Protect 2 - PowerPoint PPT Presentation

1 / 14
About This Presentation
Title:

Protect 2

Description:

Booster and Charger. Battery U DC nominal 20kVA : 2 x ... booster mode / line fail : battery voltage = 2 x 400V DC. charger capacity : 3kW (20kVA system) ... – PowerPoint PPT presentation

Number of Views:11
Avg rating:3.0/5.0
Slides: 15
Provided by: dietmarp
Category:

less

Transcript and Presenter's Notes

Title: Protect 2


1
Presentation
  • Protect 2

2
Allround UPS - Product portfolio
PROTECT 2. 33
PROTECT 3. 31
PROTECT 3. 33
PROTECT 4. 33
3
PROTECT 2. 33 20kVA (10kVA) weight 250kg
without battery 490kg with integrated
battery PROTECT 2. 33 40kVA
(30kVA) weight 400 kg without battery
1500mm
4
New UPS Protect 2.33
30 / 40kVA
10 / 20kVA
1500mm
1900mm
5
Whats new ?
  • Transformerless


SBS
Mains
Loads
Pulse-Rectifier
Inverter
  • 2x 400Vdc

Safe load bus
  • sinusodial Input current
  • 2x 132V- 2x232Vdc

Battery
UPS
6
New UPS Protect 2.33
Normal-Mode (Mains available)
Loads
  • 2x 400Vdc
  • 2x 132- 2x 228VDC

7
BATTERY-Mode
8
BYPASS-Mode
9
New UPS Protect 2.33
DC voltage 2 x 400V 800V
  • Inverter
  • Rectifier

3 x 400V
3 x 400V
Battery U DC nominal lt 20kVA 2 x 132V - 2 x
228V lt 40kVA 2 x 192V - 2 x 228V 2 x 11 - 2
x 19blocks DC range 210 - 550V
Booster and Charger
10
New UPS Protect 2.33
  • Rectifier
  • IGBT technology
  • sinusoidal input current
  • low THD I lt 3 (low harmonics, compliant with
    actual and future standards IEC 61000-3-12 / IEC
    61000-3-4 / IEEE 519)
  • Cos-Phi / Power factor gt0.99

11
New UPS Protect 2.33
Sinusoidal Input Current as build-in Feature
Input Voltage 100 V / screen t 5 ms /
screen Input Current THDi lt 3 20A / screen
12
New UPS Protect 2.33
  • Booster / Charger
  • IGBT technology
  • DC/DC converter
  • charger mode 2 x 400V DC gt battery voltage
  • booster mode / line fail battery voltage gt 2 x
    400V DC
  • charger capacity 3kW (20kVA system)
  • Battery Charging Management AeBM

13
New UPS Protect 2.33
  • Inverter
  • IGBT technology
  • High-Speed ST 10 Controller for fast dynamic
    regulation
  • output voltage with low THD U lt 3 at nonlinear
    load
  • able to handle capacitive and inductive loads

14
New UPS Protect 2.33
  • Static Bypass / Manual Bypass
  • SCR technology (Thyristors)
  • convection cooled
  • fully 100 rated
  • overload / short circuit capacity 1000 -
  • synchronization to an alternate line voltage with
    high harmonic content
  • THDu lt 10 IEC 61000-2-4 Class 3 for
    industrial environment !
  • synchronization range adjustable
  • slew rate adjustable
  • Manual bypass switch integrated

15
New UPS Protect 2.33
  • Battery for Protect 2 10 / 20kVA
  • nominal battery voltage 2 x 132V - 2 x 228V
  • integrated standard battery voltage 2 x 132V
  • (2 x 11 blocks Panasonic LC-X 1228 AP )
  • gt 10kVA - 30min
  • gt 20kVA - 10min
  • higher flexibility, to adjust any required
    battery back-up time with various number of cells
  • avoids oversizing of battery
  • extended back-up time available with external
    battery

16
New UPS Protect 2.33
  • Battery for Protect 2 30 / 40kVA
  • nominal battery voltage 2 x 192V - 2 x 228V
  • integrated standard battery voltage 2 x 216V
  • (2 x 18 blocks Panasonic LC-X 1228 AP)
  • gt 30kVA - 10min
  • gt 40kVA - 7.5min
  • higher flexibility, to adjust any required
    battery back-up time with various number of cells
  • avoids oversizing of battery
  • extended back-up time available with external
    battery

17
New UPS Protect 2.33
External Battery Cabinet - 2 x 11 blocks
20kVA / 10min - 4 x 11 blocks 20kVA /
30min internal battery plus external battery
with 6 x 11 blocks 20kVA / 50min
18
New UPS Protect 2.33
External Battery Cabinet - 2 x 18 blocks
40kVA / 7.5min - 4 x 18 blocks 40kVA /
22min internal battery plus external battery
with 6 x 18 blocks 40kVA / 40min
Write a Comment
User Comments (0)
About PowerShow.com