Title: The IFC, The IBC and E Occupancies
1The IFC, The IBCand E Occupancies
2International Fire Code Intent
- The purpose of this code is to establish the
minimum requirements consistent with nationally
recognized good practice for providing a
reasonable level of life safety and property
protection from the hazards of fire, explosion or
dangerous conditions in new and existing
buildings, structures and premises and to provide
safety to fire fighters and emergency responders
during emergency conditions.
3International Building Code Intent
- The purpose of this code is to establish the
minimum requirements to safeguard the public
health, safety and general welfare through
structural strength, means of egress
facilitiesand safety to life and property from
fire and other hazards attributed to the built
environment and to provide safety to fire
fighters and emergency responders during
emergency operations.
4Chapter One
5IFC Section 106 Inspections
- 106.3 Concealed work. Whenever any installation
subject to inspections prior to use is covered or
concealed without having first been inspected,
the fire code official shall have the authority
to require that such work be exposed for
inspection.
6IBC Section 109 Inspections
- To be accessible and exposed until approved
- - Footings and Foundations
- - Concrete slab and underfloor areas
- - Lowest floor elevations (flood zones)
- - Framing
- - Lath and gypsum board inspections
7IBC Inspections Continued
- - Fire-resistive penetrations
- - Energy efficiency inspections
- - Other inspections required by building
official. - - Special Inspections
- - Final Inspection
8IFC Section 107 Maintenance
- Whenever or wherever any device, equipment,
system, condition, arrangement, level of
protection, or any other feature is required for
compliance with the provisions of this code, or
otherwise installed, such deviceshall thereafter
by continuously maintained in accordance with
this code and applicable referenced standards.
9Maintenance Contd
- Testing and operation of equipment
- Test and inspection records
- Re-inspection and testing
- Supervision
- Rendering equipment inoperable.
- Owner/occupant responsibility
- Overcrowding
10Chapter 3
- General Fire Precautions
- Use Occupancy Classification
11IFC Section 304Combustible Waste Material
- - Not allowed to accumulate in buildings or upon
the premises. Includes spaces underneath
grandstands and bleacher seats. - - Storage not to create a nuisance or hazard.
- - Oily rags to be stored in listed, disposal
container with tight fitting lid and contents
disposed of daily.
12IFC Section 3 Contd
- Dumpsters and containers with an individual
capacity of 1.5 cubic yard or more shall not be
stored in buildings or placed within 5 feet of
combustible walls, openings or combustible roof
eave lines.
13IFC Section 308Open Burning Recreational Fires
- General A person shall not kindle or maintain
or authorize to be kindled or maintained any open
burning unless conducted and approved in
accordance with this section. - Permit required.
- Authorization from Division of Air Quality
- Location-not less than 50 feet from any structure.
14IFC Section 308 Open Flames
- A person shall not utilize or allow to be
utilized, an open flame in connection with a
public meeting or gathering for purposes of
deliberation, worship, entertainment, amusement,
instruction, education, recreation, without fire
obtaining a permit. - Candles shall not be located on or near
combustible materials
15Section 313 Fueled Equipment
- Fueled equipment including but not limited to
lawn-care equipment shall not be stored,
operated or repaired within a building. - Exception A building or room constructed
for such use in accordance with the IBC. - - 313.1.1 Authorizes the fire code official to
require removal of fueled equipment from
locations deemed hazardous.
16IFC Section 314 Indoor Displays
- Displays of highly combustible goods, including
but not limited toagricultural goods, are
prohibited in main exit access aisles, corridors
or within 5 feet of entrances to exits and
exterior exit doors when a fire involving such
goods would rapidly prevent or obstruct egress.
17Indoor Displays Contd
- Vehicles
- 1. Disconnect battery
- 2. ¼ tank of fuel or 5 gallons, which ever
is less. - 3. Fuel tanks and fill openings are closed
and sealed to prevent tampering. - 4. Vehicles are not fueled or de-fueled
within the building.
18IFC Section 315 MiscellaneousCombustible
Materials Storage
- Storage in buildings shall be orderly. Storage
shall be separated from heat sources. - Clearance from ceilings, 18 inches in sprinklered
buildings, 24 inches in non-sprinklered
buildings. - No storage in means of egress, exits or exit
enclosures. - No storage in boiler rooms, electrical or
mechanical equipment rooms.
19Incidental and AccessoryUse Areas
- Areas or spaces that are subordinate and
secondary to the structures primary function. - Limited in size
- May or may not require separation
20(No Transcript)
21IBC Section 302.1.1.1Separation
- Where Table 302.1.1 permits an automatic
fire-extinguishing system without a fire barrier,
the incidental use area shall be separated by
construction capable of resisting the passage of
smoke.
22Chapter 4
- Emergency Planning
- Special Detailed Requirements Based on Use
23IFC Section 404Fire Safety and Evacuation Plan
- Emergency egress or escape routes
- Procedures for employees who must remain to
operate critical equipment before evacuating - Procedures for accounting for occupants and
employees after evacuation has been completed
24Section 404 Contd
- Identification and assignment of personnel
responsible for rescue or emergency medical aid - The preferred and any alternative means of
notifying occupants of a fire or emergency - The preferred and any alternative means of
reporting fires and other emergencies to the
authorities
25Section 404 Contd
- Identification and assignment of personnel who
can be contacted for further information or
explanation of duties under the plan - A description of the emergency voice/alarm
communication system alert tone and preprogrammed
voice messages, where provided
26IFC Section 404.3.2Fire Safety Plans
- The procedure for reporting a fire or other
emergency - The life safety strategy and procedures for
notifying, relocating, or evacuating occupants - Site plans indicating
- a. The occupancy assembly point
- b. The location of fire hydrants
- c. Access routes for vehicles
27Section 404.3.2 Contd
- Floor plans identifying
- a. Exits
- b. Primary and secondary evacuation routes
- c. Accessible egress routes and areas of
refuge. - d. Pull stations
- e. Fire extinguishers
- f. Fire alarm annunciators and controls
28Section 404.3.2 Contd
- A list of major fire hazards
- Identification of personnel responsible for
maintenance of systems and equipment installed to
prevent or control fires - Identification of personnel responsible for
maintenance, housekeeping and controlling fuel
hazard sources
29IFC Section 405Emergency Evacuation Drills
- Emergency evacuation drills shall be conducted
monthly in elementary schools. - Emergency evacuation drills shall be conducted at
least every two months in secondary schools for a
total of four drills in nine months. The first
drill shall be conducted within the first two
weeks of the school year.
30IFC Section 408.3Emergency Evacuation Drills
- First drill of each school year shall be
conducted within the first 10 days. - Emergency drills shall be conducted at different
times of the day - Outdoor assembly areas shall be designated and
shall be located a safe distance from the
building. - Shall provide accountability
31IBC Section 410.1Stages and Platforms
- Stage is a space within a building utilized for
entertainment which includes overhead hanging
curtains, drops, scenery or stage effects. - To be called a stage the area must measure 1000
sq. ft. in floor area and 50 ft. in height.
32Stages Platforms Contd
- Section 410.5.2 - Dressing rooms, scene docks,
property rooms, workshops, storerooms and
compartments appurtenant to the stage shall be
separated from each other by fire barrier wall
and horizontal assemblies, or both, with not less
than a 1-hour fire-resistance rating with
protected openings.
33Stages Platforms Contd
- An automatic sprinkler system is required for
stages that are 1,000 square feet in floor area
and 50 feet in height. - Standpipes are required on stages 1,000 square
feet in area and 50 feet in height. - At least one exit from each side of stage is
required
34Spray Finishing Areas
- Spray booths, areas and rooms shall be protected
by a sprinkler system - Construct of materials that allow cleaning
- Filters shall be changed often
- Sprinkler heads are to be protected
- Light fixtures and exposed electrical wiring
shall be explosion proof
35Chapter 5
- Fire Service Features
- General Building Heights and Areas
36IFC Section 504Access To Building Openings
- Required exterior doors and openings shall be
maintained readily accessible for emergency
access by the fire department. - Required exterior doors for fire department
access shall not be eliminated without prior
approval and shall not be obstructed
37Section 505Premises Identification
- New and existing buildings shall have approved
address numbers, placed in a position that is
plainly legible and visible from the street or
road fronting the property
38IFC Section 507Hazards to Fire Fighters
- Trapdoors and scuttle covers shall be kept closed
at all times except when in use or are
automatically operated. - Outside opening accessible to the Fire department
and which open on a hoistway or shaftway
communicating between two or more floors shall be
plainly marked in red letters, 6 inches high, on
white background
39Hazards to Fire Fighters Contd
- Door or window openings to a hoistway or shaftway
from the interior of the building shall be
plainly marked. - The intentional design or alteration of buildings
to disable, injure, maim or kill intruders is
prohibited
40IFC Section 508Fire Protection Water Supplies
- Fire hydrant systems shall be subject to periodic
tests and shall be maintained in an operative
condition at all times and shall be repaired
where defective. - A 3-foot clear space shall be maintained around
the circumference of a fire hydrant. - Bollards shall be provided when needed
41IFC 510FD Access to Equipment
- Fire protection equipment shall be identified in
an approved manner. Rooms containing
controlsshall be identified for fire department
use. Signs shall be permanently installed,
readily visible and durable.
42IBC Chapter 5General Building Heights and Areas
- Numbers or addresses shall be provided for new
buildings in such a position as to be clearly
visible and legible from the street fronting the
property.
43Chapter 6
- Building Services Systems
- Types of Construction
44IFC Section 605 ElectricalEquipment Wiring
Hazards
- Identified electrical hazards shall be abated.
Electrical wiring, devices, appliances and other
equipment that is modified or damaged and
constitutes and electrical shock or fire hazard
shall not be used - Illumination shall be provided for service
equipment areas, motor control centers and
electrical panals.
45Electrical Equipment, Wiring and Hazards Contd
- A working space of not less than 30 inches in
width, 36 inches in depth and 78 inches in height
shall be provided in front of electrical
equipment. - Doors into electrical control panel rooms shall
be marked with a sign stating ELECTRICAL ROOM. - Electrical panals shall be labeled.
46Electrical Hazards Contd
- Multiplug adaptors shall comply with the NEC or
are prohibited. - Relocatable power taps shall be polarized or
grounded, equipped with overcurrent protection
and be listed. They shall be directly connected
to a permanently installed receptacle. - Shall not extend through floors, walls, etc.
47Electrical Hazards Contd
- Extension Cords shall not be used as permanent
wiring, shall not be affixed to structures,
extended through walls, ceilings or floors, under
doors or floor coverings and shall not be
subjected to damage. - Extension cords shall be used only with portable
appliances.
48Electrical Hazards Contd
- Extension cords shall be plugged directly into a
receptacle - The ampacity of the cord shall not be less than
the rated capacity of the appliance being served. - Maintained in good conditon
- Extension cord shall be grounded when serving
grounded appliances
49Electrical Hazards Contd
- Open junction boxes and open-wiring splices are
prohibited - Electrical appliances and fixtures shall be
tested and listed - Temporary wiring for electrical power and
lighting is allowed for a period not to exceed 90
days.
50IBC Chapter 6
51Chapter 7
- Fire-Resistance-Rated Construction
52Section 705 Fire Walls
- Create two separate buildings
- Must provide same level of structural integrity
and independence as an exterior wall - Under fire conditions-must remain intact to 2
hours if one or the other side collapses. - Has minimum fire-rating of 2 hours
- Continuous from footings to parapet
53Section 706 Fire Barrier
- Used for separating exits, incidental use areas,
shafts, and fire areas. - Fire barriers cannot terminated at the ceiling
- Areas separated with a fire barriers are not
considered separate buildings - Openings are limited to 25 of wall space
54708 Fire Partitions
- Wall assemblies that enclose an exit access
corridor - Openings are not limited but must be protected
- Extend from the top of the floor assembly to the
fire-resistance-rated floor/ceiling or
roof/ceiling assembly
55Section 712 Penetrations
- Penetrations through fire-resistance-rated
assemblies shall be protected to maintain the
integrity of the hourly rating. - Each type of penetration requires a specific
method of protection based on the type of
assembly that is penetrated and the type of
penetrating item.
56712 Penetrations Contd
- If sleeves are used, the space between the sleeve
and the penetrating item as well as the space
between the sleeve and the assembly shall be
protected. - Insulation and coverings on or in the penetrating
item shall not penetrate the assembly unless
tested by ASTM
57712 Penetrations Contd
- In a masonry wall, mortar or cement may be used.
- Tape and sheetrock mud does not produce a
fire-resistance rating around pipe, conduit, etc. - UL Directories, Factory Mutual and others provide
accepted, listed methods and materials.
58Chapter 8
59IFC Interior Finish, Decorative Materials
Furnishing
- Furnishing or decorations of an explosive or
highly flammable character shall not be used. - Fire-retardant coatings shall be maintained so as
to retain the effectiveness of the treatment
under service conditions encountered in actual
use.
60Interior Finishes Contd
- Furnishings or other objects shall not be placed
to obstruct exits, exit access or egress or
visibility
61IFC Section 803.3.1Storage in corridors and
lobbies
- Clothing and personal effects shall not be stored
in corridors and lobbies - Exceptions
- - Corridors protected by an -automatic
sprinkler system - - Corridors protected by an approved
smoke detection system - - Storage in metal lockers
62803.3.2 Artwork in Corridors
- Artwork and teaching materials shall be limited
on the walls of corridors to not more than 20
percent of the wall area.
63IFC Section 804Decorative Vegetation
- Natural cut trees allowed in sprinklered
buildings only. - Support device should hold the tree securely and
be sized large enough so the tree wont fall over - 2-day supply of water
- When full, water shall cover tree stem at least
2-inches, check daily
64Decorative Vegetation Contd
- Check daily for dryness-discard when needles are
dry, brittle, and fall off easily when shaken - Do not obstruct required width of means of egress
- Do not use candles or open flame near tree and
keep a distance from heat source
65Decorative Vegetation
- Use lights that are listed
- Live vegetation shall be flame-retardant treated
(SFMO) - Artificial vegetation shall e flame resistance
or flame retardant treated with documentation - Use lights that are listed on artificial
vegetation - No lights on metal trees
66IBC Interior Finishes
- Purpose This chapter contains the performance
requirements for controlling fire growth within
buildings by restricting interior finish
materials and decorations.
67IBC Section 805 Decorations Trim
- Curtains, draperies, hangings and other
decorative materials suspended from walls or
ceilings shall be flame resistant or
noncombustible. - Noncombustible decorative materials shall not be
limited
68Decorations Trim Contd
- The amount of flame-resistant decorative material
shall not exceed 10 of the aggregate area of
walls and ceilings. - Foam plastics basically cannot be used. Has to
be covered by thermal barrier or subjects to
rigorous testing
69Chapter 9
70IFC Section 901
- Fire Protection Systems shall be maintained
- Non-required systems shall meet the requirements
of the IBC and the IFC - Any device that has the appearance of life safety
or fire protection equipment but does not perform
as such shall be prohibited
71Fire Protection Systems Contd
- It shall be unlawful to occupy any portion of a
building or structure until the required fire
detection, alarm and suppression systems have
been tested and approved - Fire Protection Systems shall be operational at
all times and shall be repaired or replaced when
defective
72Fire Protection Systems Contd
- Records of all system inspections, tests and
maintenance required by referenced standards
shall be maintained on the premises for three
years and made available to the code official
73Fire Protection Systems Contd
- Systems Out of Service When systems are out of
service, notify the fire department and the code
official. When required by the code official,
the building shall be evacuated or a fire watch
provided - Fire watch shall have at least one method to
notify the fire department, the fire watch is the
only duty
74Fire Protection Systems Contd
- Any system or portion of a system that is out of
service shall be tagged indicating exactly what
has been identified as a problem - If a system is planned to be taken out of
service, a Preplanned Impairment Program is
required
75Fire Protection Systems Contd
- An Impairment Program requires
- The extent expected duration
- Evaluate the risk to the area or building
- Recommendations have been submitted to the
building owner - Notify the Fire Department
76Impairment Plan Contd
- Notify the insurance carrier, the alarm
monitoring company, building owner and code
official - Notify supervisors in affected area
- Place the impairment tag on system
- Assemble necessary tools and materials
77Fire Protection Contd
- Emergency Impairment
- During unplanned impairments, appropriate actions
shall be take to minimize potential injury and
damage. - Implement steps of a Preplanned Impairment Program
78Fire Protection Systems Contd
- Restoring systems to service
- Perform inspections and testing to verify proper
operation of system - Advise supervisors that system is restored
- Advise Fire Department of restoration
79Fire Protection Systems Contd
- Advise building owner, alarm company, insurance
carrier and other interested parties of
restoration - Remove impairment tag
80Fire Protection Systems Contd
- Removal or Tampering with Equipment
- It is unlawful for any person to remove, tamper
with or otherwise disturb any fire hydrant, fire
detection and alarm system, suppression system or
other fire appliance
81Sprinkler System
- In E occupancies
- A sprinkler system is required throughout all
fire areas greater than 20,000 sq. ft. - Throughout all portions of building below the
level of exit discharge unless every classroom
throughout has exterior door at ground level
82Sprinkler System Contd
- Sprinklers are required in spray finishing areas,
booths or rooms. - Existing buildings
- Sprinklers can provide a reasonable degree of
safety in existing structures not complying with
the minimum requirements of the IBC
83Hood Suppression System
- A hood suppression system is required over
kitchen equipment which produces smoke and grease
laden vapors or grease of appreciable depth (1/4
inch)
84Hood Systems Contd
- Shall meet the requirement of UL 300
- Automatic and manual operation
- System interconnection for fuel and power shutoff
- Requires K-type extinguisher within 30 feet of
the appliances
85Hood System Contd
- Ventilation system required with specific rate of
air movement - Classified grease filters shall be in place when
grease hood is in use - Clean regularly to prevent accumulation of
grease, records of cleaning are to be kept on
premises - Service every 6 months Certificate of
Inspection shall go to code official
86Standpipes
- Class III standpipes are required on each side of
a stage. - Shall be equipped with a 1.5 inch and a 2.5 inch
hose connection - Hose and cabinet shall have sufficient length of
1.5 inch hose to protect the entire state area
87Portable Fire Extinguisher
- Required as required by NFPA 10 but can be
limited to special hazard areas if the building
is equipped throughout with quick-response
sprinklers - Required within 30 feet of commercial cooking
equipment - Required where flammable or combustible liquids
are stored, used or dispensed
88Portable Fire Extinguishers Contd
- Required in special hazard areas including
laboratories, computer rooms, and generator
rooms, where required by the fire code official - Located in conspicuous locations in the normal
path of travel - Not obstructed or clearly marked
- Mounted not more that 5-feet above the floor
89Fire Alarm Systems
- Required in schools with an occupant load over 50
- No pull stations at exits if building is equipped
with a sprinkler system - Visual and audible appliances
- Duct detectors connected to fire alarm system,
access provided - Monitored off site
90Fire Department Connections
- Located on street side of buildings, fully
visible and recognizable from street - Existing buildings-Wherever a FDC is not visible,
a sign shall be mounted on street side indicating
FDC location. Letters FDC shall be 6-inches
high. Words shall be 2-inches high
91Chapter 10
92IFC IBC Section 1001General
- Every building and portion thereof shall be
provided with a means of egress system - It shall be unlawful to alter a building or
structure in a manner that will reduce the
required number of exits - Means of egress systems shall be maintained in
accordance with the IFC
93Section 1003.6
- Clear path of egress travel
- Obstructions shall not be placed in the required
width of a means of egress - The required capacity of a means of egress system
shall not be diminished along the path of egress
travel
94Section 1016 Corridors
- Minimum corridor width shall not be less than 44
inches. - In group E - Required width of 6-feet where the
capacity is 100 or more. - Required width of 3-feet where the capacity is
less than 50
95Section 1006Means of Egress Illumination
- The means of egress, including the exit
discharge, shall be illuminated at all times the
building is occupied
96Section 1006.3Illumination Emergency Power
- In the event of a power failure, an emergency
electrical system shall automatically illuminate - Exit access corridors, passageways and aisles in
rooms with two exits - Exit stairways
- Exterior egress components at othe than the level
of exit discharge
97Emergency Illumination Contd
- Interior exit discharge elements in buildings
required to have two or more exits - The portion of the exterior exit discharge
immediately adjacent to exit discharge doorways
in buildings required to have two or more exits. - Emergency power system shall provide power for 90
minutes
98Section 1011 Exit Signs
- Exits and exit access doors shall be marked by
and approved exit sign readily visible from any
direction of egress travel - Exit sign placement shall be such that no point
in an exit access corridor is more than 100 feet
from the nearest visible exit sign
99Exit Signs Continued
- Shall be illuminated at all times
- May be internally or externally illuminated
- Shall be connected to an emergency power system,
battery or generator - Shall remain illuminated not less than 90 minutes
after a power outage
100Section 1008 Doors
- Means of egress doors shall be easily
recognizable as doors and shall not be concealed
by curtains, drapes, decorations or similar
materials - Minimum clear width of a door is 32 inches of
clear opening between the face of the door and
the stop when the door is open 90 degrees
101Doors Continued
- Egress doors shall be side-hinged swinging.
- Doors shall swing in the direction of egress
travel where serving an occupant load of 50 - In Group E with an occupant load of 100 or more a
door shall not be provided with a latch or lock
unless it is panic hardware or fire exit hardware
102Doors Continued
- Egress door shall be readily openable without the
use of a key or special knowledge or effort - Doors in rated corridors shall be automatic or
self closing
103Doors Continued
- Manually operated flush bolts or surface bolts
are not permitted - Exception
- The inactive leaf on a pair of doors serving
storage or equipment rooms - Gates serving in the means of egress system shall
comply with the requirements of doors
104Doors Continued
- Where two or more doors are required, they shall
remain clear and unobstructed