Presentation on Best Practice for Electrical
Equipment Installation and Safety of
Product(Earthing Protection)
2
Electric Power Systems Lets us work till dark is
away from Each Home
Battery Power Generation Transmission
Distribution Consumption
Generation
Transmission
Distribution
Load
3
(No Transcript)
4
(No Transcript)
5
(No Transcript)
6
(No Transcript)
7
(No Transcript)
8
(No Transcript)
9
(No Transcript)
10
(No Transcript)
11
(No Transcript)
12
(No Transcript)
13
(No Transcript)
14
(No Transcript)
15
(No Transcript)
16
(No Transcript)
17
(No Transcript)
18
(No Transcript)
19
(No Transcript)
20
Easy to generate power as our Choice
21
(No Transcript)
22
An Arcing Fault is the flow of current through
the air between phase conductors or phase
conductors and neutral or ground. Concentrated
radiant energy is released at the point of arcing
an a small amount of time resulting in Extremely
High Temperature.
23
(No Transcript)
24
Fire Accident in Solar PV Power PlantReason Lose
Contact Earthing Disorder and Lightning
25
Solar Panel Fire Accident
26
More Picture Fire in Solar Pv Power Plant
27
More Picture
28
  • India Plan 100GW Solar Power in Year 2022
  • Solar Power Now Changing Many Phases
  • Use with Genset
  • Use with Wind Power
  • Use with High Energy Storage(Battery)
  • Instalation on Ground/Cannel Mounted
  • Instalation on Roof (Building)
  • Instalation on Water (Floating)
  • Instaltion on Building(BIPV Building Integrated
    Transparent Photovoltaic Solar Glass

29
My Gudget My Confidence My Safety
30
(No Transcript)
31
Surge Protection use Recommendation
32
We are offering Surge Protection Devices as
IS/IEC 62305-4
33
v
34
External/Internal Surge Source
35
Horrifying Losses Due To Devil Lightning
36
India Life can be Save from Lightning
37
(No Transcript)
38
Sikhana to Padega Hi Follow NBC2016
39
Surge in Systems and Result
40
Surge in DC Application
41
(No Transcript)
42
Earthing Design and Require Result
  • For substation Large Power below 1.00Ohm
  • For substation Small Power below 2.00Ohm
  • SCADA/TELECOM and AutomationFor substation
    Large Power below 0.50Ohm
  • Tower and Other Structure between 8-15Ohm
  • Lightning Surge Protection 50KA below 5Ohm or
    100KA between 8-15Ohm
  • Follow Standard IEC /IEEE
  • Recommended use of Hybrid Metal to Protect from
    Theft Copper Clad Steel/Alumineum Clad Copper
  • Exothermeic weld IEEE 837

43
Maintenance Free - Equipment Earthing
44
33KV Electrical Sub Station
45
Grid/Earth Mat Design
46
(No Transcript)
47
(No Transcript)
48
JMV LPS Products
49
Copper Cladded Conductor For Electrical
Installation
The Copper Clad Steel Grounding Conductor is made
up of steel with the coating of 99.99 pure
copper. These conductors/ wires or strands are
equipped with the strength of steel with the
conductivity and copper with the better corrosion
resistance property. The concentric copper
cladding is metallurgic ally bonded to a steel
core through a continuous, solid cladding
process using pressure rolling for primary
bonding. The copper cladding thickness remains
constant surrounding steel. We use different
steel grades for the steel core result in Dead
Soft Annealed, High strength and Extra High
Strength Characteristics.  The Copper Clad Steel
Wire yields a composite conductivity of 21, 30
and 40 IACS, and available in Annealed and Hard
drawn. We are delivering products with varied
conductivity and tensile strength as per the
customer need. Further, the wire can be processed
to be silver plated or tinned copper clad steel
wire.
50
Most Efficient Joint Process/Fail Proof
It is efficient and superior to all existing
surface to-surface mechanical retention
connectors.
51
What is Exothermic Welding System Copper to
Bi-Metal and Alumenium
  • Types of Exothermic Joints
  • Possible to join any bi metal except aluminum
  • Exothermic welding is a process of making
    maintain free highly molecular bonding process is
    superior in performance connection to any known
    mechanical or compression-type surface-to-surface
    contact connector. Exothermic weld connections
    provide current carrying (fusing) capacity equal
    to that of the conductor and will not deteriorate
    with age.
  • It offers Electrical connections between two or
    more copper to copper and copper to steel
    conductors.
  • Highly portable method as it does not require
    any external power source or heat source, so it
    can be done almost anywhere.
  • It provides strong permanent molecular bond
    among metallic conductors that cannot loosen and
    further will not deteriorate with age.
  • Connection does not corrode with time and it
    offers permanent conductivity.

52
Copper Clad Steel Solid ROD and Conductor
53
(No Transcript)
54
LIGHTNING FORMATION
55
  • Facts about Lightning
  • A strike can average 100 million volts of
    electricity
  • Current of up to 200,000 amperes
  • Can generate 54,000 oF
  • 10/350MicroSec/50KA Fault Current/Discharge in
    Nano Sec
  • Protection
  • Earthing Design100KA Fault Current/Joints
    Exothermic /Flexible Down Conductor with
    Shortest Route Less Corner

56
  • Lightning Protection Standard use in India
  • (IS2309 Now IEC 62305-5)NBC2016
  • Working Principle Angullar No Compromise with
    Design Max Protection 30Mtrs from One
  • No Product warrenty from Manufacturer
  • High Maintenance Require
  • Earthing below 10.00 Ohm

57
Lightning Risk assessment Study is actually the
measure of risk of a lightning strike and
probability of damages. As Per IEC62305-2.
  • All these calculations are based on
  • Lightning strike density inthat particular
    area(provided byOMV i.e.Ng 8),
  • Danger for people,
  • Occupation coefficient of structure,
  • Relative location of site,
  • Fire Risk,
  • Associated services,
  • Electrical Lines,
  • Lightning Protection Level,
  • Surge Arrestor and
  • Dimensions of installation.

58
Risk Assessment Calculator as per IS/IEC 62305
59
Standards Worldwide for Lightning NFC17-102 and
IEC62305-3

60
Air- Termination System
  1. Vertical Rods- simple shaped buildings
  2. Catenary wires- suitable for all cases
  3. Meshed/ Grid Conductors- best for where plane/
    pitch roof surfaces

61
Lightning Protection As Per NF C 17 102/UNE 211186
The ESE air terminal is a terminal which enables
to generate artificially an upward leader earlier
than a simple rod, with an ionization system, in
order to establish a special impact on its point.
The capture of the lightning strike being faster
than a simple rod, this technology enables to
benefit from larger protection areas, ensuring
protection for large dimensions structures. The
generated protection radius depends on the early
streamer emission value of the air terminal (?t
in µs), its height, and the efficiency of the
protection. The protection radius ensured by this
type of air terminal is 120 m (Protection level
IV, height 60 m , early streamer emission time
60µs). The NFC 17-102/UNE 211186 standard
describes the installation procedure for this
type of air terminal. The installation of this
type of air terminal is easy and cheaper than
other technologies. It can protect whole
buildings with one E.S.E. air terminal. It
enables the protection of a structure and its
environment, the protection of opened areas and
well integrate in the architecture of a structure
without aesthetic alteration. 1 ESE, 2 down
conductors and 2 earthing systems are necessary
to ensure the protection.
62
The Simple Rod air terminal is composed
from a metallic rod with 2 to 8 m height
dominating the structure to protect, and linked
to 2 down conductors minimum, and 2 earthing
systems. The protection radius ensured by this
air terminal which is limited to 30 m more or
less (Protection level IV, height 60 m),
especially dedicated to the protection of small
structures or areas like towers, chimneys, tanks,
water tower, antenna masts The EN 62305-3
standard describes the installation procedure for
these air terminals. 13 Simple Rods, 13 down
conductors, and 13 earthing systems are necessary
to ensure the protection below
63
IEC Declaration by CENELEC for NFC17-102
64
BT has confirmed that ESE National Standards
would remain valid and thus BT recognizedthere
would be no evidence of conflict between NF C
17-102 and IEC EN 62-305 standards and
consequently there is no reason, technical or
otherwise, for the withdrawal of the respective
national standard.BT has requested that this
standard be modified in order to cancel all
reference to the IEC EN 62-305 series, allowing
the NF C 17-102 standard to exist, with the
proposal of possible future migration to
international level (lEC). Accordingly, it was
establishedthat European ESE standards (France,
Spain, Portugal, Slovaquia, etc.) will
notconflict with other European standards and
will remain valid.
  • GIMELEC would draw your attention to the fact
    that the terms of reference of NF C 17-102 and
  • other standards, addressing alternative terminals
    (NF C 17-100, PR EN 61-024-1) were from the
  • outset, very different. It is a fact that NF C
    17-102, whilst referring to ESE Technology also
  • comments on other standards for lightning
    protection systems, particularly incorporating
  • faraday cage, franklin rod and catenary wire
    systems. the 'camouflaging' of NF C 17-102 by IEC
    EN
  • 62-305 and its proponents, that FRENCH STANDARD
    NF C 17-102 is still in full force.

65
The ESE air terminal is a
terminal which enables to generate artificially
an upward leader earlier than a simple rod, with
an ionization system, in order to establish a
special impact on its point. The capture of the
lightning strike being faster than a simple rod,
this technology enables to benefit from larger
protection areas, ensuring protection for large
dimensions structures. The generated protection
radius depends on the early streamer emission
value of the air terminal (?t in µs), its height,
and the efficiency of the protection. The
protection radius ensured by this type of air
terminal is 120 m (Protection level IV, height
60 m , early streamer emission time 60µs) The NFC
17-102 standard describes the installation
procedure for this type of air terminal. The
installation of this type of air terminal is easy
and cheaper than other technologies. It can
protect whole buildings with one E.S.E. air
terminal. It enables the protection of a
structure and its environment, the protection of
opened areas and well integrate in the
architecture of a structure without aesthetic
alteration. 1 ESE, 2 down conductors and 2
earthing systems are necessary to ensure the
protection below
66
  • An active and advance technology device based on
    the principle of Corona effect.
  • Internationally accepted technology complying
    standard NFC 17-102.
  • Active Protection not only protects the structure
    also protect surroundings open areas.
  • Made up of stainless steel SS-316L hence highly
    corrosion resistant and long lasting.
  • More life due to corrosion resistant material is
    used.
  • Single installation offering maximum radius of
    protection of 109 meters which is very large in
    comparison to conventional lightning system.
  • ESE air terminal is very quick in response.
  • Excellent, no electronic device.
  • Economical solution.
  • Easy to Install.

67
ESE Installation Guidence
ESE AT with radius protection form 32 mtr to 107
mtr.
DMC Insulator .
GI/FRP Mast .
Down Conductor Copper / Copper Cadmium Cable 70
sq. mm
Copper Bonded Ground Earthing
68
(No Transcript)
69
(No Transcript)
70
(No Transcript)
71
(No Transcript)
72
(No Transcript)
73
Thimble
Joint all phase wire/ cable with the help of
crimping tools and lugs
Step 1
Separation Sheet
Fixed the separation sheet between all wires/
cables
Gel / Silicon
Step 2
Close the filled Silicon enclosure from top and
bottom , complete installation is done.
Step 3
74
  • Features
  • Provides cable with cable connections and
    jointing wires in switchboard / electric boxes
    Being a jelly it can be easily fit into molds of
    any shape and size.
  • Helps in safeguarding electrical connections and
    also protects electrical connection joints from
    catching fire, sparking and leakage current.
  • Eradicates all the possibilities of fire,
    electric shocks and sparks, etc. causes due to
    improper electrical connection joints and
    safeguards structure, equipment and person.
  • Offers safety to your electrical joints from
    ageing, corrosion, moisture and also observes
    leakage current.
  • Advantages
  • Nontoxic
  • Insulating
  • Highly reliable operation
  • Maintenance Free
  • Repairable
  • Cost Effective
  • High repeat value
  • Elasticity
  • Shape retention

75
(No Transcript)
76
(No Transcript)
77
JMVs Clients
78
Contact Professionals for Advise
79
We Protect You Use Electrical SafetyEarthing
Protection
80
Contact our Team JMV INDIALeader and
Insperation behind Mr.Neeraj Saini
neeraj_at_jmv.co.inMr.Mahesh Chandra Manav Brand
JMV HOD manav_at_jmv.co.inwww.jmv.co.inMoblie
-919910398999Telecom -9191204590000