Title: Class 19 Control System Instrumentation
1Class 19 Control System Instrumentation
2How Do We Implement Our Control Strategies?
3How Do We Implement Our Control Strategies?
It is necessary to measure (at least) the output
variable, transfer the signal, and manipulate one
of the input variables
4How Do We Implement Our Control Strategies?
We need One instrument, one transducer, And one
actuator
5Measurement - Transducer
This is the general configuration of a
measurement transducer This typically consists of
a sensing element combined with a driving element
(transmitter) Sometimes, the whole thing is
called transducer
6Measurement - Transducer
Transducers convert the magnitude of a process
variable (e.g., flow rate, pressure, temperature,
level, or concentration) into a signal that can
be sent directly to the controller The sensing
element is required to convert the measured
process variable into some quantity more
appropriate for mechanical or electrical
processing within the transducer
7Sensors - Selection Criteria
Measurement range (span) Performance Reliability M
aterials of construction Prior use Potential for
releasing substances to the environment Electrical
classification (safety) Invasive or non-invasive
8Sensors - Temperature
Termocouple (widely used for Tlt1000C) Resistance
temperature detector Bimetal thermometer Pyrometer
Surface acoustic wave
9Sensors - Flow
Orifice Venturi Roameter Turbine Coriolis
(becoming popular)
10Sensors - Pressure
Liquid column Elastic element (diaphragm) Piezoele
ctric Optical fiber
11Sensors - Level
Float - activated Head devices Electrical Radiatio
n
12Sensors - Composition
Gas-liquid chromatography Mass spectroscopy Infrar
ed spectroscopy Thermal conductivity Refractive
index Electrophoresis Electrochemical
Note this is the most difficult measurement in
process engineering. One chemical composition
analysis system can cost 100,000. It is often
preferred to do indirect measurements (refractive
index) frequently and on-line, and quantitative
measurements less frequently and off-line.
13Transmitter
A transmitter converts the sensor output to a
signal level appropriate for input to a
controller (usually a computer) This signal tends
to be a current, in the range 4 to 20
mA Transmitters tend to be direct acting the
output signal increases as the measured variable
increases Commercial transmitters have adjustable
input range (span) and zero
14Transmitter - Example
- A temperature transmitter might be adjusted so
that the input range of a platinum resistance
element (the sensor) is 50 to 150 C. The
following correspondence is obtained
- This transducer has a zero of 50 C and a range
or span of 100 C - The relation between transducer output and input
is
15Transmitter - Example
The gain of the measurement element Km is 0.16
mA/C For any linear instrument
Not all transducers are linear Forgetting
non-ideality (which we always do in our examples)
may lead to big problems in practice
16Transmitter - Example
Example of linear instrument calibration
17Final Control Element - Actuator
- Every process control loop contains a final
control element (actuator), the device that
enables a process variable to be manipulated - For most chemical and petroleum processes, the
final control elements (usually control valves)
adjust the flow rates of materials, and
indirectly, the rates of energy transfer to and
from the process - The control valve components include valve body,
trim, seat, and actuator - We will discuss pneumatic valves, but motors can
also be used to adjust the trim
18Final Control Element - Valves
- There are many different ways to manipulate the
flows of material and energy into and out of a
process for example, the speed of a pump drive,
screw conveyer, or blower can be adjusted - However, a simple and widely used method of
accomplishing this result with fluids is to use a
control valve, also called an automatic control
valve - The the choice of air-to-open (A-O) or
air-to-close (A-C) valve is based on safety
considerations - This consideration depends on the transducer
when power goes off, the transducer signal goes
to the lowest value in the range (for
direct-acting transducers) do we need open or
close valve when that happens?
19Pneumatic Valves
A pneumatic control valve (air-to-open)
20Pneumatic Valves - Example 1
Pneumatic control valves are to be specified for
the applications listed below. State whether an
A-O or A-C valve should be used for the following
manipulated variables and give reason(s).
- Steam pressure in a reactor heating coil.
- Flow rate of reactants into a polymerization
reactor. - Flow of effluent from a wastewater treatment
holding tank into a river. - Flow of cooling water to a distillation condenser.
21Specifying Control Valves
A design equation used for sizing control valves
relates valve lift to the actual flow rate q
by means of the valve coefficient Cv, the
proportionality factor that depends predominantly
on valve size or capacity
When you buy a valve, you need to specify Cv,
together with valve type, material, etc.
22Specifying Control Valves
A design equation used for sizing control valves
relates valve lift to the actual flow rate q
by means of the valve coefficient Cv, the
proportionality factor that depends predominantly
on valve size or capacity
- Here q is the flow rate, is the flow
characteristic, is the pressure drop
across the valve, and gs is the specific gravity
of the fluid. - This relation is valid for nonflashing fluids.
23Specifying Control Valves
- Specification of the valve size is dependent on
the so-called valve characteristic f (l). - Three control valve characteristics are mainly
used. - For a fixed pressure drop across the valve, the
flow characteristic is
related to the lift , that is,
the extent of valve opening, by one of the
following relations
R 20-50
24Control Valves Characteristics
25Control Valves Rangeability
The rangeability of a control valve is defined as
the ratio of maximum to minimum input signal
level. For control valves, rangeability
translates to the need to operate the valve
within the range 0.05 f 0.95 or a
rangeability of 0.95/0.05 19.
26Specifying Control Valves - Example
A pump furnishes a constant head of 40 psi over
the entire flow rate range of interest. The heat
exchanger pressure drop is 30 psig at 200 gal/min
(qd) and can be assumed to be proportional to q2.
Select the rated Cv of the valve and plot the
installed characteristic for the following case
- A linear valve that is half open at the design
flow rate.
27Solution First we write an expression for the
pressure drop across the heat exchanger
(simplification of the Bernoullis equation)
Because the pump head is constant at 40 psi, the
pressure drop available for the valve is
Figure 9.11 illustrates these relations. Note
that in all four design cases at qd.
28(No Transcript)
29- First calculate the rated Cv.
We will use Cv 125. For a linear characteristic
valve, use the relation between and q from
Eq. 9-2
Using Eq. 9-9 and values of from Eq. 9-7,
the installed valve characteristic curve can be
plotted.
30(No Transcript)
31Accuracy in Instrumentation
Figure 9.13 Analysis of types of error for a flow
instrument whose range is 0 to 4 flow units.
32Accuracy in Instrumentation
We need to distinguish between Error Precision R
esolution Accuracy Repeatability
33Accuracy in Instrumentation
Analysis of instrument error showing the
increased error at low readings
34Accuracy in Instrumentation
Figure 9.15 Nonideal instrument behavior (a)
hysteresis, (b) deadband.