. - All seismic provisions and references have been
removed.
138Part 14 Chapter 26 - Plastic
139Scope
- Establishes minimum requirements for all
light-transmitting plastics and foam plastics in
all applications regulated by the code.
140Highlights
- Foam Plastic Insulation (s. 2603)
- Must have a flame spread index of not more than
75 and a smoke-development index of not more than
450 as per ASTM E 84. (s. 2603.3) - Clearance between earth and foam plastic applied
to the exterior wall must be not less than 6
inches. (s. 2603.9.2)
141Highlights
- Foam Plastic Insulation
- Thermal Barrier. (s. 2603.4)
- Except as provided in section 2603.4.1 and
2603.8, foam plastic must be separate from
interior of a building by an approved thermal
barrier of 0.5 inch gypsum wall board or
equivalent. - Labeling and Identification (s. 2603.2)
- Packages and containers of foam plastic
insulation must be labeled.
142Florida Amendments
- Provisions governing buildings located in the
HVHZ have been added. - Regulations concerning termite control have been
included. - Added requirements for foam plastic insulation
have been included.
143Florida Amendments
- Modify definition of approve plastics (HVHZ)
Approved plastics for outdoor exposure shall be
evaluated for outdoor durability in accordance
with the Voluntary Standard Uniform Load Test
Procedure for Thermoformed Plastic Domed
Skylights, of the AAMA/WDMA 101/IS2/NAFS
Voluntary Performance Specification for Windows,
Skylights and Glass Doors Architectural Aluminum
Manufacturers Association Publication AAMA 1600
as follows . Remaining text unchanged.
144Part 15 Chapter 30 Elevators and Conveying
Systems
145Scope
- Regulates the installation, testing, inspection,
maintenance, alteration and repair of vertical
and horizontal transportation and
material-handling systems installed in buildings.
146Highlights
- Administration (s. 3001.1
- Administrative and programmatic provisions must
be in accordance with the Department of Business
and Professional Regulations, Chapter 399,
Florida Statutes, and Chapter 61G Florida
Administrative Code. - Reference Standards (s. 3001.2)
- ASME A17.1-2000
- ASME A17.3-1996
- ASME A18.1-1999
- ASME A90.1-1997
- ASME B20.1-2001
- Design, Installation and Alteration of Elevators.
- Must comply with the Elevator Safety Code. (s.
3001.1)
147Florida Amendments
- Provisions governing the design, installation and
alteration of elevators have been added. - Definitions have been added.
- Provisions governing elevator accessibility
requirements for the physically handicapped have
been included.
148Florida Amendments
- Provisions governing the following topics have
been included. - Serial numbers.
- Electrolysis protection for underground hydraulic
elevator cylinders. - Bulletin boards.
- Alterations to electric and hydraulic elevators.
149Florida Amendments
- Section 3007 Change to read as shown
- 1 and 2 are unchanged.
- 3 Each elevator car interior must have a support
rail on at least one wall. All support rails must
be smooth and have no sharp edges and must not be
more than 1 ½ inches (38 mm) thick or 2 ½ inches
(63 mm) in diameter. Support rails must be
continuous and a minimum length of 42 inches
(1067 mm) overall. The inside surface of support
rails must be 1 ½ inches (38 mm)
150Florida Amendments
- clear of the car wall. The distance from the top
of the support rail to the finished car floor
must be at least 31 inches (787 mm) and not more
than 33 inches (838 m). Padded or tufted material
or decorative materials such as wallpaper, vinyl,
cloth or the like may not be used on support
rails. - 3. 4 A bench or seat may be installed on the rear
wall of the elevator - (remaining text is unchanged)
151Part 16 Chapter 31 Special Construction
152Scope
- Provides provisions that regulate construction
for protection requirements for structures having
unique characteristics, such as structures that
are unusually tall and not used for human
occupancy, structures occupied for short periods
of time or recreational structures.
153Performance Highlights
- Membrane Structures (s. 3102)
- Air-supported, air-inflated, membrane-covered
cable and membrane-covered frame structures. (s.
3102.1) - Erected 180 days or longer. (s. 3102.1)
- Must be designed and constructed to sustain dead
loads, loads due to tension or inflation, and
live loads including wind. (s. 3102.7)
154Performance Highlights
- Temporary Structures (s. 3103)
- Erected for a period of less than 180 days. (s.
3103.1) - Tents and other membrane structures erected for a
period of l80 days must comply with the Florida
Fire Prevention Code. (s. 3103.1)
155Performance Highlights
- Awnings and Canopies (s. 3105)
- Design (s. 3105.4)
- Framing membranes must be based on removal or
repositioning of parts, or the whole, during
periods of 75 mph. (s. 3105.4.1) - Design must be based on the applicable wind loads
of Chapter 16. (s. 3105.4.2)
156Performance Highlights
- Awnings and Canopies Design Cont.
- The wind design loads for any fabric or
membrane-covered structure designed with a quick
removal or breakway membrane or fabric at wind
velocities of 75 mph must be based on the
following criteria (s. 3105.4.2.1) - Maximum wind speed of 90 mph
- Importance factor of .77
- Exposure Category B or C
157Performance Highlights
- Awnings and Canopies Design Cont.
- The wind design loads for any fabric or
membrane-covered structure designed with a
permanent or non-removable fabric or membrane
must be based on the following criteria (s.
3105.4.2.2) - Minimum wind velocity as per Chapter 16
- Importance factor of .77
- Exposure Category B or C
158Florida Amendments
- Provisions governing awnings and canopies have
been replaced. - Swimming pool enclosures and safety device
provisions have been removed (covered in Chapter
4).
159Florida Amendments
- Sections have been added that cover the following
topics - Structures seaward of a coastal construction line
are the same as the 2001 FBC. - Flood resistant construction is the same as the
2001 FBC. - Deposit of material in tidewater is regulated as
in 2001 FBC. - Lighting, mirrors, landscaping are the same as in
the 2001 FBC.
160Florida Amendments
- 2005 Supplement creates new section addressing
airport Noise - 3113.1 Airport Noise Study Guidelines. The
Aviation Safety and Noise Abatement Act of 1979,
14 CRF Part 150 (U.S. Department of
Transportation), including revisions through
January, 2005, are hereby adopted as a guideline
for establishing airport noise control.
161Part 17 Chapter 32 Encroachments into the
Public Right-of-Way
162Scope
- Regulates projections and encroachments of
structures.
163Performance Highlights
- Drainage (s. 3201.4)
- Drainage waters collected from a roof, awning,
etc. must not flow over a public walking surface. - Encroachments above grade and below 8 feet in
height. (s. 3202.2) - Steps must not project more than 12 inches or
must be guarded by approved devices not less than
3 feet high. (s. 3202.2.1) - Columns or pilasters, including bases and
moldings, must not project more than 12 inches.
(s. 3202.2.2) - Awnings.
- Vertical clearance from public right-of-way must
be 7 feet minimum. (s. 3202.2.3)
164Performance Highlights
- Sidewalk or street obstructions. (s. 3202.5)
- Unless allowed by the applicable governing
authority having jurisdiction of the right-of-way
or public property, public property must be
maintained clear of any and all obstructions,
including among others, posts, columns, display
of wares or merchandise, and sidewalk signs.
165Florida Amendments
- A provision has been added clarifying
requirements for sidewalk and street obstructions.
166Part 18 Chapter 33 Safeguards During
Construction
167Scope
- Cites safety requirements during construction or
demolition of buildings and structures. These
requirements are intended to protect the public
from injury and adjoining property from damage.
168Performance Highlights
- Storage and Placement (s. 3301.2)
- Construction equipment and materials must be
stored and placed so as not to endanger the
public, the workers, or adjoining property for
the duration of the construction project. - Facilities Required. (s. 3305.1)
- Sanitary facilities must be provided during
construction remodeling, demolition activities as
per the FBC, Plumbing.
169Performance Highlights
- Fire Extinguishers (s. 3309)
- Where required, all structures under
construction, alteration, or demolition must be
provided with not less than one approved portable
fire extinguisher as per section 906. (s. 3309.1) - Excavation and fill for buildings and structures
must be constructed or protected so as not to
endanger life or property. (s. 3304)
170Part 19 Chapter 34 Existing Buildings
171Scope
- Defines the responsibilities for maintenance,
repairs, compliance with other codes and periodic
testing.
172Florida Amendments
- Provisions from Chapter 34 have been deleted and
replaced with references to the Florida Existing
Building Code.
173Part 20 Chapter 35 Reference Standards
174Scope
- Lists the standards that are referenced in the
various sections of the code.
175Florida Amendments
- Standards have been added or updated to meet the
specific needs of Florida.
176Florida Amendments
- 2005 Supplement updates and corrects various
standards in Chapter 35, including the adoption
of ASCE 7-02