1
Inherently Safer Design Example
  • Dennis C. Hendershot
  • Rohm and Haas Company
  • Engineering Division
  • Croydon, PA
  • Dhendershot_at_rohmhaas.com
  • 2003 SACHE Faculty Workshop
  • Baton Rouge, LA
  • September, 2003

2
Scenario
  • You are the chief engineer for a municipal water
    and sewer department. You are asked to identify
    inherently safer technologies for treatment of
    drinking water and also for disinfection of
    effluent from the municipal sewage treatment
    plant prior to discharge to a stream. You are
    chartered to investigate options from the basic
    treatment technology through options to improve
    the inherent safety of the existing chlorination
    facility (chlorine usage is one 90 ton rail car
    every month, both for the drinking water and
    sewage treatment plant).

3
Basic technology
  • Options for municipal drinking water
  • Identify options to eliminate or significantly
    reduce chlorine usage
  • New hazards for the options?
  • Options for waste water effluent disinfection
  • Identify options to eliminate or significantly
    reduce chlorine usage
  • New hazards for the options?

4
Existing water treatment process options
  • Objective drinking water and sewage plant
    effluent chlorinated to the concentration
    required by public health and environmental
    authorities
  • Both existing plants use 90 ton chlorine rail
    cars with liquid chlorine transferred with
    pressure (say 125 psig, from the chlorine vapor
    pressure and a nitrogen blanket) about 200 feet
    across a site road in a 2 inch pipe to a 50 psig
    steam heated vaporizer, then gaseous chlorine is
    injected into the water
  • Identify design alternatives and discuss inherent
    safety advantages and disadvantages