1
Digital Generator Protection System
  • Microprocessor Based Protection, Control and
    Monitoring System
  • Waveform Sampling
  • User Friendly
  • GE/Hydro Quebec Joint Development

2
(No Transcript)
3
System Overview
  • Multiple Microprocessors
  • Sampling Rate 12 Samples/Cycle
  • 20 MHz Operation
  • Auto Gain Change A/D Converter

DSPS 3-TMS320
MICROPROCESSORS 2-80C186
8 CURRENTS
ANALOG TO DIGITAL CONVERTER
FILTER AND MUX
REMOTE PC
4 VOLTAGES
MMI
TIME SYNCH (IRIG-B)
4 TRIP RELAYS
DIGITAL INPUTS/ OUTPUTS
6 CONTACT INPUTS
11 AUXILIARY RELAYS
4
Applications
  • For Small, Medium and Large Generator Protection
  • Suitable for Variety of Prime-Movers - Gas,
    Steam, Hydro Turbines
  • Most Commonly Used Protection Functions Packaged
    in a Standard Modular Case

5
Protective Functions
(87G)
  • Stator Differential (87G)
  • Variable Slope Characteristic
  • 100 Stator Ground Fault (64G)
  • Two Overlapping Zones
  • 95 with Fundamental Neutral OV
  • 15 with 3rd Harmonic Comparator
  • or 15 with 27TN Function (Special)
  • Time Overcurrent with Voltage Restraint (51V)
  • Current Unbalance (46)
  • Negative Sequence Overcurrent - I22t
  • Linear Reset Characteristic
  • Loss of Excitation (40)
  • Two Zones of Off-Set Mho

(40)
X
R
Offset Xd 2
Diameter 1.0 pu
Diameter Xd
6
Protective Functions (Cont.)
(24)
VOLTS/HERTZ ()
  • Overexcitation or V/Hz (24)
  • Inverse Characteristic
  • Instantaneous with Time Delay
  • Reverse Power (32)
  • Two Levels
  • Under/Over Frequency (81)
  • Multiple Steps (2-4)
  • Undervoltage Cutoff Feature
  • Overvoltage (59)
  • Inverse Characteristic
  • Undervoltage (27)
  • Neutral Overcurrent (51GN)

Transformer Limit Curve on Generator Voltage Base
140
Generator Manufacturers Recommended Protection
Curve
130
120
110
Relay Characteristic
100
.01
0.1
1.0
10
100
TIME (MINUTES)
7
Additional Protective Features
  • Voltage Transformer Fuse Failure (VTFF)
  • Internal or External
  • Block 40 and 51V functions

8
Adaptive Sampling Interval - 30.5 - 79.5 Hz
9
Additional Protective Features
  • Accidental Energization Logic
  • Sequential Trip Logic

10
Inputs
  • (8) Currents
  • Ia, Ib, Ic, In(Neutral Side)
  • Ia, Ib, Ic, In(System Side)
  • (4) Voltages
  • Va, Vb, Vc(Wye or Open Delta)
  • Vng(Neutral Ground Xfmr)
  • IRIG-B Time Synchronization
  • (6) Digital Inputs
  • Two External Trip (DI3, DI4)
  • Generator Off-Line Indication (AE)
  • Turbine Inlet Valve Close Indication (Sequential
    Trip)
  • Oscillography Trigger
  • External VT Fuse Failure

11
Outputs
  • (4) Trip Relays
  • Two From A Contacts Each
  • Configurable
  • (11) Auxiliary Relays
  • One Form C Contact Each
  • Four Configurable Alarm Contacts (74A, 74B, 74C,
    74D)
  • Pre-defined Alarm Contacts
  • Critical Self-Test Alarm
  • Non Critical Self-Test Alarm
  • VT Fuse Failure Alarm
  • Test Pickup Indication
  • Test Trip Indication
  • Loss of Power Supply No. 1
  • Loss of Power Supply No. 2

12
Simplified Logic Diagram
13
Monitoring
  • Present Values
  • Trip Circuit Monitor
  • Fault Reports (Last 3 Faults)
  • Sequence of Events(Last 100 Events)
  • Self Tests

14
Present Value Monitoring
  • Currents
  • System and Neutral Side (Ia, Ib, Ic, In)
  • Negative Sequence
  • Voltages
  • Va, Vb, Vc
  • 3rd Harmonic Voltage (Phase and Neutral)
  • Megawatts
  • Mvars
  • Frequency
  • Status of Digital Inputs

Scroll on Command or Display Selected Parameters
15
Trip Circuit Monitor
  • Trip Voltage Monitor
  • Normal Condition
  • Four Trip Circuits (94G, 94G1, 94G2, 94G3)
  • Trip Current Monitor
  • Trip Condition
  • Four Trip Circuits (94G, 94G1, 94G2, 94G3)
  • Seal-in of Output Relay
  • Disable/Enable Feature

16
Communications
  • Local MMI (Standard)
  • 2 Level Password Protection
  • 16 LED Alphanumeric Display
  • Keypad with 20 Keys
  • Separate Function Keys for
  • Settings
  • Action
  • Information
  • 19 LED Targets
  • Status LED
  • Local Printer Port (AA, CA models)

17
Communications
  • Remote Access
  • Via RS232 DGP-LINK Software
  • Front and Rear RS232 Ports
  • 3 Level Password Protection
  • Access to
  • Present Values
  • Fault Report
  • Sequence of Events
  • Oscillography
  • Manual Control
  • Relay Settings

18
Present Values
  • Currents
  • Voltages
  • Watts
  • Vars
  • Frequency
  • Negative Sequence Current
  • 3rd Harmonic Voltage
  • Status of Digital Inputs

GEN Simulator DGP 0000 PRESENT
VALUES Station IDMALVERN Generator IDMODEL
GENERATOR 10/28/93 143723446 IAS
5696.0 A -014 DEGS VAN 008.5 KV 000
DEGS IBS 5488.0 A -142 DEGS VBN 008.1
KV -118 DEGS ICS 4864.0 A 104 DEGS VCN
008.2 KV 122 DEGS IAR 5680.0 A -014
DEGS IBR 5456.0 A -142 DEGS ICR 4880.0 A
104 DEGS NEGATIVE SEQ CURRENT 08.1 3RD HARM
PH 00.1 3RD HARM N 03.7 WATTS 126.
33 MWATT VARS 041.95 MVAR GEN OFF-LIN
OPEN INLET VLV OPEN DIG IN 3
OPEN DIG IN 4 OPEN OSC TRIG
OPEN EXT VTFF OPEN FREQ 60.00 SAM
PLING FREQ 720.0
19
Fault Report
Gen Simulator DGP 0000 FAULT
REPORT Station IDMALVERN Generator IDMODEL
GENERATOR FAULT 02 FAULT DATE
08/09/93 TRIP TIME 051037829 FAULT TYPE
ABC TRIP TYPE 87G SYSTEM OPERATING TIME
000008 PREFAULT FAULT ---------------------------
----------- -------------------------------------
----------------- IAS 0128.0 A IAS 014672
A IAR 015664 A IBS 0208.0 A IBS 015264 A IBR
016704 A ICS 0080.0 A ICS 013600 A ICR 014960
A INS 0048.0 A INR 0384.0 A VAN 010.2
KV VBN 010.2 KV VAN 693.0 V VCN 010.0
KV VBN 693.0 V VCN 679.4 V FREQ
60.00 VN 047.0 V WATTS 1888.5 KWATT VARS
3777.0 KVAR 051037.834 87G PHASE A
ON 051037.834 87G PHASE B ON
  • Prefault
  • Currents
  • Voltages
  • Watts
  • Vars
  • Frequency
  • Post Fault
  • Currents
  • Voltages
  • Trip Targets
  • Operating Time
  • Selected Events
  • Last 3 Faults Stored

20
Sequence of Events
GEN Simulator DGP 0000 Events Station
IDMALVERN Generator IDMODEL
GENERATOR 10/29/93 143954971 94G TRIP CIRCUIT
OPEN ALARM ON 10/29/93 143335661 94G2 TRIP
SIGNAL RESET 10/29/93 143335660 32-1
OFF 10/29/93 143335639 32-2 OFF 10/29/93 1433
34396 32-1 ON 10/29/93 143331997 TURBINE
INLET VALUE CLOSED 10/29/93 143328423 GENERATOR
OFF-LINE 10/29/93 143326452 94G2 TRIP SIGNAL
ON 10/29/93 143326451 32-2 ON 10/29/93 142709
878 GENERATOR ON-LINE 10/29/93 142704968 TURBI
NE INLET VALUE OPEN 10/29/93 142654263 94G3
TRIP SIGNAL RESET 10/29/93 142654262 64G1
OFF 10/29/93 142650911 TURBINE INLET VALUE
CLOSED 10/29/93 142647584 GENERATOR
OFF-LINE 10/29/93 142642604 94G3 TRIP SIGNAL
ON 10/29/93 142642603 64G1 ON 10/29/93 142544
444 GENERATOR ON-LINE 10/29/93 142538202 TURBI
NE INLET VALUE OPEN 10/28/93 163231642 REMOTE
- SETTINGS CHANGE DONE 10/28/93 163230882 REMOT
E - SETTINGS CHANGE STARTED
  • Operational Events
  • Setting Changes
  • Fault Data
  • Status
  • Diagnostic Self-Test Events
  • Warning (Non-Critical Alarm)
  • Failure (Critical Alarm)
  • Time Tagged to 1ms Resolution
  • Last 100 Events Stored
  • Available at Communication Port or at Printer Port

21
Sequence of Events
  • Events Include
  • Trip Signal ON / RESET
  • Protection Function ON / OFF
  • Digital Input Status
  • VT Fuse Failure Alarm ON / OFF
  • Trip Circuit Open Alarm ON / OFF
  • Trip Circuit ENERGIZED / NOT ENERGIZED
  • Password Changed
  • ENABLE / DISABLE Outputs
  • Setting Change START / DONE
  • Failure Messages (Critical Self-Test Alarm)
  • Warning Messages (Non-Critical Self-Test Alarm)

22
Oscillography Data
  • Currents and Voltages
  • Digital Flags
  • Internal and External Oscillography Triggering
  • 120 Cycles of Storage Capability
  • Up to 20 Cycles Prefault Data
  • Up to 3 Trip Event Captures
  • ASCII File Format(Readable by EXCEL/LOTUS/DGP-DAT
    A)
  • Fault Report and Settings Saved for Each Fault

23
Hardware and Packaging
  • Testing and Trouble Shooting
  • Optional MOD-10 Modular Test and Connection Plugs
    for Current/Voltage Injection
  • Draw-Out Modular Construction
  • Plug-In Modules for Test and Maintenance
  • Removable Door
  • Target Clearing Through Door
  • Self-Test Diagnostics
  • Critical Alarm
  • Non-Critical Alarm

24
Nomenclature Selection Guide
  • DGP A
  • 1 1 AMP Rated
  • 5 5 AMP Rated
  • 0 One power supply, 48 Vdc
  • 1 One power supply, 110/125 Vdc
  • 2 One power supply, 220/250 Vdc
  • 3 Two power supplies, 48 Vdc
  • 4 Two power supplies, 110/125 Vdc
  • 5 Two power supplies, 220/250 Vdc
  • A With Test Blocks
  • B Without Test Blocks
  • A Future Use
  • A Function Group A See
  • B Function Group B DGP Selection
  • C Function Group C Guide
  • A Revision Level

25
DGP Selection Guide
  • FUNCTIONS FEATURES A B C
  • Stator Differential 87G X X X
  • Current Unbalance 46 X X X
  • Loss of Excitation 40-1, 40-2 X X X
  • Anti-motoring 32 2 Setpoints 1 Setpoint 2
    Setpoints
  • OC - voltage restraint 51V X X X
  • Stator Ground 64G1 (Fundamental OV) X X X
  • Stator Ground 64G2 (3rd Harm. Comparator) X - X
  • Neutral OC 51GN - X X
  • Over Excitation 24 (Volts/Hz) X X X
  • Over Voltage 59 X X X
  • Under Voltage 27 - X X
  • Under Frequency 81-U 4 Setpoints 2 Setpoints 4
    Setpoints
  • Over Frequency 81-O 4 Setpoints 2 Setpoints 4
    Setpoints
  • Accidental Energization Logic X X X
  • Sequential Trip Logic X X X
  • Voltage Transformer Fuse Failure VTFF X X X
  • Oscillography Data Capture X - X
  • Communication Ports 2-RS232 2-RS232 2-RS232