Title: ARC-FAULT CIRCUIT INTERRUPTER(AFCI)
1ARC-FAULT CIRCUIT INTERRUPTER(AFCI)
- Presented by
- Honey Baby George
- S7,EEE
- Roll no-21
2CONTENTS
- Introduction
- Arc fault Circuit Interrupter (AFCI)
- AFCI Working
- Types of AFCIs
- Arcing
- Where AFCI should be used
- Installing AFCI
- Testing AFCI
- Conclusion
- References
3INTRODUCTION
4- Annually, 40,000 fires - 300 deaths - over 1,400
injuries - Arcing faults are the major cause of residential
fires. In 1994 an insurance company survey of
660 electrical fires indicated that over 33 of
these fires were from arcing condition. - An arc fault is the flow of electricity over an
unintended path.
5- Unwanted arcing generates high temperatures and
discharges molten metal that can ignite nearby
combustibles such as paper, insulation, vapors,
and carpets. - Temperature -several thousand degrees Celsius
depending on the available current, voltage, and
materials involved.
6- A circuit breaker
- protects electrical branch circuit wiring.
- reduce the risk of fire from overheating.
- Circuit protection devices role interrupts the
current before - the heat generated by an overload or fault
damages the wire's electrical insulation - the heat generated by an overload reaches
temperatures that could result in a risk of fire.
7- At overload condition, the current drawn by the
sum of the electrical loads , connected to a
particular circuit, exceeds the current capacity
(ampacity) of the circuit conductors.
8ARC FAULT CIRCUIT INTERRUPTER
9- Designed to prevent fires by detecting a
non-working electrical arc. - Disconnect the power before the arc starts
a fire. - It should distinguish between a working arc and a
non-working arc that can occur.
10 Arc Faults Arise From A Number Of Situations,
Including Damaged Wires Receptacle Leakage
Worn Electrical Insulation Loose Electrical
Connections Shorted Wires Wires Or Cords In
Contact With Vibrating Metal Overheated Or
Stressed Electrical Cords And Wires
Misapplied/Damaged Appliances
11AFCI WORKING
12Conventional circuit breakers only respond to
overloads and short circuits, so they do not
protect against arcing conditions that produce
erratic current flow. An AFCI is selective so
that normal arcs do not cause it to trip. It
circuitry continuously monitors current flow
through the AFCI to discriminate between normal
and unwanted arcing conditions.
13Once an unwanted arcing condition is detected,
the control circuitry in the AFCI trips the
internal contacts, thus de-energizing the circuit
and reducing the potential for a fire to occur.
An AFCI should not trip during normal arcing
conditions, which can occur when a switch is
opened or a plug is pulled from a receptacle.
14- AFCIs have a test button and look similar to
ground fault circuit interrupter circuit
breakers. - Some designs combine GFCI and AFCI protection.
- AFCIs are designed to mitigate the effects of
arcing faults but cannot eliminate them
completely.
15- In some cases, the initial arc may cause
ignition prior to detection and circuit
interruption by the AFCI. - The AFCI circuit breaker serves a dual purpose
- shut off electricity in the event of an arcing
fault - trip when a short circuit or an overload occurs.
16- The AFCI circuit breaker provides protection for
the branch circuit wiring and limited protection
for power cords and extension cords. - Single-pole, 15- and 20- ampere AFCI circuit
breakers are presently available.
17(No Transcript)
18TYPES OF AFCIs
19- Branch/Feeder AFCI
- Outlet Circuit AFCI
- Combination AFCI
20- BRANCH/FEEDER AFCI
- Installed at the origin of a branch circuit or
feeder, such as at a panel board. - Provide protection of the branch circuit wiring,
feeder wiring, or both, and branch circuit
extension wiring. against unwanted effects of
arcing.
21- It may be a circuit- breaker-type device or a
device in its own enclosure mounted at or near a
panel board.
22- 2. OUTLET CIRCUIT AFCI
- Installed at a branch circuit outlet, such as at
an outlet box. - Provide protection of cord sets and power-supply
- cords connected to it (when provided with
receptacle outlets) - against the unwanted effects of arcing.
23- 3. COMBINATION AFCI
- Complies with the requirements for both
branch/feeder and outlet circuit AFCIs. - Protect downstream branch circuit wiring and
cord sets and power-supply cords.
24ARCING
25- Continuous luminous discharge of electricity
across an insulating medium. - Usually accompanied by the partial volatilization
of the electrodes. - Some arcs are a normal consequence of device
operation. - Certain devices are designed to contain arcs
from combustible surroundings. Other arcs are
unwanted.
26 For arcs in electrical distribution systems,
the insulating medium is an air gap, wire
insulation, or any other insulator used to
separate the electrodes or line and neutral
conductors. An arc will not jump an air gap
and sustain itself unless there is at least 350 V
across the gap. Therefore, in 120/240 V ac
systems, it is difficult for arcing to cause
ignition unless arc tracking occurs, or the
electrodes loosely contact each other causing a
sustained arcing fault.
27- Two basic types of arcing faults
-
- Series arcing faults
- Parallel arcing faults
28Series arcing faults
- Occur when the current-carrying path in series
with the load is unintentionally broken. - Arcing may occur across the broken gap and create
localized heating. - The magnitude of the current in a series arc is
limited by the load.
29- The series arcing currents are below the typical
circuit breakers ampacity rating (handle rating)
and, therefore, would never trip the conventional
circuit breaker either thermally or magnetically.
30Series arcing can lead to overheating that can
be hazardous.Examples of conditions that may
result in series arcing fault - loose
connections to a receptacle or a wire splice - a
worn conductor from over flexing of a cable.
31Parallel arcing faults
- Occurs when there is an unintentional conducting
path between conductors of opposite polarity. - Limited by the available fault current of the
source and the impedance of the fault. - If the fault is of low impedance, the over
current device should open.
32When the fault impedance is relatively high,
there may be insufficient energy to open the
overcurrent device. This can cause arcing that
can propel particles of molten metal onto nearby
combustibles.
- Examples
- short circuit caused by an intermittent contact
- line-to-ground arcing fault
33- Develop in three stages leakage, tracking, and
arcing. - Leakage currents normally occur in every
electrical wiring system due to parasitic
capacitance and resistance of the cable
insulation. - Leakage current values below 0.5 mA are safe. If
maintained in good condition, the wiring may be
used safely for several decades.
34- When the wiring is subjected to moisture,
conductive dusts, salts, sunlight, excessive
heat, or high-voltage lightning strikes, the
insulation can break down and conduct higher
leakage currents. - As leakage current increases, the surface can
heat up and pyrolyze the insulation. This
process, known as tracking, produces carbon that
generates more heat and progressively more
carbon. - This process may continue for weeks, months, or
longer without incident, eventually, sustained
arcing may occur.
35Parallel arcing faults are hazardous than series
arcing faults, since more energy is associated
with a parallel arcing fault. Parallel arcing
faults result in peak currents above the handle
rating of the conventional circuit breaker. This
may trip the circuit breaker magnetically, if the
impedance of the fault is low and the available
fault current is sufficient. But usually, the
available fault current is not sufficient to trip
the circuit breaker instantaneously.
36ARC CHARACTERISTICS
37 High-frequency noise is seen in voltage and
current traces. There is a voltage drop across
the arc. Because of the voltage drop across the
arc, arcing current is lower than non-arcing
current in the same circuit, except in cases in
which the equipment attempts to compensate for
the difference. Rate of rise of arc current is
usually greater than that for normal current.
38(No Transcript)
39 In each half cycle, arcing current extinguishes
before a normal current zero and reignites after
the normal current zero, establishing a nearly
flat, zero-current section in each half cycle.
These regions shoulders. The voltage wave
looks rectangular.
40ARC DETECTION TECHNOLOGY
41- Two means of detecting hazardous arcs
- arc signal detection.
- ground-fault detection.
42- Arc signal detection
- Constantly monitor current and/or voltage signals
for distinguishing characteristics of arcs or
changes of arc characteristics. - The detecting circuit might look for a number of
characteristics or changes that indicate the
probable presence of an arc. - If sufficient numbers of these conditions are
present, it declares that an arc exists and it
outputs a signal to cause the AFCI to open the
circuit.
43- Ground-fault detection
- Detect the imbalance of current between that
leaving the line terminal and that returning in
the neutral conductor. If the imbalance is
greater than about 50 mA, the device opens the
circuit.
44WHERE AFCIs SHOULD BE USED
45- The 1999 edition of the US National Electrical
Code adopted by many local jurisdictions,
requires AFCIs for receptacle outlets in
bedrooms. - The requirement is limited to only certain
circuits in new residential construction. - AFCIs are considered for added protection in
other circuits and for existing homes.
46- Older homes with aging and deteriorating wiring
systems can especially benefit from the added
protection of AFCIs. - AFCIs should also be considered whenever adding
or upgrading a panel box while using existing
branch circuit conductors. - AFCIs would replace the conventional
thermal/magnetic circuit breakers currently used
in a panel.
47Installing of afci
48- Should be installed by a qualified electrician.
- The installer should follow the instructions
accompanying the device and the panel box.
49- In homes equipped with conventional circuit
breakers rather than fuses, an AFCI circuit
breaker may be installed in the panel box in
place of the conventional circuit breaker to add
arc protection to a branch circuit.
50TESTING AN AFCI
51- AFCIs should be tested after installation to make
sure they are working properly and protecting the
circuit. - AFCIs should be tested once a month to make sure
they are working properly and providing
protection from fires initiated by arcing faults.
- A test button is located on the front of the
device. - The user should follow the instructions
accompanying the device. - If the device does not trip when tested, the AFCI
is defective and should be replaced.
52(No Transcript)
53CONCLUSION
54- Applying technology to improve the electrical
safety of the home is a wise investment for both
the homeowner and the community at large. - Reducing fires of electrical origin and saving
lives is an important responsibility of the
entire construction and regulatory community. - The heavy toll on human life and property from
electrical fires provides a clear indication of
the need for home builders and contractors to
provide consumers with the safest home possible. - Educating home buyers on the latest in home
protection devices and similar after the fact
safety devices.
55- New home owners should know what options are
available in the way of home safety, and are
encouraged to ask their builder or electrician
about the life-saving capabilities of AFCIs. - With the potential to cut the number of
electrical fires that occur each year in half,
AFCI technology should not be overlooked.
56THANK YOU
57- REFERENCES
- George D. Gregory More about arc-fault circuit
interrupters, IEEE TRANSACTIONS ON INDUSTRY
APPLICATIONS, VOL. 40, no. 4, july /august 2004 - Douglas A. Lee, Andrew M. Trotta and William H-
New Technology for Preventing Residential
Electrical Fires Arc-Fault Circuit Interrupters
(AFCIs) - John Brooks and Gary Scott- Arc-fault Circuit
Interrupters For Aerospace Applications, - T. Gammon and J. Matthews, Instantaneous
arcing-fault models developed for building system
analysis, IEEE/ACM Transactions in Industry
Applications, vol. 37, no. 1, pp. 197203,
Jan/Feb 2001.