Title: Unit 41 Troubleshooting
1Unit 41 - Troubleshooting
241.1. Introduction
- a. Troubleshooting air conditioning equipment
involves both the mechanical and electrical
systems - b. Symptoms may overlap
- c. Technicians must diagnose problems correctly
341.2. Mechanical Troubleshooting
- a. Gages and temperature-testing equipment are
used when performing mechanical troubleshooting - b. The most common refrigerant used in air
conditioning equipment is R-22 - c. R-22 temperature chart is printed on each gage
of the gage manifold set for determining the
saturation temperature for the low and high side
pressures of the system
441.3 Gage manifold usage
- a. Displays the low and high side pressures while
the unit is operating - b. These pressures can be converted tot he
saturation temperatures for the evaporating
refrigerant and the condensing refrigerant by
using the pressure and temperature relationship - c. Take the pressure and temperature readings at
the condensing unit suction line to determine
system performance when performing a superheat
check on the evaporator - d. The high-side gage may be used to convert
pressures to condensing temperatures - e. Gage manifolds are used whenever the pressures
need to be known for the system - f. Two types of pressure connections
- 1. Schrader valve
- 2. Service valve
- g. Schrader valve is a pressure connection only
- h. Service valves can be used to isolate the
system for service
541.4 When to Connect the Gages
- a. Gage manifolds should not be connected every
time a system is serviced - b. Small amounts of refrigerant escape each time
the gages are connected and removed from a sealed
system - c. Short gage hoses will limit the amount of the
refrigerant loss - d. Connecting the gages to Schrader valve service
ports with a small hand valve is another method
of limiting the amount of refrigerant loss when
gages are removed
641.5 Low Side Gage Readings
- a. Used to compare the actual evaporating
pressure to the normal evaporating pressure - b. The low side reading verifies that the
refrigerant is boiling at the correct temperature
for the low side of the system at some load
condition - c. Standard efficiency systems usually have a
refrigerant boiling temperature of about 35
degrees F cooler than the entering air
temperature at the standard operating condition
of 75 degrees F return air with 50 humidity - d. Space temperature out of these ranges will
cause an oversized load on the evaporator - e. Under oversized loads, the evaporator is
absorbing an extra heat load of sensible and
latent heat from the moisture in the air - f. Technicians should wait sufficient time for
system to reduce the load before determining if
the equipment is functioning properly - g. Gage readings when the system is operating in
or close to design range will verify the system's
true performance
741.6. High Side Gage Readings
- a. Gage readings from the high side of the system
are used to check the relationship of the
condensing refrigerant to the ambient air
temperature - b. Standard air cooled condensers condense the
refrigerant at no more than 30 degrees F higher
than the ambient temperature - c. Make sure to check the outside actual air
temperature - d. High efficiency condensers perform the same as
standard efficiency condensers, except they
operate at lower pressures and condensing
temperatures - e. High efficiency condensers normally condense
the refrigerant at a temperature as low as 20
degrees F higher than the ambient temperature
841.7 Temperature Readings
- a. Temperature readings can be very useful when
checking the performance of air conditioning
equipment - b. Temperature leads can be attached to the high
and low side lines for determination of the
system's superheat and subcooling temperatures - c. It is important that the leads be insulated
from the ambient air - d. Temperatures will vary from system to system,
so technicians should be prepared to record and
accurately evaluate the readings - e. Common temperatures used for evaluation are
- 1. Indoor air wet and dry bulb temperatures
- 2. Outdoor air dry-bulb temperature
- 3. Suction-line temperature
- 4. Condenser outlet-line temperature
- 5. Compressor discharge-line temperature
- f. Inlet air temperature
- 1. Necessary to know to determine the load the
evaporator is dealing with - 2. A wet-bulb reading for determining the
humidity is necessary - 3. Dry-bulb temperature reading is necessary
- g. Evaporator outlet temperature
- 1. Evaporator outlet air temperature is seldom
important - 2. Outlet dry-bulb temperature will normally be
about 20 degrees less than inlet air temperature - 3. The temperature drop across an evaporator coil
is about 20 degrees F when operating at typical
operating conditions of an inside air temperature
of 75 degrees F and 50 relative humidity return
air - 4. If the conditioned space temperature is high
with high humidity, the temperature drop across
the coil will be much less because of the
latent-heat load of moisture in the air
941.8 Charging Procedures in the Field
- a. The correct charge of a system consist of
enough refrigerant in the following - 1. The evaporator
- 2. The liquid line
- 3. The discharge line between the compressor and
condenser - 4. The suction line
- b. When the system is operating correctly under
design conditions, there should be a prescribed
amount of refrigerant in the condenser, the
evaporator, and the liquid line - c. The amount of refrigerant in the evaporator
can be measured by superheat - d. The amount of refrigerant in the condenser can
be measured by subcooling - e. The amount of refrigerant in the liquid line
may be determined by measuring the length and
calculating the refrigerant charge - f. Following are methods for field charging
different types of equipment - g. Fixed-bore metering devices - capillary tube
and orifice type - 1. Fixed-bore metering devices do not throttle
the refrigerant like a TXV - 2. They allow refrigerant flow based on the
differences in the inlet and the outlet pressures - 3. Best method for checking or adjusting a
system's charge is to follow the manufacturer's
recommendations - 4. If the manufacturer's recommendations are not
available, use the following method - 1. Simulate typical operating conditions
- 2. Reduce the airflow across the condenser to
cause the head pressure to rise to simulate a 95
degree F outside air temperature - 3. For an R-22 system under these conditions, the
head pressure would be around 278 psig - 4. Under these conditions with a line set of 10
to 30 feet, the evaporator superheat should be 10
to 15 degrees F
1041.9 Electrical Troubleshooting
- a. The volt-ohm-milliammeter (VOM) and the
clamp-on ammeter are the primary test instruments
used for troubleshooting electrical problems in
air conditioning equipment - b. You need to know what the readings should be
to know whether the existing readings are correct
or not - c. The power for the control voltage is stepped
down to 24 volts by a transformer - d. Begin any electrical troubleshooting by
verifying that the power supply is energized and
that the voltage is correct - e. If the power supply voltage is correct, move
on to the various components
1141.10 Compressor Overload Problems
- a. When the compressor overload protector is
open, touch the motor housing to see if it is hot - b. If you cannot hold your hand on the compressor
shell, the motor is too hot - c. The compressor can be cooled by running cold
water over the top of it or by disconnecting it
and allowing it to cool - d. When cooling a compressor by running water
over it, it may take 30 minutes or longer for one
to cool that has a tripped overload
1241.11 Compressor Electrical Checkup
- a. Check the motor windings with an ohmmeter
- b. Refer to the manufacturer's specifications for
correct winding resistance values - c. The compressor may have a shorted winding
1341.12 Troubleshooting the Circuit Electrical
Protectors - Fuses and Breakers
- a. Open circuit breakers or blown fuses should be
treated with caution - b. Compressors and fan motors have protection
that will normally guard them from minor problems - c. The breaker or fuse is for large power surges
in the circuits - d. Do not reset or replace a tripped breaker of
fuse without trying to determine what caused the
fuse to blow or the breaker to trip - Preventive Maintenance
- a. Involves indoor and outdoor airsides and
electrical circuits - b. If the fan is dirty the coil is also dirty
- c. Coil can usually be cleaned in place with
specially designed chemicals - d. Follow manufacturer's directions on chemical
containers - e. Back washing is good practice
- f. Do not use hot water or steam to clean
refrigeration equipment - g. If the coil must be removed for cleaning, the
system may be pumped down - h. Outdoor fan motors need to be lubricated
- i. Outdoor fan blade should be secure
- j. Outdoor coil is much easier to clean than the
indoor coil - k. Check water bleed on water cooled systems
- l. Make certain water treatment is correct
- m. Contactors and relays should be inspected
- n. All wiring connections should be tight
1441.13 Service Technician Calls
- a. Service call 1
- 1. Customer complaint unit runs continuously and
does not cool well - 2. Problem low refrigerant charge (R-22)
- 3. Technician notices
- 1. Space temperature is 80 degrees, thermostat
set at 72 - 2. Space is humid
- 3. Indoor fan is running and air flow is adequate
- 4. Condenser fan is running
- 5. Condensing unit discharge air is not warm
- 6. Compressor is not running and is hot to the
touch - 7. High and low side pressures are 144 psig (80
degrees) - 8. A low charge is suspected
- 9. Compressor is checked and the winding
thermostat is open - 4. Electrical components are covered and the
compressor is cooled down with a water hose - 5. The system is restarted and the suction
pressure drops to 40 psig (the normal suction
pressure should be about 70 psig) - 6. Outside ambient is 90 degrees 90 degrees 30
degrees 120 degrees (condensing temperature)
120 degrees corresponds to 260 psig - 7. Space temperature is 80 degrees 80 degrees -
35 degrees 45 degrees (boiling temperature) 45
degrees corresponds to 76 psig - 8. The unit is charged to the correct levels and
the operation checked - b. Service call 2