Title: Safety Systems for ALICE


1
Safety Systems for ALICE
  • DSS Detector Safety System under the
    responsibility of ALICE (safe part of
    DCS) treats Level 1 and 2 alarms
  • CSAM CERN Safety Alarm Monitoring under the
    responsibility of TS-CSE (former ST-MA,
    contract B1171/ST) treats Level-3 alarms
  • SNIFFER air sampling system for detection
    of - ODH Oxygen Deficiency Hazard -
    Flammable gas leak - Smoke from fire and
    hot-spots sends alarms to CSAM


2
CSS CERN Safety System
SCR Fire Station
TCR Tech. Specialists

CSAM
  • 9 types of
  • Detectors of Hazards

SNIFFER System ODH, Fl.Gas, Smoke
3
CSAM - general
  • Highly reliable alarm transmission system
  • Based on PLC and SCADA industrial technology
  • Supported by international safety standards
  • Available 24h/d, 365d/y
  • Defined by the AL3S working group
  • Designed for CERN, not only for LHC
  • Approved by SC (TIS), including experienced
    firemen
  • Approved by TCR representatives
  • INB compliant
  • Maintenance integrated in the Maintenance Manager
    System


4
CSAM - inputs
9 possible types of entries, including the
SNIFFER
  • Smoke detectors 40 5
  • Flammable gas detectors 20 5
  • ODH detectors 10 5
  • Water detectors (flooding) 10
  • Evacuation signals 40
  • Red buttons 50
  • Red telephones 10
  • Dead-man detector 1
  • Blocked lifts 2


5
CSAM some inputs
Some safety systems are already in place at Pt-2
  • Smoke detectors in SX-2 and SXL-2 in UX-25
  • Evacuation buttons and alarm everywhere
  • Red buttons //
  • Red telephones //
    (Note that the normal phones have been
    dismantled from underground areas.)
  • Blocked-lift alarms in lifts
  • to be rejuvenated in 2005
  • ODH and gas detectors to be defined


6
CSAM example of inputs

7
CSAM - outputs
  • CSAM sends alarms to
  • Safety Control Room (SCR, fire station),
  • they send the firemen.
  • Technical Control Room (TCR),
  • they send the relevant specialists if needed.
  • Note Installation planned in April-May
    2004 at Pt-2.
  • DSS/DCS sends alarms to ALICE Control Room.


8
Sniffers racks
9
Sniffer tubes
10
CSAM - actions
  • CSAM sends alarms to the firemen.
  • Whats next ??
  • Cut the power ( gas) at the place of alarm
  • If the alarm comes from UX-25 ? request to
    stop the beam send the firemen relevant
    specialists
  • If the alarm comes from inside L3
    magnet ? flush N2 ? (under study)


11
Open Safety Issue
  • Fire detection (and fire fighting) in Electronic
    Racks
  • Proposal from TS-CSE
  • - 1 smoke sensor per normal rack
  • - signal sent to DSS for automatic action to
    be defined
  • - one possible action cut-off power of the
    Hazemayer powering ( 1 or ) 23 racks.
  • Possible solution
  • - 2 smoke sensors per rack
  • - wired logic cutting of power of the given
    rack
  • signal sent to DCS for info
  • Required automatic fire-fighting ?