Unit 41 Troubleshooting - PowerPoint PPT Presentation

1 / 14
About This Presentation
Title:

Unit 41 Troubleshooting

Description:

c. R-22 temperature chart is printed on each gage of the gage manifold set for ... a. The volt-ohm-milliammeter (VOM) and the clamp-on ammeter are the primary test ... – PowerPoint PPT presentation

Number of Views:981
Avg rating:3.0/5.0
Slides: 15
Provided by: robinlb
Category:

less

Transcript and Presenter's Notes

Title: Unit 41 Troubleshooting


1
Unit 41 - Troubleshooting
2
41.1. Introduction
  • a. Troubleshooting air conditioning equipment
    involves both the mechanical and electrical
    systems
  • b. Symptoms may overlap
  • c. Technicians must diagnose problems correctly

3
41.2. Mechanical Troubleshooting
  • a. Gages and temperature-testing equipment are
    used when performing mechanical troubleshooting
  • b. The most common refrigerant used in air
    conditioning equipment is R-22
  • c. R-22 temperature chart is printed on each gage
    of the gage manifold set for determining the
    saturation temperature for the low and high side
    pressures of the system

4
41.3 Gage manifold usage
  • a. Displays the low and high side pressures while
    the unit is operating
  • b. These pressures can be converted tot he
    saturation temperatures for the evaporating
    refrigerant and the condensing refrigerant by
    using the pressure and temperature relationship
  • c. Take the pressure and temperature readings at
    the condensing unit suction line to determine
    system performance when performing a superheat
    check on the evaporator
  • d. The high-side gage may be used to convert
    pressures to condensing temperatures
  • e. Gage manifolds are used whenever the pressures
    need to be known for the system
  • f. Two types of pressure connections
  • 1. Schrader valve
  • 2. Service valve
  • g. Schrader valve is a pressure connection only
  • h. Service valves can be used to isolate the
    system for service

5
41.4 When to Connect the Gages
  • a. Gage manifolds should not be connected every
    time a system is serviced
  • b. Small amounts of refrigerant escape each time
    the gages are connected and removed from a sealed
    system
  • c. Short gage hoses will limit the amount of the
    refrigerant loss
  • d. Connecting the gages to Schrader valve service
    ports with a small hand valve is another method
    of limiting the amount of refrigerant loss when
    gages are removed

6
41.5 Low Side Gage Readings
  • a. Used to compare the actual evaporating
    pressure to the normal evaporating pressure
  • b. The low side reading verifies that the
    refrigerant is boiling at the correct temperature
    for the low side of the system at some load
    condition
  • c. Standard efficiency systems usually have a
    refrigerant boiling temperature of about 35
    degrees F cooler than the entering air
    temperature at the standard operating condition
    of 75 degrees F return air with 50 humidity
  • d. Space temperature out of these ranges will
    cause an oversized load on the evaporator
  • e. Under oversized loads, the evaporator is
    absorbing an extra heat load of sensible and
    latent heat from the moisture in the air
  • f. Technicians should wait sufficient time for
    system to reduce the load before determining if
    the equipment is functioning properly
  • g. Gage readings when the system is operating in
    or close to design range will verify the system's
    true performance

7
41.6. High Side Gage Readings
  • a. Gage readings from the high side of the system
    are used to check the relationship of the
    condensing refrigerant to the ambient air
    temperature
  • b. Standard air cooled condensers condense the
    refrigerant at no more than 30 degrees F higher
    than the ambient temperature
  • c. Make sure to check the outside actual air
    temperature
  • d. High efficiency condensers perform the same as
    standard efficiency condensers, except they
    operate at lower pressures and condensing
    temperatures
  • e. High efficiency condensers normally condense
    the refrigerant at a temperature as low as 20
    degrees F higher than the ambient temperature

8
41.7 Temperature Readings
  • a. Temperature readings can be very useful when
    checking the performance of air conditioning
    equipment
  • b. Temperature leads can be attached to the high
    and low side lines for determination of the
    system's superheat and subcooling temperatures
  • c. It is important that the leads be insulated
    from the ambient air
  • d. Temperatures will vary from system to system,
    so technicians should be prepared to record and
    accurately evaluate the readings
  • e. Common temperatures used for evaluation are
  • 1. Indoor air wet and dry bulb temperatures
  • 2. Outdoor air dry-bulb temperature
  • 3. Suction-line temperature
  • 4. Condenser outlet-line temperature
  • 5. Compressor discharge-line temperature
  • f. Inlet air temperature
  • 1. Necessary to know to determine the load the
    evaporator is dealing with
  • 2. A wet-bulb reading for determining the
    humidity is necessary
  • 3. Dry-bulb temperature reading is necessary
  • g. Evaporator outlet temperature
  • 1. Evaporator outlet air temperature is seldom
    important
  • 2. Outlet dry-bulb temperature will normally be
    about 20 degrees less than inlet air temperature
  • 3. The temperature drop across an evaporator coil
    is about 20 degrees F when operating at typical
    operating conditions of an inside air temperature
    of 75 degrees F and 50 relative humidity return
    air
  • 4. If the conditioned space temperature is high
    with high humidity, the temperature drop across
    the coil will be much less because of the
    latent-heat load of moisture in the air

9
41.8 Charging Procedures in the Field
  • a. The correct charge of a system consist of
    enough refrigerant in the following
  • 1. The evaporator
  • 2. The liquid line
  • 3. The discharge line between the compressor and
    condenser
  • 4. The suction line
  • b. When the system is operating correctly under
    design conditions, there should be a prescribed
    amount of refrigerant in the condenser, the
    evaporator, and the liquid line
  • c. The amount of refrigerant in the evaporator
    can be measured by superheat
  • d. The amount of refrigerant in the condenser can
    be measured by subcooling
  • e. The amount of refrigerant in the liquid line
    may be determined by measuring the length and
    calculating the refrigerant charge
  • f. Following are methods for field charging
    different types of equipment
  • g. Fixed-bore metering devices - capillary tube
    and orifice type
  • 1. Fixed-bore metering devices do not throttle
    the refrigerant like a TXV
  • 2. They allow refrigerant flow based on the
    differences in the inlet and the outlet pressures
  • 3. Best method for checking or adjusting a
    system's charge is to follow the manufacturer's
    recommendations
  • 4. If the manufacturer's recommendations are not
    available, use the following method
  • 1. Simulate typical operating conditions
  • 2. Reduce the airflow across the condenser to
    cause the head pressure to rise to simulate a 95
    degree F outside air temperature
  • 3. For an R-22 system under these conditions, the
    head pressure would be around 278 psig
  • 4. Under these conditions with a line set of 10
    to 30 feet, the evaporator superheat should be 10
    to 15 degrees F

10
41.9 Electrical Troubleshooting
  • a. The volt-ohm-milliammeter (VOM) and the
    clamp-on ammeter are the primary test instruments
    used for troubleshooting electrical problems in
    air conditioning equipment
  • b. You need to know what the readings should be
    to know whether the existing readings are correct
    or not
  • c. The power for the control voltage is stepped
    down to 24 volts by a transformer
  • d. Begin any electrical troubleshooting by
    verifying that the power supply is energized and
    that the voltage is correct
  • e. If the power supply voltage is correct, move
    on to the various components

11
41.10 Compressor Overload Problems
  • a. When the compressor overload protector is
    open, touch the motor housing to see if it is hot
  • b. If you cannot hold your hand on the compressor
    shell, the motor is too hot
  • c. The compressor can be cooled by running cold
    water over the top of it or by disconnecting it
    and allowing it to cool
  • d. When cooling a compressor by running water
    over it, it may take 30 minutes or longer for one
    to cool that has a tripped overload

12
41.11 Compressor Electrical Checkup
  • a. Check the motor windings with an ohmmeter
  • b. Refer to the manufacturer's specifications for
    correct winding resistance values
  • c. The compressor may have a shorted winding

13
41.12 Troubleshooting the Circuit Electrical
Protectors - Fuses and Breakers
  • a. Open circuit breakers or blown fuses should be
    treated with caution
  • b. Compressors and fan motors have protection
    that will normally guard them from minor problems
  • c. The breaker or fuse is for large power surges
    in the circuits
  • d. Do not reset or replace a tripped breaker of
    fuse without trying to determine what caused the
    fuse to blow or the breaker to trip
  • Preventive Maintenance
  • a. Involves indoor and outdoor airsides and
    electrical circuits
  • b. If the fan is dirty the coil is also dirty
  • c. Coil can usually be cleaned in place with
    specially designed chemicals
  • d. Follow manufacturer's directions on chemical
    containers
  • e. Back washing is good practice
  • f. Do not use hot water or steam to clean
    refrigeration equipment
  • g. If the coil must be removed for cleaning, the
    system may be pumped down
  • h. Outdoor fan motors need to be lubricated
  • i. Outdoor fan blade should be secure
  • j. Outdoor coil is much easier to clean than the
    indoor coil
  • k. Check water bleed on water cooled systems
  • l. Make certain water treatment is correct
  • m. Contactors and relays should be inspected
  • n. All wiring connections should be tight

14
41.13 Service Technician Calls
  • a. Service call 1
  • 1. Customer complaint unit runs continuously and
    does not cool well
  • 2. Problem low refrigerant charge (R-22)
  • 3. Technician notices
  • 1. Space temperature is 80 degrees, thermostat
    set at 72
  • 2. Space is humid
  • 3. Indoor fan is running and air flow is adequate
  • 4. Condenser fan is running
  • 5. Condensing unit discharge air is not warm
  • 6. Compressor is not running and is hot to the
    touch
  • 7. High and low side pressures are 144 psig (80
    degrees)
  • 8. A low charge is suspected
  • 9. Compressor is checked and the winding
    thermostat is open
  • 4. Electrical components are covered and the
    compressor is cooled down with a water hose
  • 5. The system is restarted and the suction
    pressure drops to 40 psig (the normal suction
    pressure should be about 70 psig)
  • 6. Outside ambient is 90 degrees 90 degrees 30
    degrees 120 degrees (condensing temperature)
    120 degrees corresponds to 260 psig
  • 7. Space temperature is 80 degrees 80 degrees -
    35 degrees 45 degrees (boiling temperature) 45
    degrees corresponds to 76 psig
  • 8. The unit is charged to the correct levels and
    the operation checked
  • b. Service call 2
Write a Comment
User Comments (0)
About PowerShow.com