New Features in DeltaV SimulatePro - PowerPoint PPT Presentation

1 / 17
About This Presentation
Title:

New Features in DeltaV SimulatePro

Description:

Title: DeltaV SimulatePro v7.2 Features Author: Terry Blevins Last modified by: blevins Created Date: 9/22/2003 6:00:42 PM Document presentation format – PowerPoint PPT presentation

Number of Views:52
Avg rating:3.0/5.0
Slides: 18
Provided by: Terr136
Category:

less

Transcript and Presenter's Notes

Title: New Features in DeltaV SimulatePro


1
New Features in DeltaV SimulatePro
  • Available in DeltaV v7.2

2
DeltaV SimulatePro DeltaV v7.2
  • New DeltaV SimulatePro features for operator
    training and control development and checkout.
  • Save and Restore Allows a snapshot to be
    created of the control modules assigned to one or
    more PC nodes.
  • Convert Automatically transforms blocks
    assigned to fieldbus to to their equivalent
    DeltaV function block. Also, changes external I/O
    reference parameters so that applications may
    read and write these parameters.

3
New Feature - On-Demand Save Request
Choose the node(s) and provide Save file
description
4
Auto Save Option
Choose period, nodes, description
5
Restoring All or Parts of Snapshot
6
Updating a Save File
  • The following procedure should be followed to
    allow previous save file values to be retained
  • Load the configuration used when the last save
    file was created. Request a Restore (with option
    to resume execution NOT selected)  
  • Import new or modified modules, assign to PC
    nodes and do a partial download.
  • Set the desired initial value of the parameters
    in the modules that were downloaded
  • Request a Save to create an updated Save file

7
New Feature - SimulatePro Convert
  • Convert may be accessed by right clicking on the
    PC node in DeltaV Explorer.
  • All blocks assigned to fieldbus are changed to
    their equivalent controller blocks
  • All external I/O references are redefined as
    external parameter references

8
After Executing SimulatePro Convert
  • A new module whose tag is M_PC name appears in
    the list of assigned modules.
  • Converted modules show up as needing to be
    downloaded since the modules have been changed.

New Module Automatically Created
9
Devices Referenced in Example Modules
  • Foundation Fieldbus transmitter and valve
  • PLC with data sets defined for input and holding
    registers

10
Conversion of Blocks Assigned to Fieldbus
  • Blocks assigned to fieldbus are automatically
    changed to their equivalent DeltaV block.
  • Conversion is one way and thus should be done
    using a copy of the primary database.

11
On-line Execution of Converted Module Containing
Fieldbus Blocks
  • All blocks execute as they would in fieldbus.
  • Control logic may be checked out by enabling
    Simulate in input blocks
  • Blocks execute exactly as they will in fieldbus
    devices.

12
Example of Module Using External I/O References
  • External I/O references are commonly used in
    modules.
  • Provide a means of including input/output from
    PLCs, sub-systems, and fieldbus e.g. Asi,
    DeviceNet, Profibus.
  • In a simulation environment, these external I/O
    references are invalid. DeltaV SimulatePro
    Convert addresses this issue.

13
Conversion of Modules with I/O References
  • I/O references are automatically converted to
    external parameter references no impact on
    displays that use these parameters.
  • A new module is automatically created that
    contains all parameter referenced by modules
    assigned to the node
  • The new modules name is M_ PC machine name

Converted Module
Reference Module
14
On-line Execution of Converted Module
  • Referenced parameters in the new modules may be
    read and written from control studio allowing
    control logic to be checked out.
  • Process Simulate packages may read and write
    these reference parameters using OPC.
  • Modules may be created that use these parameters
    to duplicate the logic contained in the PLC,
    subsystem etc.

15
Converted Reference May be Viewed and Values
Changed from SimulatePro
16
Convert is One-Way
  • Always import modules into the training or
    development system from the plants DeltaV
    control system.
  • Periodically Import any changes or updates in the
    modules or displays.

Operator Training or Engineering Test System
Import
Control System
17
Summary
  • The DeltaV SimulatePro Save and Restore features
    are useful for operator training and in
    engineering development and control checkout.
  • The SimulatePro Convert feature allows blocks
    assigned Fieldbus and External I/O references to
    be automatically modified so they can be utilized
    in the DeltaV Simulate environment
Write a Comment
User Comments (0)
About PowerShow.com