Control IT Hardware (AC800 M/C) & SoftController - PowerPoint PPT Presentation

1 / 74
About This Presentation
Title:

Control IT Hardware (AC800 M/C) & SoftController

Description:

Hardware (AC800 M/C) & SoftController A suite of IEC 61131-3 compatible controllers AC 800 M ControlIT AC 800M Hardware AC 800M Controller with a S800 I/O Module ... – PowerPoint PPT presentation

Number of Views:204
Avg rating:3.0/5.0
Slides: 75
Provided by: aGongkon
Category:

less

Transcript and Presenter's Notes

Title: Control IT Hardware (AC800 M/C) & SoftController


1
Control IT Hardware (AC800 M/C) SoftController
2
A suite of IEC 61131-3 compatible controllers
  • AC 800M the new Modular Controller designated
    for binary control as well as advanced control
    applications
  • AC 800C the Compact Controller for small, yet
    advanced applications
  • SoftControl the controller that runs on a PC
    providing high performance at low cost

3
AC 800 M
4
ControlIT AC 800M Hardware
  • AC 800M
  • Modular and flexible concept, DIN-rail mounted
  • Built in redundant Ethernet
  • Very low power consumption
  • Hot swap of communication- and I/O modules
  • Local and remote I/O options
  • Industry quality hardware with excellent EMC and
    MTBF properties

5
AC 800M Controller with a S800 I/O Module
AC 800M
I/O System
Communication Interface
Processor Module
S800 I/O Module
6
Processor Module
7
Processor Module
8
Hardware mapped to Control Builder
1 2 3 4 5 6 7 8
1
6
5
4
3
2
7
8
9
Base components for AC 800M
  • Processor Module
  • PM860 - Processor
  • TP830 - Baseplate
  • Communication Interfaces
  • CI851 Profibus
  • CI852 Foundation Fieldbus
  • CI853 RS232-C
  • Power Supply
  • SD821 - 24 V d.c. regulated _at_ 2.5 A
  • SD822 - 24 V d.c. regulated _at_ 5 A
  • SD823 - 24 V d.c. regulated _at_ 10 A
  • Battery Backup
  • SB821- External Backup

10
Processor Module
  • MPC860/48MHZ
  • Motorola Power PC
  • 8 MB RAM
  • 5 MB for application program
  • 3 MB for executable firmware
  • Mounted on the module
  • 2 MB System FLASH PROM
  • For non-volatile storage of firmware and license
    key
  • Mounted on the module
  • Optical Modulebus to connect clusters of S800 I/O
    modules
  • A connector for Compact Flash (not included in
    this release)
  • Two Ethernet ports for connection to the control
    network
  • CN1, CN2
  • Two serial ports (COM3, COM4)
  • COM3 is an RS232-C port with modem control
    signals
  • COM4 is isolated and used for the connection of
    the configuration tool
  • Electrical Modulebus is used for connection
    clusters of S800 I/O directly to the baseplate
  • CEX-bus is used for extending the on-board
    communication ports with communication interface
    modules

11
Power Supply
  • Switch-mode power converters
  • Converting a.c. Mains supply voltage to a
    regulated 24 V d.c.
  • Input can be either 115 V a.c. or 230 V a.c
  • Redundant or non redundant
  • When a redundant power supply is connected to a
    common load, you need a voting device, SS822, to
    combine two outputs into one via diodes
  • The CPU module does has no requirement for a UPS
  • It has a 5 ms reservoir to safely shutdown
  • The power supply handles short power
    interruptions (lt20 ms)
  • Available modules
  • SD 823
  • 24 V d.c. regulated _at_ 10 A
  • SD 822
  • 24 V d.c. regulated _at_ 5 A
  • SD 821
  • 24 V d.c. regulated _at_ 2.5 A

12
Battery Backup
External battery
  • Internal battery
  • Up to one month (720 hours)
  • Lithium Battery 3.6 V, 950 mAh.
  • External battery module - SB821
  • Lithium battery, 3.6 V 16 Ah
  • A minimum of 18 months
  • Mounted on the DIN rail and connected to the CPU
    via cable

Internal battery
External battery Connection
13
I/O System
  • Local I/O S800
  • 12 local I/O modules per cluster
  • 24 with optical modem
  • 7 clusters x 12 I/O modules of local on the
    Modulebus
  • Up to 96 local I/O Modules
  • Remote I/O via Profibus
  • Foundation Fieldbus and Advant Fieldbus to come
  • Recommened to use ABB I/O S900, S800 and S200
  • Field Communication Interface (FCI) is used to
    connect the I/O modules to the PROFIBUS
  • There is no physical limit for the number of I/Os
    that can be connected to AC 800M
  • Recommendation
  • 600-700 I/O per controller
  • The memory for the application sets the limit
  • The hardware is relatively cheap
  • Buy an extra controller

14
I/O System
  • Local I/O
  • Up to 96 modules
  • Remote I/O via Profibus

CI851 Profibus
PM860 CPU
PM860 CPU
12 I/O Modules
Optical
CI830 FCI
12 I/O modules
TB820 OpticalModem
12 I/O modules
Up to 24 modules per stations
CI830 FCI
Optical
12 I/O modules
TB820 OpticalModem
12 I/O modules
TB820 OpticalModem
12 I/O modules
Up to 7 clusters and 200m between clusters
Up to 5 PROFIBUS segments Up to 32 stations per
segment Up to 24 modules per stations Up to 384
DI/DO and 192AI/AO per station
15
AC 800M / S800 I/O Interconnection
16
AC 800M / S800 I/O Interconnection
TB805
PM810
AI810
AI810
AO810
AO810
AO810
AO810
CI851
TK801V003/6/12
TB850V007
TB851
See note 1
TB806
See note 3
AI810
AI810
AO810
AO810
AO810
AO810
CI851
See note 2
DO810
TB820
DI810
DI810
DO810
TK811V015/050/150
See note 5
To addition module clusters
CI830
DI810
DI810
DO810
DO810
TB810
See note 4
TB820
DI810
DI810
DO810
DO810
17
Modulebus Extension Termination
TB805
TB806
DIN-Rail
TK801V003/006/012
Note 3
18
I/O Module on Compact Extended MTUs
I/O Modules
Extended MTU
Typical Compact MTU with I/O Module
CI830
Compact MTU
Typical Extended MTU with I/O Module
19
AC 800M Connectors for Optical Modulebus
Duplex Fiber Optic Cable Connector
TK811V015/050/150
Rx
Tx
TK812V015/050/150
Simplex Fiber Optic Cable Connector
Front View
Note 1
For connection from PM810 to TB820
20
TB820 Optical Modulebus Connection

TB820
Optical ModuleBus Interface Connectors (X4, X5)
TK811V015/050/150
Rx
X4
Tx
Duplex Fiber Optic Cable Connector
Rx
X5
TK812V015/050/150
Tx
Simplex Fiber Optic Cable Connector
Front View
Note 5
21
CEX Extension Termination
Note 2
22
CEX Extension Termination
Note 2
23
Supported S800 I/O Modules (Local Remote)
S800 I/O Modules
S800 I/O I.S. Modules
S800L I/O Modules
24
Supported S200 I/O Modules (Remote I/O)
Via 200-APB12 PROFIBUS Adapter
S200L I/O Modules
S200 I/O Modules
S200L I/O Modules
25
PROFIBUS Support
  • CI851 Profibus Interface
  • Power from the processor module
  • TP851 Baseplate
  • Profibus DP must be terminated on both sides
  • It is possible to connect any standard PROFIBUS
    I/O via CI851
  • For example S800 I/O or S200 I/O

26
PROFIBUS Connection - CI830 TB820
Connector for TB810
TB820 Modulebus Optical Port
Power Supply Connections
Profibus-DP Connector
Note 4
CI830
27
AC 800M, Profibus integration
S800 I/O
Profibus-PA via standard segmentcoupler
Profibus-DP
S900 I/O
Profibus-PA
DP/PA Converter
28
Foundation Fieldbus (In future release)
  • CI852 Foundation Fieldbus H1 Interface
  • Power from the processor module
  • TP852 Baseplate
  • Up to 32 Foundation Fieldbus Devices

29
AC 800M ,FF integration
Communication with FF-instruments is easily
performed via IEC 61131-3 function blocks
FF H1
30
Serial Interface RS232-C
  • CI853 RS232-C
  • Two serial ports
  • Power from the processor module
  • TP853 Baseplate
  • A RS232-C channel, with full modem support, can
    be connect to COM1 or COM2
  • For cables longer than 15m a short distances
    modem, TC562, must be used
  • Up to 12 km, depending on the transmission speed
  • Available Protocols
  • Please see screen dump to the right

31
CEX Extension and Termination
  • CEX Bus in the communication bus
  • TB 850 CEX-bus termination shall always be
    installed on the last unit
  • CEX extension cable TK850 (0.7m) to mount the
    modules on another DIN-rail

32
Modulebus Extension and Termination
  • The Modulebus connects the local I/O
  • A terminator, TB807, must always be mounted on
    the last I/O module on the Modulebus
  • Will support direct connection to Drives in the
    future

33
Installation
  • Mounted on a horizontal DIN rail
  • Locking device to connect to the DIN rail to get
    grounding
  • The locking device can be in OPEN, SLIDE or
    LOCKED
  • AC800M S800I/O has protection class IP20
  • To get higher protection we recommend the
    following cabinets with protection class IP54
  • RM550 Floor mounted
  • RE820 Wall mounted

Example of Wall mounted
34
Environmental Specifications
35
CE Compliance
36
Electromagnetic Compatibility and Main Voltage
Conditions
37
AC 800 C
38
AC 800C Main Module
  • Processor Module PM210
  • 18,432 MHz
  • 2 Mb RAM and 2 Mb Flash PROM
  • On board I/O Modules
  • 10 DI, 6 DO
  • Two on-board RJ-45 jacks for RS-232 channels
  • COM 0 The port for the Control Builder
  • COM 1- full set of modem control signals
  • Two slots for optional communication plug-in
    boards are provided
  • Serial Links
  • Ethernet
  • PROFIBUS-DP master of class 1
  • FOUNDATION Fieldbus link master (future)
  • Battery back-up module - SB210
  • 1 slot for an optional battery plug-in board with
    a real-time clock and a lithium battery

39
AC 800C Hardware Layout
40
Hardware mapped to Control Builder
8
7
1
1 2 3 4 5 6 7 8
6
5
2
4
3
41
Installation
  • Horizontally and vertically mounted on the DIN
    rail
  • The AC 800C, S200, S200L and S800 I/O-unit have
    all protection class IP 20

42
AC 800C / S200/S200L/ S800 I/O Modules
Interconnection
Programming Terminal
Central I/O
Remote I/O
AC 800C
S800 I/O
S200/S200L I/O
Profibus-DP
S200/S200L I/O
43
How to connect I/O Modules
  • On-board I/O
  • 10 DI and 6 DO on board
  • 24 V DC
  • The inputs and outputs are filtered and
    galvanically isolated by optocouplers
  • Local Input/Output (I/O) units
  • 8 S200 Local I/O Modules
  • two rows by means of the extension cables CE1 or
    CE3.
  • 8 Extra via a TK210 cable and a 200 AIO adapter
  • Remote I/O Modules
  • PROFIBUS-DP can be used for connection of remote
    I/O units, for instance S200/S200L and S800 I/O
    units
  • The total number of I/O units connected (central
    and remote) to the controller are 32 I/O units

44
On board I/O
  • On-board I/O
  • 10 DI and 6 DO on board
  • 24 V DC
  • The inputs and outputs are filtered and
    galvanically isolated by optocouplers
  • A separate two-pole plug-in screw connector for
    the external 24 V DC power supply
  • The unit is not damaged if the polarity is
    reversed

45
Local I/O
  • Local Input/Output (I/O) units
  • 8 S200 Local I/O Modules
  • two rows by means of the extension cables CE1 or
    CE3 0.3 and 0.9 m respectively
  • 8 Extra via a TK210 cable and a 200 AIO adapter
  • (length 0.5, 1.0, or 2.5 m)
  • Note that a TK210 cable longer than 0.9 m is not
    allowed in hazardous locations according to
    UL1604

46
Supported S200 I/O (Local Remote)
S200C I/O Modules
S200 I/O Modules
S200L I/O Modules
47
AC 800C Communication Possibilities
  • To Control Builder
  • Via a serial port using the PPP protocol, or
    alternatively via Ethernet
  • Serial Interfaces
  • Available protocols are Siemens 3964R (as
    master),
  • COMLI, MODBUS RTU (as master) and MMS.
    User-defined protocols may also be used
  • Fieldbus Support
  • PROFIBUS
  • FOUNDATION Fieldbus
  • On-board serial Communication
  • COM 0 can receive and transmit signals
  • COM 0 is the default channel for the programming
    station tool port
  • COM 1 has a full set of modem control signals
  • Each channel has LEDs indicating the status of
    transmit and receive activities
  • RS-232 is a point-to-point communication standard
    with a maximum cable length of 15 meters

48
Communication Extensions
Ethernet Communication Board CI272
Profibus Communication Board CI274
RS-232 Communication Board CI271
49
Communication Extensions - Serial
  • RS-232 Communication Board CI271 (Option)
  • There are two RJ-45 jacks for RS-232 channels
  • Full set of modem control signals
  • This gives a multiple RS-232 point-to-point
    communication with e.g. printers, scales, bar
    codes, controllers, and for multiple protocols
    (COMLI, Modbus, etc)

50
Communication Extensions - Ethernet
  • Ethernet Communication Board CI272 (Option)
  • Enables a network consisting of many
    interconnected controllers, operator stations and
    servers
  • Communication via MMS
  • It has one RJ-45 jack for Ethernet 10BASE-T
    (twisted pair, max. cable length 100 m)

51
PROFIBUS Board CI274
  • PROFIBUS Board - CI274
  • A fast (12 Mb/s) PROFIBUS-DP master
  • A PROFIBUS-PA can also be used, via a segment
    coupler 1, in heavy industries with intrinsically
    safe I/Os
  • The CI274 board acts as a PROFIBUS-DP master of
    class 1 and up to two of them can be installed on
    the AC 800C controller

52
PROFIBUS Board CI274
  • Can be used to connect remotely installed S800
    I/O, S200 I/O, S200L I/O and third party I/O
    units
  • Maximum length of 100 to 1200 meters, depending
    on the transmission rate
  • S800/S800L I/O
  • The S800 I/O units are connected to one or more
    I/O adapters, CI830
  • These I/O units are connected to one or more I/O
    adapters, with a maximum of twelve I/O units per
    adapter.
  • Additional units can be connected to the same
    adapter via optical cables and optical interface
    units, TB820.
  • S200/S200L I/O
  • These I/O units are connected to one or more I/O
    adapters, 200-APB12, with a maximum of eight I/O
    units per adapter

53
FOUNDATION Fieldbus CI 275 (future release)
  • The CI275 board is an optional interface for
    remote connection of 31.25 Kb/s FOUNDATION
    Fieldbus devices
  • A maximum length of 200 to 1900 meters, depending
    on cable type
  • The CI275 board acts as link master device
  • Used to connect remotely installed I/O and
    third-party units and which comply with its
    specifications

54
Battery Backup - SB210
  • At least a year with the battery and 20 minutes
    without
  • Low battery voltage, such as after a power
    failure, is indicated by flashing PWR
  • Battery replacement can be performed during
    operation by lifting a small lid in the
    controller cover. UL-approved 3 V batteries of
    type CR2430 must be used

55
Power Supply
  • Note
  • The controller and the I/O systems should, if
    possible, have separate 24 V DC supplies

56
Technical Data
57
Environmental Specification - Climate
58
Environmental Specification - Mechanical
59
CE - Compliance
60
Electro Magnetic Compatibility
61
Electro Magnetic Compatibility
62
SoftControllerFor future release
63
SoftControl An Overview
  • A personal computer can be turned into a
    controller by means of Control Builder software
    and communication plug-in boards
  • Central I/O
  • S200 and S200L I/O units
  • Remote I/O
  • Via PROFIBUS-DP and FOUNDATION Fieldbus. SattBus
    (developed by ABB Automation Products) and
    DataHighway Plus (from Allen-Bradley)

64
Hardware mapped to Control Builder
65
Communications Serial Interface
  • S-232 Protocols
  • A PC is usually delivered with one or two RS-232
    COM-ports (COM1 and COM2)
  • You can add more interface boards
  • Standard protocols such as PPP is specified by
    use of standard Windows installation software
  • A range of other protocols can be defined by the
    Project Explorer

66
Local I/O
  • S200/S200L I/O units
  • Up to four plug-in boards can be handled by the
    Soft Controller
  • each of them capable of connecting up to sixteen
    I/O units
  • Use the ISA CIIO Board
  • Alternatively, the units can be connected via
    PROFIBUS-DP

67
Supported S200 I/O (Local Remote)
S200C I/O Modules
S200 I/O Modules
S200L I/O Modules
68
Ethernet Communication
  • Ethernet
  • A standard Ethernet PC board can be used if the
    controller is to be connected to Ethernet
  • Use standard network components to build your
    network

69
PROFIBUS-DP Communication
  • A plug-in board a PROFIBUS-DP network.
  • Up to four board per SoftController
  • Two adapters
  • one for connection of up to eight S200/S200L I/O
    units
  • The other for connection of up to twelve S800 I/O
    units

S200 I/O Modules via PROFIBUS
S800 I/O Modules via PROFIBUS
70
FOUNDATION Fieldbus
  • FOUNDATION Fieldbus
  • Up to thirty-two FOUNDATION Fieldbus devices can
    be connected to a plug-in board. Up to four such
    boards can be handled by the SoftControl

71
SattBus
  • SattBus is a communication protocol and a
    physical layer, both developed by ABB Automation
    Products
  • Up to 120 nodes can be connected to a SATTBUSPC
    board, and up to four such boards can be handled
    by the SoftController
  • COMLI can be used for communication on SattBus

72
DataHighway Plus
  • DataHighway Plus is a multi-master communication
    protocol from Allen-Bradley
  • Up to 63 Allen-Bradley PLC-5 systems can be
    connected to a DataHighway Plus board, and up to
    four such boards can be handled by the
    SoftController.

73
Hardware Requirements
74
(No Transcript)