Title: Ohms Law
1??????????????????????????????
- ???
- ??.???????? ????????
- ???????????????????? ??????????????????????????
- ???????????????????????????????????????????
- ??????????????????????????????????????????????
2Ohms Law
- The Ohms Law states that
- Where
- I Current (Amps)
- V Voltage (Volts)
- R Resistance (Ohms)
-
3Ohms Law
- The formula for Ohms law only apply to ac
circuits that are purely resistive - However, many ac circuits have reactance (X) as
well as resistance measured in ohms - This reactance must be combined with the
resistance to calculate the impedance (Z) and is
also measured in ohms
4Ohms Law
- Therefore,
- The result leads to
5AC Power
- Alternating Current (AC) is an electrical current
that periodically reverse its direction of flow
because the polarity of the voltage source
constantly changes - When an AC circuit is connected to a resistance,
the resulting alternating current follows the
same alternating pattern as the voltage source - This pattern is called a sine wave
6AC Power
- A sine wave cycle is one variation of the sine
wave from zero to maximum, back through zero, to
minimum, and back to zero
7AC Power
- The amplitude of the sine wave is expressed as
either voltage or current - The peak value is the current magnitude between
zero and the highest point of the sine wave for
one-half cycle
8AC Power
- The current at any point on a sine wave is called
the instantaneous current (i) - It is also possible to determine the arithmetic
value of the alternating current - The average value is the arithmetical average of
all values in the sine wave for one-half cycle
9AC Power
- The most common method of measuring the amplitude
of a sine wave is its root-mean-square (rms)
value - RMS is the square root of the average of all the
instantaneous currents squared - The rms value of a sine wave is readily
determined by calculus but can perhaps be more
easily understood by simple arithmetic
10AC Power
- The RMS value is 0.707 times the zero-to-peak
value of the sine wave
11AC Power
12AC Power
13AC Power
- The number of times this cycle occurs in one
second is called frequency and is expressed in
Hertz (Hz) - Another parameter of interests is the length of
time required for the sinusoidal function to pass
through all its possible values
14AC Power
- This time is referred to as the period of the
function and is denoted as T which can be
expressed as - Omega (?) represents the angular frequency of the
sinusoidal function and it is given as
15Frequency
- A cycle per second is referred to as a hertz
- In north America, the frequency is 60 Hz
- However, in other countries may have different
frequencies - In Thailand, the frequency is 50 Hz
16AC Power
- For the pure resistance circuit, both current and
voltage are in the same phase
17AC Power
- For the pure inductance circuit, current lags
voltage with the angle of 90 degree
18AC Power
Where
19AC Power
- For the pure capacitance circuit, current leads
voltage with the angle of 90 degree
20AC Power
Where
21AC Power
- For the series R-L circuit, current lags voltage
with the angle of tan-1?L/R
22Example
Let
Calculate The Voltage
23Example
24AC Power
- For the series R-C circuit, current leads voltage
with the angle of tan-11/?CR
25Example
- A sinusoidal voltage is given by
- Determine
- a) What is the period of the voltage?
- b) What is the frequency in hertz?
- c) What is the magnitude of v at t 2.778 ms
- d) What is the rms value of v
26Example
- Solution
- a) Since ? 100p rad/s
- b)
27Example
Hence
d)
28Phasor Diagram
- A diagram of phasor currents and voltages can be
used to analyze the steady-state sinusoidal
operation of a circuit - A phasor diagram shows the magnitude and phase
angle of each phasor quantity in the
complex-number plane - Phase angle are measured counterclockwise from
the positive real axis and magnitude are measured
from the origin of the axes
29Phasor Diagram
30Phasor Diagram
- For the pure resistance circuit, phasor current
has the same phase (in phase) with the phase
voltage
31Phasor Diagram
- For the series R-L circuit, phasor current lags
the phase voltage with the angle of ? degree
32Phasor Diagram
- For the series R-C circuit, phasor current leads
the phase voltage with the angle of ? degree
33Phasor Diagram
- In this circuit, the parallel combination of R2
and L2 represents a load on the output end of a
distribution line - The distribution line is modeled by the series
combination of R1 and L1
R1
L1
Vs
R2
L2
VL
-
34Phasor Diagram
Ib
- Because we are holding the amplitude of the load
voltage constant, VL is chosen as the reference
R1
j?L1
I
Vs
R2
j?L2
VL
Ia
-
VL
35Phasor Diagram
- We know that Ia is in phase with VL and its
magnitude is - We also know that Ib lag behind VL by 90 degree
and its magnitude is
Ia
VL
VL
Ia
Ib
36Phasor Diagram
- The line current I is equal to the sum of Ia and
Ib - The voltage drop across R1 is in phase with the
line current, and the voltage drop across j?L1
leads the line current by 90 degree
Ia
VL
Ib
I
37Phasor Diagram
- The source voltage is the sum of the load voltage
and the drop along the line
j?L1I
VL
Ia
R1I
Ib
I
38Phasor Diagram
j?L1I
Vs
j?L1I
Ia
VL
R1I
Ib
R1I
I
39Configuration
- Configuration is the number of phases and the
types of connection between the utility and the
user - For the number of phases, they can be
- One Phase
- Two Phases
- Three Phases
40Balanced Three-Phase
- A set of balanced three-phase voltages consists
of three sinusoidal voltages that have identical
amplitudes and frequency but are out of phase
with each other by exactly 120 degree - Because the phase voltages are out of phase by
120 degree, two possible phase relationship can
exist between a-phase voltage and the b- and
c-phase voltage
41Balanced Three-Phase
- One possibility is for the b-phase voltage to lag
the a-phase voltage by 120 degree, in which case
the c-phase voltage must lead the a-phase voltage
by 120 degree - This phase relationship is known as the abc phase
sequence or positive phase sequence
42Balanced Three-Phase
VC
VA
VB
Positive Phase Sequence
43Balanced Three-Phase
- Another possibility is for the b-phase voltage to
lead the a-phase voltage by 120 degree, in which
case the c-phase voltage must lag the a-phase
voltage by 120 degree - This phase relationship is known as acb phase
sequence or negative phase sequence
44Balanced Three-Phase
VB
VA
VC
Negative Phase Sequence
45Configuration
- A three-phase source can be either Wye-connected
or Delta-connected and the three-phase loads can
also be either Wye-connected or Delta-connected
Three-phase Voltage Source
Three-phase Load
Three-phase Line
46Configuration
- Thus, the basic circuit in the above figure can
take four different configurations - Wye-Wye Connection
- Wye-Delta Connection
- Delta-Wye Connection
- Delta-Delta Connection
47Wye-Wye Connection
A Three-Phase Y-Y System
48Wye-Wye Connection
- Zga, Zgb, and Zgc represent the internal
impedance associated with each phase winding of
the voltage source - Z1a, Z1b, and Z1c represent the impedance of each
phase conductor of the line connecting the source
to the load - Zo is the impedance of the neutral conductor that
connects the source neutral to the load neutral - ZA, ZB, and ZC are the impedance of each phase of
load
49Wye-Wye Connection
- The circuit is a balanced three-phase circuit if
it satisfies all the following criteria - Van, Vbn, and Vcn form a set of balanced
three-phase voltages - Zga Zgb Zgc
- Z1a Z1b Z1c
- ZA ZB ZC
50Wye-Wye Connection
- If the system is balanced, VN must be zero
- VN denote the node voltage between nodes N and n
- If VN is zero, there is no difference in
potential between the source neutral, n, and the
load neutral, N - Consequently, the current in the neutral
conductor is zero
51Wye-Wye Connection
- When the system is balanced, three line currents
are
52Wye-Wye Connection
- In a balanced system, the three line currents
form a balanced set of three-phase currents - Thus, the current in each line is equal in
amplitude and frequency and 120 degree out of
phase with the other two line currents - Hence, if the current IaA is calculated, the line
currents IbB and IcC can be obtained without
further computations
53Wye-Wye Connection
- Once the line currents in the circuit are
obtained, calculating any voltages of interest is
relatively simple - Of particular interest is the relationship
between the line-to-line voltages and the
line-to-neutral voltages - Thus, line-to-line voltages at the load terminals
in terms of the line-to-neutral load voltages are
54Wye-Wye Connection
A
VAB
VAN
ZA
B
ZB
N
VCA
VBN
VBC
ZC
VCN
C
Line-to-Line and Line-to-Neutral Voltages
55Wye-Wye Connection
- To show the relationship between the line-to-line
voltages and the line-to-neutral voltages, a
positive phase sequence is assumed and the
line-to-neutral voltage of the a-phase is used as
the reference
56Wye-Wye Connection
VCN
VAN
VBN
Vp is Line-to-Neutral Voltage or Phase Voltage
57Wye-Wye Connection
- From the above equations, it can be concluded
that
58Wye-Wye Connection
- The magnitude of the line-to-line voltage is
times the magnitude of the line-to-neutral
voltage - The line-to-line voltages form a balanced
three-phase set of voltages - The set of line-to-line voltages leads the set of
line-to-neutral voltages by 30 degree
59Wye-Wye Connection
VCN
VAB
VCA
VAN
VBN
VBC
60Wye-Delta Connection
- If the load in a three-phase circuit is connected
in a delta, it can be transformed in to a wye by
using the delta-wye-transformation
61Wye-Delta Connection
Impedance Transformation from Delta-to-Wye
62Wye-Delta Connection
- When the load is balanced, the impedance of each
leg of the wye is one-third the impedance of each
leg of the delta - To determine the relationship between the phase
currents and line currents, a positive phase
sequence is used
63Wye-Delta Connection
A
IaA
IAB
ICA
Z?
Z?
IbB
Z?
C
B
IBC
IcC
Relationship Between Line Currents and Phase
Currents in a Balanced Delta-Load
64Wye-Delta Connection
- The previous figure shows that, in the delta
configuration, the phase voltage is identical to
the line voltage
ICA
IAB
IBC
Ip is the phase current
65Wye-Delta Connection
- The line current in terms of the phase current
can be written by Kirchhoffs law as following
66Wye-Delta Connection
- By comparing the phase current and line current,
it can be concluded that - The magnitude of the line current is times
the magnitude of phase current - The set of line currents lags the set of phase
current by 30 degree - If a negative phase sequence is applied, line
currents are larger than phase currents and
lead the phase current by 30 degree
67Delta-Wye Connection
- In the Delta-Wye three phase circuit, the source
is delta-connected and the load is wye-connected - The analysis of the delta-wye connection can be
achieved by replacing the balanced
delta-connected source with a wye equivalent - The wye equivalent of the source by dividing the
internal phase voltages of the delta-source by
68Delta-Wye Connection
- If the phase sequence is positive, the phase
angle of this set of three-phase voltages is
shifted by the angle of -30 degree - However, in the case of negative sequence, the
phase angle of this set of three-phase voltages
is shifted by the angle of 30 degree - The internal impedance of the wye-equivalent is
one third the internal impedance of the
delta-source
69The Y-equivalent of a balanced, three-phase,
delta-connected source (positive sequence)
70Delta-Wye Connection
- For a positive phase sequence, the set of
delta-source phase current (Iba, Icb, and Iac)
lead the set of line currents IaA, IbB, and IcC)
by 30 degree - For a negative phase sequence, the phase currents
in the source lag the line currents by 30 degree - The magnitude of the phase current is times
the magnitude of the line current
71Delta-Delta Connection
- In the delta-delta circuit, both source and load
are delta-connected - By replacing both source and load with their
wye-equivalent, the analysis of delta-delta
connection can be achieved -
72Configuration
- Wye Connection
- Delta Connection
73Example
- A three-phase, positive sequence, Y-connected
generator has an impedance of 0.2 j0.5
ohm/phase. The internal phase voltage of the
generator is 120 V. The generator feeds a
balanced, three-phase, Y-connected load having an
impedance of 39 j28 ohm/phase. - The impedance of line connecting the generator to
the load is 0.8 j1.5 ohm/phase. - The a-phase voltage of the generator is specified
as the reference phasor
74Example
- Calculate
- a) Line currents (IaA, IbB, and IcC)
- b) Line-to-Neutral voltages at the load (VAN,
VBN, VCN) - c) Line voltages at load (VAB, VBC, VCA)
75Example
IaA
a
A
0.2 O
j0.5 O
0.8 O
j1.5 O
39 O
j28 O
N
76- Solution
- a) The a-phase line current
IcC
IaA
IbB
For positive sequence
77- b) The line-to-neutral voltages at load
VCN
For positive sequence
VAN
VBN
78- c) The line-to-line voltages at load
- For a positive sequence, the line-to-line
voltages lead the line-to-neutral voltages by 30
degree
VAB
VCN
VCA
VAN
VBN
VBC
79Configuration
- For the number of connections, they can be
- Two-wire connections
- Three-wire connections
- Four-wire connections
- Five-wire connections
- The electrical system between the generating
source and the customers site is known as the
distribution system
80Configuration
- The wiring between the connection to the
distribution system at the customers site and
the equipment to be powered is called the
premises wiring (system) - The various loads that the electrical system is
required to power have certain characteristics
which affect the amount of power (watts) that is
demanded by these loads
81Configuration
- These characteristics are
- Resistance
- Inductance
- Capacitance
- Inductance and capacitance cause a difference
between the real power and the apparent power
required by the load in an AC circuit
82Premises Wiring (System)
Branch Circuits
Distribution System
Main Feeder
Feeder
Loads
Medium Voltage Supply
Equipment Loads
Main Electrical Service Panel
Pole or Pad-mounted Transformer
Meter
Feeder Panel or Sub-Panel
Receptacles or Hard-wired
Building Service Transformer (if Required)
83Capacity
- The capacity of a given system is the amperage
- This can be also be stated in volt-amperes (VA)
or watts (W) - Generally, in an AC circuit, the product of the
measured rms value of the current and the
measured rms value of the voltage equals the
volt-amperes
84Real and Reactive Power
- The VA product is only the Apparent power of
the circuit
VA
VAR
Phase Angle
W
85Real and Reactive Power
- To determine real or true power, one must know
the amount (phase angle) the current leads or
lags the voltage - Real power associates with the purely resistive
- This phase angle can vary from 90 degree leading
in a purely capacitive circuit through 0 degree
in a purely resistive circuit, to 90 degree
lagging in a purely inductive circuit
86Real and Reactive Power
Where
87Real and Reactive Power
- VAR (volt-amperes reactive) is defined two
meanings - The power absorbed by the reactive part of the
load - The power delivered by the capacitive part of the
load - Thus, VAR is simply referred as reactive power
88Real and Reactive Power
Where
RF is Reactive Factor
89Example
- An electrical load operates at 220 V, 15 A, and
power factor 0.8. Calculate the real and
reactive power. - Solution
- Load VA 22015 3300 VA
- PF 0.8, cos? 0.8, ? 36.87o
3300 VA
Q
W
90Example
- Real power
- Reactive power
91Watthours
- Watts indicate the amount of power that is
consumed by a circuit at any given time - Typically, utility companies charge for power in
kilowatt-hours (kWh) - Hence, multiplying the number of watts consumed
by the number of hours that the watts are being
consumed produces watt-hours
92Example
- ?????????????????????????????? (????????? 3
??????????????, ?????? 22 ?????????)
???????????????????????????????? TOU
??????????????????????????????????????????????? - ????????????????????
- On-Peak (?????? - ????? 09.00 - 22.00 ?.) 850 kW
- Off-Peak 1 (?????? - ????? 22.00 09.00 ?.) 600
kW - Off-Peak 2 (????? - ???????, ?????????????) 500
kW
93Example
- ????????????????
- On-Peak (?????? - ????? 09.00 - 22.00 ?.) 40,000
????? - Off-Peak 1 (?????? - ????? 22.00 09.00
?.) 35,000 ????? - Off-Peak 2 (????? ???????, ?????????????) 25,000
????? - ?????????????
- ??????????????????????? 74.14 ???/?????????
- ??????????????? (Peak) 2.695 ???/?????
94Example
- ??????????????? (Off-Peak) 1.1914 ???/?????
- ????????? 228.17 ???/?????
- ?????????????? 0.4328 ???/?????
- Solution
- ??????????????????????? 85074.17 63,044.50
??? - ??????????????? (400002.695)(350001.1914)(25
0001.1914) - 172,586.19 ???
95Example
- ?????????????? 1000000.4328 43,280 ???
- ????????? 228.17 ???
- ??? (1) 279,138.86 ???
- ?????????????????? (7) (279138.36)(0.07)
19,539.72 - ?????????????????? 298,678.58 ???
96Complex power
- For circuit operating in sinusoidal-steady-state,
real and reactive power conveniently calculated
from complex power - Complex power is the complex sum of real power
and reactive power which can be defined as
97Complex power
- Where
- S is Apparent Power (VA)
- P is Real Power (W)
- Q is Reactive power (VAR)
98Complex power
- Thus, the apparent, real and reactive power in
three-phase system are calculated as following - In form of phase value
Vp is Line-to-Neutral Voltage or Phase Voltage
99Complex power
VL is Line-to-Line Voltage
100Example
- The wye source with the rating of 100 kVA and 380
V (line) supplies power the wye load. Load has a
operating power factor of 0.8 lagging. Calculate - Phase voltage at load
- Phase current at load
- Real power at load
- Reactive power at load
101Example
102Example
103Example
104Power Factor
- Power factor is defined as the ratio of the real
power to the apparent power - Power factor will be leading or lagging
depending on which way the load shifts the
currents phase with respect to the voltages
phase - Inductive loads cause current to lag behind
voltage, while capacitive loads cause current to
lead voltage
105Power Factor
- From the power triangle, the following equations
can be expressed
S (VA)
Q (VAR)
W
106Example
- An electrical load operates at 240 V rms. The
load absorbs an average power of 8 kW at a
lagging power factor of 0.8. Calculate the
complex power of the load. - Solution
- Since the power factor is described as lagging,
it indicates that the load is inductive
107Example
S
Q
P
108Example
- A 50 kW fully-loaded motor is operating at 595
volts, 3-phase drawing 88 A. Determine operating
power factor. - Solution
88 A
S
Q
Voltage Source 595 V, 3 phase
Motor 50 kW
P 50 kW
109Example
Since motor is three-phase motor, thus the
apparent power is calculated from
Then, operating power can be calculated by
110Example
- Alternatively, operating power factor can be
calculated in just one step as following
111Power Factor
- Low power factor results in
- Power loss in the network
- Higher transformer losses
- Increased voltage drop in power distribution
networks - Less power distributed via the network
- Increasing peak kVA
112Power Factor Correction
- Power factor improvement can be obtained by
adding capacitor into the system - Capacitors produces the necessary leading
reactive power to compensate the lagging reactive
power
113Power Factor Correction
VA1
VAR1
VA2
VAR2
W
Where Cos ?1 is power factor before power
factor correction Cos ?2 is power factor after
power factor correction VAR1 is reactive power
before power factor correction VAR2 is reactive
power after power factor correction
114Power Factor Correction
- Calculation Method
- Suppose the power factor of both before and after
power factor correction are known - Thus
115Power Factor Correction
Therefore, the required VAR can be calculated
from
116Power Factor Correction
- Where to connect capacitor on the customers
electrical system? - Connect all together at any point past the
utility metering (usually at the service entrance
switchgear) - Divide the total capacitor requirement in
selected amounts and connect to the system about
the load center of the feeder
117Power Factor Correction
- Connect the capacitors as close to the loads,
with which they will be trading VARs, as possible - If a system or part of a system operates with a
varying load, then connect the capacitors through
a series of steps with each step switched
through a contactor that is controlled by power
factor controller
118Example
- Suppose a factory currently has a peak demand at
1250 kW with the operating power factor of 0.65.
If this factory needs to improve its power factor
to 0.95, calculate the require capacitor size. - Solution
VA1
VAR1
PF1 0.65
1250 kW
Before Improving Power Factor
119Example
Before Improving Power Factor
After Improving Power Factor
VA2
VAR2
1250 kW
120Example
121Example
- Suppose capacitor bank with a capacity of 50 kVar
is designed for rated 240 V and 60 Hz. If this
capacitor is applied for rated 220 V and 50 Hz,
what is the actual capacity of this capacitor
bank?
122Example
123Example
124Transformer
- A schematic represents of a two-winding
transformer with the phasor voltages E1 and E2
across the windings
125Transformer
- From figure the phasor current I1 entering
winding 1, which has N1 turns - The phasor current I2 entering winding 2, which
has N2 turns - Ohms law for the magnetic circuit states that
the net magnetomotive force (mmf) equals the
product of core reluctance (Rc) and the core flux
(?)
126Transformer
- For an ideal transformer, core is assumed to have
infinite permeability, therefore, the core
reluctance is zero
127Transformer
- By applying the Faradays law, voltage at the
primary side can be calculated as - Assuming a sinusoidal-steady-state flux with
constant frequency and replacing e(t) and
by E and ?
128Transformer
- Similarly, the voltage at secondary side is given
as - Therefore,
129Transformer
- Turn ratio (a) is defined as follows
- Hence, the basic relation for an ideal
single-phase two-winding transformers are
130Transformer
- Two additional relations concerning complex power
and impedance can be also derived - The complex power entering winding 1
131Transformer
- If an impedance Z2 is connected across winding 2
of the ideal transformer, then - This impedance, when measured from winding 1, is
132Example
- A single-phase two-winding transformer is rated
20 kVA, 480/120 V, 60 Hz. A source connected to
the 480-V winding supplies an impedance load
connected to the 120-V winding. - The load absorbs 15 kVA at 0.8 p.f. lagging when
the load voltage is 118 V. Assume that the
transformer is an ideal. Calculate - a) The voltage across the 480-V winding
- b) The load impedance
- c) The load impedance referred to the 480-V
winding
133Example
Selecting the load voltage E2 as the reference
134Example
S2 15 kVA
VAR
P
135Example
- a) Turn Ratio
- The voltage across winding 1
136Example
- b)
- Therefore,
- The load impedance is calculated from
137Example
- c) The load impedance referred to the 480-V
winding can be calculated by -
138Per-Unit System
- In power system a normalization of variable
called per unit normalization is almost always
used - It is especially convenient if many transformers
and voltage levels are involved - One advantage of the per-unit system is to avoid
the possibility of making serious calculation
errors when referring quantities from one side of
a transformer to the other
139Per-Unit System
- The basic idea is to pick base values for
quantities such as voltages, currents,
impedances, and power - Hence, the quantity in per unit is defined as the
ratio of actual quantity to the base value
quantity
140Per-Unit System
141Per-Unit System
142Per-Unit System
Per Unit Value
143Per-Unit System
- When only one component, such as a transformer,
is considered, the nameplate ratings of that
component are usually selected as base values - When several components are involved, the system
base values may be different from the nameplate
ratings of any particular device - It is then necessary to convert the per-unit
impedance of a device from the old base to new
base values
144Per-Unit System
- To convert a per-unit impedance from old to
new base use
145Example
- Three zones of a single-phase circuit are
connected by transformers T1 and T2 whose ratings
are shown in figure. By using base values of 30
kVA and 240 V in zone 1 - a) Draw the per-unit circuit and determine the
per unit impedances and per-unit source voltage - b) Calculate load current in both in per-unit and
in amperes -
146Example
- Solution
- a) First the base values in each zone are
determined. - For base kVA will be 30 kVA for the entire
network
Zone 1
Zone 2
Zone 3
Xline 2 O
Zload 0.9 j 0.2 O
30 kVA, 240/480 volts X0.1 pu
20 kVA, 460/115 volts X0.1 pu
147Example
- Thus
- For base voltage in zone 1
- As moving across a transformer, the voltage base
is changed to the transformer voltage ratings,
hence
148Example
- For base voltage in zone 3
- The base impedance in zone 2 and 3 are
149Example
- The base current in zone 3 is calculated from
- Per-unit reactance of Transformer 1 is then
calculated from
150Example
- Per-unit reactance of line in zone 2 can be
calculated from - Per-unit reactance of transformer 2 must be
converted from its nameplate rating to the system
base (Vb2)
151Example
- Alternatively, use Vb3
- Load in zone 3 has a per-unit impedance of
152Example
- Finally, the per-unit source voltage is
calculated from
Xpu(line)j0.2604 pu
Xpu(T1)j0.1 pu
Xpu(T2)j0.1378 pu
Zpu(load) 1.875j0.4167 pu
Vpu(source) 0.9167
153Example
- The per-unit load current is then simply
calculated from per-unit circuit
154Example
- The actual load current is