Title: Control and regulation of boiler operation
1Control and regulation of boiler operation
2Contents
- Hot- and warm water boiler operation controland
safety limits - Domestic heating and hot water generation control
- Hot- and warm water boiler operation controland
safety limits- Spray type superheat control-
Water level control - Boiler controls for operation without permanent
supervision - Steam supply system principals
- Steam traps
3Hot- and warm water boiler operation control
Thermal oil boiler control is similar
- In these type of systems there is not phase
change only heating up of heat transfer medium
happens. Useful heat can be expressed according
to following expression. - Quseful mwater ? c ?( tout tin )
- Heat supply is controlled mainly by two ways-
In case of quantity control inlet and outlet
temperature level constant and mass flow rate of
heat transfer medium is modified - In case of
quality control inlet and outlet temperature
level modified and mass flow rate of heat
transfer medium is constant - Power level control happens generally from outlet
temperature of the boiler(Power level control
means burning fuel control done generally by
fuel inlet quantity control)
4Safety limits
- Maximal outlet temperature
- Minimal inlet temperature(in case of non
condensing boilers) - Overpressure limitation
- Heat transfer medium absence limitation
- Minimal flow limitation
5Domestic heating system control
6Heating water temperature variation
7Domestic heating and hot water generation control
8Steam generator operation control
- In case of steam generator useful heat can be
calculated according to following expression - Quseful msteam ? ( hout hin )
- Heat demand variation results variation of steam
mass flow rate. Mass flow rate variation at
constant power level and at constant feed water
parameters results outlet enthalpy and outlet
pressure variation. - Power level control happens generally by means of
outlet pressure control, because of previously
detailed phenomena.(Power level control means
burning fuel control done generally by fuel
inlet quantity control)
9Outlet temperature control
- In case of saturated steam outlet temperature is
not needs to be controlled, because outlet
temperature is determined by saturation
condition. - But in case of superheated steam generation
superheat temperature is affected by load
conditions, and several operation parameters, so
it needs to be controlled. - Earlier several methods were used for superheat
temperature control, - but nowadays only spray type superheat control is
used.
10Spray type superheat control
- Of all the direct contact types, the spray
attemperator has proved most satisfactory. - Water of high purity is injected directed into
the superheated steam main or into a mingling
chamber. - The water is sprayed in through a series of
nozzles at the throat of a venturi section,
forming a fine mist. - It is quickly vaporized and first mixes with and
then cools the superheated steam. The design must
include a thermal sleeve to protect the piping
from thermal shock caused by water droplets
striking the hot surface.
11Spray at different locationsfor outlet steam
temperature controlat the boiler outlet in
between two superheater
12Installation of a spray type attemperator
13Installation of a spray type attemperator
14Typical injector construction of spray type
attemperators
15Feed water quantity control
- According to actual evaporated water quantity the
same amount of feed water needs to be fed into
the boiler. - Generally water level in the drum is used for
this task. - In case of once-through type boilers it has to be
connected with power level control.
16Water level sensors
17Water quality control
- At any type of water treatment a certain amount
of salt is delivered to the boiler with feed
water. - But the steam delivers nearly any salt out from
the boiler. - So salt is accumulated in boiler water. Over a
certain concentration it can cause operation
troubles e.g. foaming of water, etc. - So salt concentration needs to be held below a
certain concentration level. - This is solved by letting out some boiler water
quantity, which is called slugging or
desalination. Fresh feed water will reduce salt
concentration
18General safety limitations
- Maximal outlet pressure is generally limited by
both- electronic and - mechanical way with
safety valves - Maximal outlet temperature
- Water level limitation- minimal more important-
maximal less important - Boiler water quality limitation- salt
concentration by means of water conductivity
19Boiler operation supervision
- In general case boiler operation is potential
danger, so it needs continuous attendance to
supervise. - With fulfilling special requirements boiler can
be operated without permanent attendance. But it
does not mean without attendance, it means only
that supervisor visit needs to be held regularly,
and not continuously. - Special requirement means that boiler has to be
protected automatically from all the possible
dangerous operation condition
20Boiler controls
21Shell boilers controls
22Condensate monitoring for salt and oil pollution
23Boiler and auxiliary controls
24Steam supply system principals
25Flash steam formation
26Flash steam formation
27Example for steam trap installation
28Float steam trap
29Operation of a thermodynamic steam trap
30Operation of a bimetal steam trap
31Termic steam trap
32Summary
- You are already familiar with
- Hot- and warm water boiler operation controland
safety limits - Domestic heating and hot water generation control
- Hot- and warm water boiler operation controland
safety limits- Spray type superheat control-
Water level control - Boiler controls for operation without permanent
supervision - Steam supply system principals
- Steam traps