Title: Control IT Hardware (AC800 M/C) & SoftController
1Control IT Hardware (AC800 M/C) SoftController
2A suite of IEC 61131-3 compatible controllers
- AC 800M the new Modular Controller designated
for binary control as well as advanced control
applications - AC 800C the Compact Controller for small, yet
advanced applications - SoftControl the controller that runs on a PC
providing high performance at low cost
3AC 800 M
4ControlIT AC 800M Hardware
- AC 800M
- Modular and flexible concept, DIN-rail mounted
- Built in redundant Ethernet
- Very low power consumption
- Hot swap of communication- and I/O modules
- Local and remote I/O options
- Industry quality hardware with excellent EMC and
MTBF properties
5AC 800M Controller with a S800 I/O Module
AC 800M
I/O System
Communication Interface
Processor Module
S800 I/O Module
6Processor Module
7Processor Module
8Hardware mapped to Control Builder
1 2 3 4 5 6 7 8
1
6
5
4
3
2
7
8
9Base components for AC 800M
- Processor Module
- PM860 - Processor
- TP830 - Baseplate
- Communication Interfaces
- CI851 Profibus
- CI852 Foundation Fieldbus
- CI853 RS232-C
- Power Supply
- SD821 - 24 V d.c. regulated _at_ 2.5 A
- SD822 - 24 V d.c. regulated _at_ 5 A
- SD823 - 24 V d.c. regulated _at_ 10 A
- Battery Backup
- SB821- External Backup
10Processor Module
- MPC860/48MHZ
- Motorola Power PC
- 8 MB RAM
- 5 MB for application program
- 3 MB for executable firmware
- Mounted on the module
- 2 MB System FLASH PROM
- For non-volatile storage of firmware and license
key - Mounted on the module
- Optical Modulebus to connect clusters of S800 I/O
modules - A connector for Compact Flash (not included in
this release)
- Two Ethernet ports for connection to the control
network - CN1, CN2
- Two serial ports (COM3, COM4)
- COM3 is an RS232-C port with modem control
signals - COM4 is isolated and used for the connection of
the configuration tool - Electrical Modulebus is used for connection
clusters of S800 I/O directly to the baseplate - CEX-bus is used for extending the on-board
communication ports with communication interface
modules
11Power Supply
- Switch-mode power converters
- Converting a.c. Mains supply voltage to a
regulated 24 V d.c. - Input can be either 115 V a.c. or 230 V a.c
- Redundant or non redundant
- When a redundant power supply is connected to a
common load, you need a voting device, SS822, to
combine two outputs into one via diodes
- The CPU module does has no requirement for a UPS
- It has a 5 ms reservoir to safely shutdown
- The power supply handles short power
interruptions (lt20 ms) - Available modules
- SD 823
- 24 V d.c. regulated _at_ 10 A
- SD 822
- 24 V d.c. regulated _at_ 5 A
- SD 821
- 24 V d.c. regulated _at_ 2.5 A
12Battery Backup
External battery
- Internal battery
- Up to one month (720 hours)
- Lithium Battery 3.6 V, 950 mAh.
- External battery module - SB821
- Lithium battery, 3.6 V 16 Ah
- A minimum of 18 months
- Mounted on the DIN rail and connected to the CPU
via cable
Internal battery
External battery Connection
13I/O System
- Local I/O S800
- 12 local I/O modules per cluster
- 24 with optical modem
- 7 clusters x 12 I/O modules of local on the
Modulebus - Up to 96 local I/O Modules
- Remote I/O via Profibus
- Foundation Fieldbus and Advant Fieldbus to come
- Recommened to use ABB I/O S900, S800 and S200
- Field Communication Interface (FCI) is used to
connect the I/O modules to the PROFIBUS - There is no physical limit for the number of I/Os
that can be connected to AC 800M - Recommendation
- 600-700 I/O per controller
- The memory for the application sets the limit
- The hardware is relatively cheap
- Buy an extra controller
14I/O System
- Local I/O
- Up to 96 modules
CI851 Profibus
PM860 CPU
PM860 CPU
12 I/O Modules
Optical
CI830 FCI
12 I/O modules
TB820 OpticalModem
12 I/O modules
Up to 24 modules per stations
CI830 FCI
Optical
12 I/O modules
TB820 OpticalModem
12 I/O modules
TB820 OpticalModem
12 I/O modules
Up to 7 clusters and 200m between clusters
Up to 5 PROFIBUS segments Up to 32 stations per
segment Up to 24 modules per stations Up to 384
DI/DO and 192AI/AO per station
15AC 800M / S800 I/O Interconnection
16AC 800M / S800 I/O Interconnection
TB805
PM810
AI810
AI810
AO810
AO810
AO810
AO810
CI851
TK801V003/6/12
TB850V007
TB851
See note 1
TB806
See note 3
AI810
AI810
AO810
AO810
AO810
AO810
CI851
See note 2
DO810
TB820
DI810
DI810
DO810
TK811V015/050/150
See note 5
To addition module clusters
CI830
DI810
DI810
DO810
DO810
TB810
See note 4
TB820
DI810
DI810
DO810
DO810
17Modulebus Extension Termination
TB805
TB806
DIN-Rail
TK801V003/006/012
Note 3
18I/O Module on Compact Extended MTUs
I/O Modules
Extended MTU
Typical Compact MTU with I/O Module
CI830
Compact MTU
Typical Extended MTU with I/O Module
19AC 800M Connectors for Optical Modulebus
Duplex Fiber Optic Cable Connector
TK811V015/050/150
Rx
Tx
TK812V015/050/150
Simplex Fiber Optic Cable Connector
Front View
Note 1
For connection from PM810 to TB820
20TB820 Optical Modulebus Connection
TB820
Optical ModuleBus Interface Connectors (X4, X5)
TK811V015/050/150
Rx
X4
Tx
Duplex Fiber Optic Cable Connector
Rx
X5
TK812V015/050/150
Tx
Simplex Fiber Optic Cable Connector
Front View
Note 5
21CEX Extension Termination
Note 2
22CEX Extension Termination
Note 2
23Supported S800 I/O Modules (Local Remote)
S800 I/O Modules
S800 I/O I.S. Modules
S800L I/O Modules
24Supported S200 I/O Modules (Remote I/O)
Via 200-APB12 PROFIBUS Adapter
S200L I/O Modules
S200 I/O Modules
S200L I/O Modules
25PROFIBUS Support
- CI851 Profibus Interface
- Power from the processor module
- TP851 Baseplate
- Profibus DP must be terminated on both sides
- It is possible to connect any standard PROFIBUS
I/O via CI851 - For example S800 I/O or S200 I/O
26PROFIBUS Connection - CI830 TB820
Connector for TB810
TB820 Modulebus Optical Port
Power Supply Connections
Profibus-DP Connector
Note 4
CI830
27AC 800M, Profibus integration
S800 I/O
Profibus-PA via standard segmentcoupler
Profibus-DP
S900 I/O
Profibus-PA
DP/PA Converter
28Foundation Fieldbus (In future release)
- CI852 Foundation Fieldbus H1 Interface
- Power from the processor module
- TP852 Baseplate
- Up to 32 Foundation Fieldbus Devices
29AC 800M ,FF integration
Communication with FF-instruments is easily
performed via IEC 61131-3 function blocks
FF H1
30Serial Interface RS232-C
- CI853 RS232-C
- Two serial ports
- Power from the processor module
- TP853 Baseplate
- A RS232-C channel, with full modem support, can
be connect to COM1 or COM2 - For cables longer than 15m a short distances
modem, TC562, must be used - Up to 12 km, depending on the transmission speed
- Available Protocols
- Please see screen dump to the right
31CEX Extension and Termination
- CEX Bus in the communication bus
- TB 850 CEX-bus termination shall always be
installed on the last unit - CEX extension cable TK850 (0.7m) to mount the
modules on another DIN-rail
32Modulebus Extension and Termination
- The Modulebus connects the local I/O
- A terminator, TB807, must always be mounted on
the last I/O module on the Modulebus - Will support direct connection to Drives in the
future
33Installation
- Mounted on a horizontal DIN rail
- Locking device to connect to the DIN rail to get
grounding - The locking device can be in OPEN, SLIDE or
LOCKED - AC800M S800I/O has protection class IP20
- To get higher protection we recommend the
following cabinets with protection class IP54 - RM550 Floor mounted
- RE820 Wall mounted
Example of Wall mounted
34Environmental Specifications
35CE Compliance
36Electromagnetic Compatibility and Main Voltage
Conditions
37AC 800 C
38AC 800C Main Module
- Processor Module PM210
- 18,432 MHz
- 2 Mb RAM and 2 Mb Flash PROM
- On board I/O Modules
- 10 DI, 6 DO
- Two on-board RJ-45 jacks for RS-232 channels
- COM 0 The port for the Control Builder
- COM 1- full set of modem control signals
- Two slots for optional communication plug-in
boards are provided - Serial Links
- Ethernet
- PROFIBUS-DP master of class 1
- FOUNDATION Fieldbus link master (future)
- Battery back-up module - SB210
- 1 slot for an optional battery plug-in board with
a real-time clock and a lithium battery
39AC 800C Hardware Layout
40Hardware mapped to Control Builder
8
7
1
1 2 3 4 5 6 7 8
6
5
2
4
3
41Installation
- Horizontally and vertically mounted on the DIN
rail - The AC 800C, S200, S200L and S800 I/O-unit have
all protection class IP 20
42AC 800C / S200/S200L/ S800 I/O Modules
Interconnection
Programming Terminal
Central I/O
Remote I/O
AC 800C
S800 I/O
S200/S200L I/O
Profibus-DP
S200/S200L I/O
43How to connect I/O Modules
- On-board I/O
- 10 DI and 6 DO on board
- 24 V DC
- The inputs and outputs are filtered and
galvanically isolated by optocouplers - Local Input/Output (I/O) units
- 8 S200 Local I/O Modules
- two rows by means of the extension cables CE1 or
CE3. - 8 Extra via a TK210 cable and a 200 AIO adapter
- Remote I/O Modules
- PROFIBUS-DP can be used for connection of remote
I/O units, for instance S200/S200L and S800 I/O
units
- The total number of I/O units connected (central
and remote) to the controller are 32 I/O units
44On board I/O
- On-board I/O
- 10 DI and 6 DO on board
- 24 V DC
- The inputs and outputs are filtered and
galvanically isolated by optocouplers - A separate two-pole plug-in screw connector for
the external 24 V DC power supply - The unit is not damaged if the polarity is
reversed
45Local I/O
- Local Input/Output (I/O) units
- 8 S200 Local I/O Modules
- two rows by means of the extension cables CE1 or
CE3 0.3 and 0.9 m respectively - 8 Extra via a TK210 cable and a 200 AIO adapter
- (length 0.5, 1.0, or 2.5 m)
- Note that a TK210 cable longer than 0.9 m is not
allowed in hazardous locations according to
UL1604
46Supported S200 I/O (Local Remote)
S200C I/O Modules
S200 I/O Modules
S200L I/O Modules
47AC 800C Communication Possibilities
- To Control Builder
- Via a serial port using the PPP protocol, or
alternatively via Ethernet - Serial Interfaces
- Available protocols are Siemens 3964R (as
master), - COMLI, MODBUS RTU (as master) and MMS.
User-defined protocols may also be used - Fieldbus Support
- PROFIBUS
- FOUNDATION Fieldbus
- On-board serial Communication
- COM 0 can receive and transmit signals
- COM 0 is the default channel for the programming
station tool port - COM 1 has a full set of modem control signals
- Each channel has LEDs indicating the status of
transmit and receive activities - RS-232 is a point-to-point communication standard
with a maximum cable length of 15 meters
48Communication Extensions
Ethernet Communication Board CI272
Profibus Communication Board CI274
RS-232 Communication Board CI271
49Communication Extensions - Serial
- RS-232 Communication Board CI271 (Option)
- There are two RJ-45 jacks for RS-232 channels
- Full set of modem control signals
- This gives a multiple RS-232 point-to-point
communication with e.g. printers, scales, bar
codes, controllers, and for multiple protocols
(COMLI, Modbus, etc)
50Communication Extensions - Ethernet
- Ethernet Communication Board CI272 (Option)
- Enables a network consisting of many
interconnected controllers, operator stations and
servers - Communication via MMS
- It has one RJ-45 jack for Ethernet 10BASE-T
(twisted pair, max. cable length 100 m)
51PROFIBUS Board CI274
- PROFIBUS Board - CI274
- A fast (12 Mb/s) PROFIBUS-DP master
- A PROFIBUS-PA can also be used, via a segment
coupler 1, in heavy industries with intrinsically
safe I/Os - The CI274 board acts as a PROFIBUS-DP master of
class 1 and up to two of them can be installed on
the AC 800C controller
52PROFIBUS Board CI274
- Can be used to connect remotely installed S800
I/O, S200 I/O, S200L I/O and third party I/O
units - Maximum length of 100 to 1200 meters, depending
on the transmission rate - S800/S800L I/O
- The S800 I/O units are connected to one or more
I/O adapters, CI830 - These I/O units are connected to one or more I/O
adapters, with a maximum of twelve I/O units per
adapter. - Additional units can be connected to the same
adapter via optical cables and optical interface
units, TB820. - S200/S200L I/O
- These I/O units are connected to one or more I/O
adapters, 200-APB12, with a maximum of eight I/O
units per adapter
53FOUNDATION Fieldbus CI 275 (future release)
- The CI275 board is an optional interface for
remote connection of 31.25 Kb/s FOUNDATION
Fieldbus devices - A maximum length of 200 to 1900 meters, depending
on cable type - The CI275 board acts as link master device
- Used to connect remotely installed I/O and
third-party units and which comply with its
specifications
54Battery Backup - SB210
- At least a year with the battery and 20 minutes
without - Low battery voltage, such as after a power
failure, is indicated by flashing PWR - Battery replacement can be performed during
operation by lifting a small lid in the
controller cover. UL-approved 3 V batteries of
type CR2430 must be used
55Power Supply
- Note
- The controller and the I/O systems should, if
possible, have separate 24 V DC supplies
56Technical Data
57Environmental Specification - Climate
58Environmental Specification - Mechanical
59CE - Compliance
60Electro Magnetic Compatibility
61Electro Magnetic Compatibility
62SoftControllerFor future release
63SoftControl An Overview
- A personal computer can be turned into a
controller by means of Control Builder software
and communication plug-in boards - Central I/O
- S200 and S200L I/O units
- Remote I/O
- Via PROFIBUS-DP and FOUNDATION Fieldbus. SattBus
(developed by ABB Automation Products) and
DataHighway Plus (from Allen-Bradley)
64Hardware mapped to Control Builder
65Communications Serial Interface
- S-232 Protocols
- A PC is usually delivered with one or two RS-232
COM-ports (COM1 and COM2) - You can add more interface boards
- Standard protocols such as PPP is specified by
use of standard Windows installation software - A range of other protocols can be defined by the
Project Explorer
66Local I/O
- S200/S200L I/O units
- Up to four plug-in boards can be handled by the
Soft Controller - each of them capable of connecting up to sixteen
I/O units - Use the ISA CIIO Board
- Alternatively, the units can be connected via
PROFIBUS-DP
67Supported S200 I/O (Local Remote)
S200C I/O Modules
S200 I/O Modules
S200L I/O Modules
68Ethernet Communication
- Ethernet
- A standard Ethernet PC board can be used if the
controller is to be connected to Ethernet - Use standard network components to build your
network
69PROFIBUS-DP Communication
- A plug-in board a PROFIBUS-DP network.
- Up to four board per SoftController
- Two adapters
- one for connection of up to eight S200/S200L I/O
units - The other for connection of up to twelve S800 I/O
units
S200 I/O Modules via PROFIBUS
S800 I/O Modules via PROFIBUS
70FOUNDATION Fieldbus
- FOUNDATION Fieldbus
- Up to thirty-two FOUNDATION Fieldbus devices can
be connected to a plug-in board. Up to four such
boards can be handled by the SoftControl
71SattBus
- SattBus is a communication protocol and a
physical layer, both developed by ABB Automation
Products - Up to 120 nodes can be connected to a SATTBUSPC
board, and up to four such boards can be handled
by the SoftController - COMLI can be used for communication on SattBus
72DataHighway Plus
- DataHighway Plus is a multi-master communication
protocol from Allen-Bradley - Up to 63 Allen-Bradley PLC-5 systems can be
connected to a DataHighway Plus board, and up to
four such boards can be handled by the
SoftController.
73Hardware Requirements
74(No Transcript)