Title: Earthing configurations
1Earthing configurations
2Earthing or not?
- Is that the question?
- It is often thought that an electrical appliance
can only be earthed or not earthed. - But the earthing connection comes from the
socket. What about the other end of the wire? - We should be aware that several earthing
configurations exist.
3Expert work
- Not every configuration ensures safety and
functionality for each environment, and some
configurations are more cost-effective than
others. - Choosing the right configuration is expert work.
- It is recommended that the voltage and current
distributions that would be effected in case of a
fault be investigated before opting for a certain
configuration.
4The local earth electrode
- In most cases, exposed conductive parts of
equipment (metallic frames and enclosures) are
connected to a local earth electrode in the
basement of the building (or provided by the
utility for small installations). - This is always useful, if not for conducting an
earth fault current, then for conducting a
lightning strike. - But this will neither exclude every risk of
electrical shock nor guarantee flawless operation
of electronic devices.
5Different earthing configurations
- The power for the equipment is supplied by a
transformer, which is situated on the site itself
or is part of the distribution network. - The star point of this supply transformer may be
earthed to provide extra safety. - If both earthing systems are present (consumer
side and supply side), they may or may not be
connected.
6The abbreviations for earthing configurations
- The first character describes the supply side.
- The second character describes the consumer side.
- The third character describes the way of
connection, if any. - The letters and their meanings are
- T terre (earthed)
- I isolée (not earthed)
- N neutre (neutral conductor)
- C commune (combined)
- S séparée (separate)
7Without an earthed star point IT (Isolée Terre)
- IT systems tend to be used in very specific
circumstances - IT systems are governed by specific regulations
8The IT configuration
- Major advantage the system can continue to
operate after the first earth fault. In most
cases, this is prohibited, except when the
continuity of the supply is critical (e.g.
operating theatres, chemical industry) - This configuration needs to be combined with a
monitoring device that can detect an earth fault.
An earth fault should be repaired as soon as
possible - A Residual Current Device (RCD) is required(a
Residual Current Monitoring System, or RCM might
be better to prevent nuisance tripping)
9With an earthed star point
- If the discipline to repair each earth fault
quickly cannot be guaranteed, it is recommended
that the star point of the transformer be earthed - Earthing the star point is by far the most common
practice - When this is done, there are still several
possible configurations left TN-C, TN-S, TN-C-S,
and TT
10The TN-C configuration (Terre-Neutre-Commune)
11TN-C or TN-S?
- In a TN-C configuration, the extraneous parts are
connected to the neutral wire. The main
disadvantage is that the currents in the neutral
could cause EMC problems ( interference with
signals of electronic devices). - To counter this, a separate protected earth cable
could be provided that is the TN-S system. This
system is superior in performance but more
expensive.
12The TN-S configuration (Terre-Neutre-Séparée)
13The TN-C-S configuration
A good compromise can be the TN-C-S system, in
which there is a separate cable inside the
building where EMC problems could occur, and only
the neutral wire outside the building
PCC
N
PEN
PE
PE
14Another option the TT-configuration (Terre-Terre)
15The TT configuration
- TT combines features of the IT and TN
configurations. - It has a better EMC than TN-C, it is cheaper than
TN-S, and safer than IT. - The disadvantage is that it requires a Residual
Current Device, and, in some cases, EMC problems
might still occur.
16Round-up
- Several earthing configurations exist.
- Choosing the optimal one is a complex decision
that should be made by experts. - In the event of a fault, the voltage and current
distributions should be investigated. - Arguments that influence the choice required
security of supply, cost, assumed discipline of
the users, EMC problems, RCD or RCM or fuses
required.
17Links and references
- Standard IEC 60364-3, available from www.iec.ch
- A Systems Approach to Earthing
- Earthing Systems Fundamentals of Calculation
Design - Earthing Systems Basic Constructional Aspects
www.leonardo-energy.org/drupal/apguide