Title: ENERGY CONVERSION ONE (Course 25741)
1ENERGY CONVERSION ONE (Course 25741)
- Chapter Two
- TRANSFORMERS
- continued
2Transformer Voltage Regulation and Efficiency
- Output Voltage of Transformer Varies with Load
- Due to Voltage Drop on Series Impedance of
Transformer Equivalent Model - Full Load Regulation Parameter, compares output
no-load Voltage with its Full Load Voltage -
V.R. - At no load VS VP / a thus
-
V.R. - in per unit V.R.
-
- For Ideal Transformer V.R.0
-
3Transformer Voltage Regulation and Efficiency
- The transformer phasor diagram
- To determine the voltage regulation of a
transformer - The voltage drops should be determined
- In below a Transformer equivalent circuit
referred to the secondary side shown
4Transformer Voltage Regulation and Efficiency
- since current which flow in magnetizing branch is
small can be ignored - Assuming secondary phasor voltage as reference
VS with an angle of 0? - Writing the KVL equation
-
- From this equation the phasor diagram can be
shown - At lagging power factor
5Transformer Voltage Regulation and Efficiency
- If power factor is unity, VS is lower than VP so
V.R. gt 0 - V.R. is smaller for lagging P.F.
- With a leading P.F., VS is larger VP ? V.R.lt0
- P.F. 1
- ?
- P.F. leading
- ?
6Transformer Voltage Regulation and Efficiency
- Table Summarize possible Value for V.R. vs Load
P.F. -
- Since transformer usually operate at lagging
P.F., a simplified method is introduced
Lagging P.F. VP/ a gt VS V.R. gt 0
Unity P.F. VP / a gt VS V.R. gt0 (smaller)
Leading P.F. VS gt VP/ a V.R. lt 0
7Transformer Voltage Regulation and Efficiency
- Simplified Voltage Regulation Calculation
- For lagging loads the vertical components
related to voltage drop on Req Xeq partially
cancel each other ?angle of VP/a very small -
-
8Transformer Voltage Regulation and Efficiency
- Transformer Efficiency (as applied to motors,
generators and motors) - Losses in Transformer
- 1- Copper I²R losses
- 2- Core Hysteresis losses
- 3- Core Eddy current losses
- Transformer efficiency may be determined as
follows -
9Transformer Voltage Regulation and Efficiency
- Example
- A 15kVA, 2300/230 V transformer tested to
determine 1- its excitation branch components, 2-
its series impedances, and 3- its voltage
regulation - Following data taken from the primary side of the
transformer
Open Circuit Test Short Circuit Test
VOC2300 V VSC47 V
IOC0.21A ISC6 A
POC 50 W PSC 160 W
10Transformer Voltage Regulation and Efficiency
- (a) Find the equivalent circuit referred to H.V.
side - (b) Find the equivalent circuit referred to L. V.
side - (c) Calculate the full-load voltage regulation at
0.8 lagging PF, 1.0 PF, and at 0.8 leading PF - (d) Find the efficiency at full load with PF 0.8
lagging - SOLUTION
- Open circuit impedance angle is
- Excitation admittance is
11Transformer Voltage Regulation and Efficiency
- Impedance of excitation branch referred to
primary - Short Circuit Impedance angle
- Equivalent series Impedance
-
Req4.45 O, Xeq6.45 O -
12Transformer Voltage Regulation and Efficiency
- The equivalent circuits shown below
-
13Transformer Voltage Regulation and Efficiency
- (b) To find eq. cct. Referred to L.V. side,
- impedances divided by a²NP/NS10
- RC1050 O , XM110 O
- Req0.0445 O , Xeq0.0645 O
- (c) full load current on secondary side
- IS,ratedSrated/ VS,rated15000/230
65.2 A - To determine V.R., VP/ a is needed
- VP/a VS Req IS j Xeq IS , and
- IS65.2/_-36.9? A , at PF0.8 lagging
14Transformer Voltage Regulation and Efficiency
- Therefore
- VP / a
- V.R.(234.85-230)/230 x 100 2.1 for 0.8
lagging - At PF0.8 leading ? IS65.2/_36.9? A
- VP / a
-
15Transformer Voltage Regulation and Efficiency
- V.R. (229.85-230)/230 x 100 -0.062
- At PF1.0 , IS 65.2 /_0? A
- VP/a
- V.R. (232.94-230)/230 x 100 1.28 for PF1
-
16Transformer Voltage Regulation and Efficiency
17Transformer Voltage Regulation and Efficiency
- (d) to plot V.R. as a function of load is by
repeating the calculations of part c for many
different loads using MATLAB -
18Transformer Voltage Regulation and Efficiency
- (e) Efficiency of Transformer
- - Copper losses
- PCu(IS)²Req (65.2)² (0.0445)189 W
- - Core losses
- PCore (VP/a)² / RC (234.85)² / 105052.5 W
- output power
- PoutVSIS cos?230x65.2xcos36.9?12000 W
- ? VSIS cos? / PCuPCoreVSIS cos? x 100
- 12000/ 18952.512000 98.03
19Efficiency of Distribution Transformers
20Energy Losses in Electrical Energy Systems
- The total electrical energy use per annum of the
world is estimated as 13,934 - TeraWatthours TWh (1 TWh 109 kWh)
- it is further estimated 2 that the losses in
all of the worlds electrical distribution
systems total about 1215 TWh or - about 8.8 of the total electrical energy
consumed. About 30-35 of these losses are
generated in the Transformers in the Distribution
systems. - Studies estimate that some 40-80 of these
transformer losses are potentially saveable by
increasing transformer efficiencies, i.e. 145-290
TWh.
21Electrical Energy Losses in Distribution Networks
22Transformer Taps Voltage Regulation
- Distribution Transformers have a series taps in
windings which permit small changes in turn ratio
of transformer after leaving factory - A typical distribution transformer has four taps
in addition to nominal setting, each has a 2.5
of full load voltage with the adjacent tap - This provides possibility for voltage adjustment
below or above nominal setting by 5
23Transformer Taps Voltage Regulation
- Example A 500 kVA, 13200/480 V distribution
transformer has 4, 2.5 taps on primary winding.
What are voltage ratios? - Five possible voltage ratings are
- 5 tap 13860/480 V
- 2.5 tap 13530/480 V
- Nominal rating 13200/480 V
- -2.5 tap 12870/480 V
- -5 tap 12540/480 V
24Transformer Taps Voltage Regulation
- Taps on transformer permit transformer to be
adjusted in field to accommodate variations in
tap voltages - While this tap can not be changed when power is
applied to transformer - Some times voltage varies widely with load, i.e.
when high line impedance exist between
generators particular load while normal loads
should be supplied by an essentially constant
voltage - One solution is using special transformer called
tap changing under load transformer - A voltage regulator is a tap changing under load
transformer with built-in voltage sensing
circuitry that automatically changes taps to
preserve system voltage constant
25AUTO TRANSFORMER
- some occasions it is desirable to change voltage
level only by a small amount - i.e. may need to increase voltage from 110 to 120
V or from 13.2 to 13.8 kV - This may be due to small increase in voltage drop
that occur in a power system with long lines - In such cases it is very expensive to hire a two
full winding transformer, however a special
transformer called auto-transformer can be
used
26AUTO TRANSFORMER
- Diagram of a step-up auto-transformer shown in
figure below - C common, SE series
27AUTO TRANSFORMER
- A step-down auto-transformer
- IHISE
- ILISEIC
28AUTO TRANSFORMER
- In step-up autotransformer
- VC / VSE NC / NSE
(1) - NC IC NSE ISE
(2) - voltages in coils are related to terminal
voltages as follows - VLVC
(3) - VHVCVSE
(4) - current in coils are related to terminal
currents - ILICISE
(5) - IHISE
(6)
29AUTO TRANSFORMER
- Voltage Current Relations in Autotransformer
- VHVCVSE
- since VC/VSENC/NSE ? VHVC NSE/NC . VC
- Noting that VLVC ?
- VHVL NSE/NC . VL (NSENC)/NC . VL
- VL / VH NC / (NSENC)
(7) - Current relations
- ILICISE employing Eq.(2) ? IC(NSE / NC)ISE
- IL (NSE / NC)ISE ISE, since ISEIH ?
- IL (NSE / NC)IH IH (NSE NC)/NC .
IH ? - IL / IH (NSE NC)/NC
(8)
30AUTO TRANSFORMER
- Apparent Power Rating Advantage of
Autotransformer - Note not all power transferring from primary to
secondary in autotransformer pass through
windings - Therefore if a conventional transformer be
reconnected as an autotransformer, it can handle
much more power than its original rating - The input apparent power to the step-up
autotransformer is SinVLIL - And the output apparent power is
- SoutVH IH
31AUTO TRANSFORMER
- And
- SinSoutSIO
- Apparent power of transformer windings
- SW VCICVSE ISE
- This apparent power can be reformulated
- SW VCICVL(IL-IH) VLIL-VLIH
- employing Eq.(8) ? SW VLIL-VLIL NC/(NSENC)
- VLIL (NSENC)-NC /(NSENC)SIO NSE
/(NSENC) - SIO / SW (NSENC) / NSE
(9) -
32AUTO TRANSFORMER
- Eq.(9) describes apparent power rating
advantage of autotransformer over a conventional
transformer - smaller the series winding the greater the
advantage - Example one A 5000 kVA autotransformer
connecting a 110 kV system to a 138 kV system has
an NC/NSE of 110/28 - for this autotransformer actual winding rating
is - SWSIO NSE/(NSENC)5000 x 28/ (28110)1015 kVA
- Example Two A 100 VA 120/12 V transformer is
connected as a step-up autotransformer, and
primary voltage of 120 applied to transformer.
33AUTO TRANSFORMER
- (a) what is the secondary voltage of transformer
- (b) what is its maximum voltampere rating in this
- mode of operation
- (c) determine the rating advantage of this
- autotransformer connection over
transformers - rating of conventional 120/12 V operation
- Solution NC/NSE 120/12 (or 101)
- (a) using Eq.(7),VH (12120)/120 x 120 132 V
- (b) maximum VA rating 100 VA?
- ISE,max100/128.33 A
34AUTO TRANSFORMER
- SoutVSISVHIH 132 x 8.33 1100 VA Sin
- (c) rating advantage
- SIO/SW(NSENC)/NSE(12120)/1211 or
- SIO/SW 1100/100 11
- It is not normally possible to reconnect an
ordinary transformer as an autotransformer due to
the fact that insulation of L.V. side may not
withstand full output voltage of autotransformer
connection - Common practice to use autotransformer when two
voltages fairly close - Also used as variable transformers, where L.V.
tap moves up down the winding - Disadvantage direct physical connection between
primary secondary circuits, and electrical
isolation of two sides is lost
35AUTO TRANSFORMER
- Internal Impedance of an Autotransformer
- Another disadvantage effective per unit
impedance of an autotransformer w.r.t. the
related conventional transformer is the
reciprocal of power advantage - This is a disadvantage where the series impedance
is required to limit current flows during power
system faults (S.C.) -
36AUTO TRANSFORMER
- Example three
- A transformer rated 1000 kVA, 12/1.2 kV, 60 Hz
- when used as a two winding conventional
transformer and its series resistance reactance
are 1 and 8 percent per unit - It is used as a 13.2/12 kV autotransformer
- (a) what is now the transformers rating ?
- (b) what is the transformers series impedance
in per unit?
37AUTO TRANSFORMER
- Solution
- (a) NC/NSE 12/1.2 (or 101) the voltage ratio
of autotransformer is 13.2/12 kV VA rating
SIO(110)/1 x 1000 kVA11000 kVA - (b) transformers impedance in per-unit when
connected as conventional transformer - Zeq0.01 j 0.08 pu
- Power advantage of autotransformer is 11, so
its per unit impedance would be - Zeq(0.01j0.08)/110.00091j0.00727 pu
38Example of Variable Auto-Transformer