The IFC, The IBC and E Occupancies - PowerPoint PPT Presentation

1 / 104
About This Presentation
Title:

The IFC, The IBC and E Occupancies

Description:

The purpose of this code is to establish the minimum requirements consistent ... person shall not kindle or maintain or authorize to be kindled or maintained any ... – PowerPoint PPT presentation

Number of Views:353
Avg rating:3.0/5.0
Slides: 105
Provided by: deannem
Category:
Tags: ibc | ifc | kindle | occupancies

less

Transcript and Presenter's Notes

Title: The IFC, The IBC and E Occupancies


1
The IFC, The IBCand E Occupancies
2
International Fire Code Intent
  • The purpose of this code is to establish the
    minimum requirements consistent with nationally
    recognized good practice for providing a
    reasonable level of life safety and property
    protection from the hazards of fire, explosion or
    dangerous conditions in new and existing
    buildings, structures and premises and to provide
    safety to fire fighters and emergency responders
    during emergency conditions.

3
International Building Code Intent
  • The purpose of this code is to establish the
    minimum requirements to safeguard the public
    health, safety and general welfare through
    structural strength, means of egress
    facilitiesand safety to life and property from
    fire and other hazards attributed to the built
    environment and to provide safety to fire
    fighters and emergency responders during
    emergency operations.

4
Chapter One
  • Administrative

5
IFC Section 106 Inspections
  • 106.3 Concealed work. Whenever any installation
    subject to inspections prior to use is covered or
    concealed without having first been inspected,
    the fire code official shall have the authority
    to require that such work be exposed for
    inspection.

6
IBC Section 109 Inspections
  • To be accessible and exposed until approved
  • - Footings and Foundations
  • - Concrete slab and underfloor areas
  • - Lowest floor elevations (flood zones)
  • - Framing
  • - Lath and gypsum board inspections

7
IBC Inspections Continued
  • - Fire-resistive penetrations
  • - Energy efficiency inspections
  • - Other inspections required by building
    official.
  • - Special Inspections
  • - Final Inspection

8
IFC Section 107 Maintenance
  • Whenever or wherever any device, equipment,
    system, condition, arrangement, level of
    protection, or any other feature is required for
    compliance with the provisions of this code, or
    otherwise installed, such deviceshall thereafter
    by continuously maintained in accordance with
    this code and applicable referenced standards.

9
Maintenance Contd
  • Testing and operation of equipment
  • Test and inspection records
  • Re-inspection and testing
  • Supervision
  • Rendering equipment inoperable.
  • Owner/occupant responsibility
  • Overcrowding

10
Chapter 3
  • General Fire Precautions
  • Use Occupancy Classification

11
IFC Section 304Combustible Waste Material
  • - Not allowed to accumulate in buildings or upon
    the premises. Includes spaces underneath
    grandstands and bleacher seats.
  • - Storage not to create a nuisance or hazard.
  • - Oily rags to be stored in listed, disposal
    container with tight fitting lid and contents
    disposed of daily.

12
IFC Section 3 Contd
  • Dumpsters and containers with an individual
    capacity of 1.5 cubic yard or more shall not be
    stored in buildings or placed within 5 feet of
    combustible walls, openings or combustible roof
    eave lines.

13
IFC Section 308Open Burning Recreational Fires
  • General A person shall not kindle or maintain
    or authorize to be kindled or maintained any open
    burning unless conducted and approved in
    accordance with this section.
  • Permit required.
  • Authorization from Division of Air Quality
  • Location-not less than 50 feet from any structure.

14
IFC Section 308 Open Flames
  • A person shall not utilize or allow to be
    utilized, an open flame in connection with a
    public meeting or gathering for purposes of
    deliberation, worship, entertainment, amusement,
    instruction, education, recreation, without fire
    obtaining a permit.
  • Candles shall not be located on or near
    combustible materials

15
Section 313 Fueled Equipment
  • Fueled equipment including but not limited to
    lawn-care equipment shall not be stored,
    operated or repaired within a building.
  • Exception A building or room constructed
    for such use in accordance with the IBC.
  • - 313.1.1 Authorizes the fire code official to
    require removal of fueled equipment from
    locations deemed hazardous.

16
IFC Section 314 Indoor Displays
  • Displays of highly combustible goods, including
    but not limited toagricultural goods, are
    prohibited in main exit access aisles, corridors
    or within 5 feet of entrances to exits and
    exterior exit doors when a fire involving such
    goods would rapidly prevent or obstruct egress.

17
Indoor Displays Contd
  • Vehicles
  • 1. Disconnect battery
  • 2. ¼ tank of fuel or 5 gallons, which ever
    is less.
  • 3. Fuel tanks and fill openings are closed
    and sealed to prevent tampering.
  • 4. Vehicles are not fueled or de-fueled
    within the building.

18
IFC Section 315 MiscellaneousCombustible
Materials Storage
  • Storage in buildings shall be orderly. Storage
    shall be separated from heat sources.
  • Clearance from ceilings, 18 inches in sprinklered
    buildings, 24 inches in non-sprinklered
    buildings.
  • No storage in means of egress, exits or exit
    enclosures.
  • No storage in boiler rooms, electrical or
    mechanical equipment rooms.

19
Incidental and AccessoryUse Areas
  • Areas or spaces that are subordinate and
    secondary to the structures primary function.
  • Limited in size
  • May or may not require separation

20
(No Transcript)
21
IBC Section 302.1.1.1Separation
  • Where Table 302.1.1 permits an automatic
    fire-extinguishing system without a fire barrier,
    the incidental use area shall be separated by
    construction capable of resisting the passage of
    smoke.

22
Chapter 4
  • Emergency Planning
  • Special Detailed Requirements Based on Use

23
IFC Section 404Fire Safety and Evacuation Plan
  • Emergency egress or escape routes
  • Procedures for employees who must remain to
    operate critical equipment before evacuating
  • Procedures for accounting for occupants and
    employees after evacuation has been completed

24
Section 404 Contd
  • Identification and assignment of personnel
    responsible for rescue or emergency medical aid
  • The preferred and any alternative means of
    notifying occupants of a fire or emergency
  • The preferred and any alternative means of
    reporting fires and other emergencies to the
    authorities

25
Section 404 Contd
  • Identification and assignment of personnel who
    can be contacted for further information or
    explanation of duties under the plan
  • A description of the emergency voice/alarm
    communication system alert tone and preprogrammed
    voice messages, where provided

26
IFC Section 404.3.2Fire Safety Plans
  • The procedure for reporting a fire or other
    emergency
  • The life safety strategy and procedures for
    notifying, relocating, or evacuating occupants
  • Site plans indicating
  • a. The occupancy assembly point
  • b. The location of fire hydrants
  • c. Access routes for vehicles

27
Section 404.3.2 Contd
  • Floor plans identifying
  • a. Exits
  • b. Primary and secondary evacuation routes
  • c. Accessible egress routes and areas of
    refuge.
  • d. Pull stations
  • e. Fire extinguishers
  • f. Fire alarm annunciators and controls

28
Section 404.3.2 Contd
  • A list of major fire hazards
  • Identification of personnel responsible for
    maintenance of systems and equipment installed to
    prevent or control fires
  • Identification of personnel responsible for
    maintenance, housekeeping and controlling fuel
    hazard sources

29
IFC Section 405Emergency Evacuation Drills
  • Emergency evacuation drills shall be conducted
    monthly in elementary schools.
  • Emergency evacuation drills shall be conducted at
    least every two months in secondary schools for a
    total of four drills in nine months. The first
    drill shall be conducted within the first two
    weeks of the school year.

30
IFC Section 408.3Emergency Evacuation Drills
  • First drill of each school year shall be
    conducted within the first 10 days.
  • Emergency drills shall be conducted at different
    times of the day
  • Outdoor assembly areas shall be designated and
    shall be located a safe distance from the
    building.
  • Shall provide accountability

31
IBC Section 410.1Stages and Platforms
  • Stage is a space within a building utilized for
    entertainment which includes overhead hanging
    curtains, drops, scenery or stage effects.
  • To be called a stage the area must measure 1000
    sq. ft. in floor area and 50 ft. in height.

32
Stages Platforms Contd
  • Section 410.5.2 - Dressing rooms, scene docks,
    property rooms, workshops, storerooms and
    compartments appurtenant to the stage shall be
    separated from each other by fire barrier wall
    and horizontal assemblies, or both, with not less
    than a 1-hour fire-resistance rating with
    protected openings.

33
Stages Platforms Contd
  • An automatic sprinkler system is required for
    stages that are 1,000 square feet in floor area
    and 50 feet in height.
  • Standpipes are required on stages 1,000 square
    feet in area and 50 feet in height.
  • At least one exit from each side of stage is
    required

34
Spray Finishing Areas
  • Spray booths, areas and rooms shall be protected
    by a sprinkler system
  • Construct of materials that allow cleaning
  • Filters shall be changed often
  • Sprinkler heads are to be protected
  • Light fixtures and exposed electrical wiring
    shall be explosion proof

35
Chapter 5
  • Fire Service Features
  • General Building Heights and Areas

36
IFC Section 504Access To Building Openings
  • Required exterior doors and openings shall be
    maintained readily accessible for emergency
    access by the fire department.
  • Required exterior doors for fire department
    access shall not be eliminated without prior
    approval and shall not be obstructed

37
Section 505Premises Identification
  • New and existing buildings shall have approved
    address numbers, placed in a position that is
    plainly legible and visible from the street or
    road fronting the property

38
IFC Section 507Hazards to Fire Fighters
  • Trapdoors and scuttle covers shall be kept closed
    at all times except when in use or are
    automatically operated.
  • Outside opening accessible to the Fire department
    and which open on a hoistway or shaftway
    communicating between two or more floors shall be
    plainly marked in red letters, 6 inches high, on
    white background

39
Hazards to Fire Fighters Contd
  • Door or window openings to a hoistway or shaftway
    from the interior of the building shall be
    plainly marked.
  • The intentional design or alteration of buildings
    to disable, injure, maim or kill intruders is
    prohibited

40
IFC Section 508Fire Protection Water Supplies
  • Fire hydrant systems shall be subject to periodic
    tests and shall be maintained in an operative
    condition at all times and shall be repaired
    where defective.
  • A 3-foot clear space shall be maintained around
    the circumference of a fire hydrant.
  • Bollards shall be provided when needed

41
IFC 510FD Access to Equipment
  • Fire protection equipment shall be identified in
    an approved manner. Rooms containing
    controlsshall be identified for fire department
    use. Signs shall be permanently installed,
    readily visible and durable.

42
IBC Chapter 5General Building Heights and Areas
  • Numbers or addresses shall be provided for new
    buildings in such a position as to be clearly
    visible and legible from the street fronting the
    property.

43
Chapter 6
  • Building Services Systems
  • Types of Construction

44
IFC Section 605 ElectricalEquipment Wiring
Hazards
  • Identified electrical hazards shall be abated.
    Electrical wiring, devices, appliances and other
    equipment that is modified or damaged and
    constitutes and electrical shock or fire hazard
    shall not be used
  • Illumination shall be provided for service
    equipment areas, motor control centers and
    electrical panals.

45
Electrical Equipment, Wiring and Hazards Contd
  • A working space of not less than 30 inches in
    width, 36 inches in depth and 78 inches in height
    shall be provided in front of electrical
    equipment.
  • Doors into electrical control panel rooms shall
    be marked with a sign stating ELECTRICAL ROOM.
  • Electrical panals shall be labeled.

46
Electrical Hazards Contd
  • Multiplug adaptors shall comply with the NEC or
    are prohibited.
  • Relocatable power taps shall be polarized or
    grounded, equipped with overcurrent protection
    and be listed. They shall be directly connected
    to a permanently installed receptacle.
  • Shall not extend through floors, walls, etc.

47
Electrical Hazards Contd
  • Extension Cords shall not be used as permanent
    wiring, shall not be affixed to structures,
    extended through walls, ceilings or floors, under
    doors or floor coverings and shall not be
    subjected to damage.
  • Extension cords shall be used only with portable
    appliances.

48
Electrical Hazards Contd
  • Extension cords shall be plugged directly into a
    receptacle
  • The ampacity of the cord shall not be less than
    the rated capacity of the appliance being served.
  • Maintained in good conditon
  • Extension cord shall be grounded when serving
    grounded appliances

49
Electrical Hazards Contd
  • Open junction boxes and open-wiring splices are
    prohibited
  • Electrical appliances and fixtures shall be
    tested and listed
  • Temporary wiring for electrical power and
    lighting is allowed for a period not to exceed 90
    days.

50
IBC Chapter 6
  • Types of Construction

51
Chapter 7
  • Fire-Resistance-Rated Construction

52
Section 705 Fire Walls
  • Create two separate buildings
  • Must provide same level of structural integrity
    and independence as an exterior wall
  • Under fire conditions-must remain intact to 2
    hours if one or the other side collapses.
  • Has minimum fire-rating of 2 hours
  • Continuous from footings to parapet

53
Section 706 Fire Barrier
  • Used for separating exits, incidental use areas,
    shafts, and fire areas.
  • Fire barriers cannot terminated at the ceiling
  • Areas separated with a fire barriers are not
    considered separate buildings
  • Openings are limited to 25 of wall space

54
708 Fire Partitions
  • Wall assemblies that enclose an exit access
    corridor
  • Openings are not limited but must be protected
  • Extend from the top of the floor assembly to the
    fire-resistance-rated floor/ceiling or
    roof/ceiling assembly

55
Section 712 Penetrations
  • Penetrations through fire-resistance-rated
    assemblies shall be protected to maintain the
    integrity of the hourly rating.
  • Each type of penetration requires a specific
    method of protection based on the type of
    assembly that is penetrated and the type of
    penetrating item.

56
712 Penetrations Contd
  • If sleeves are used, the space between the sleeve
    and the penetrating item as well as the space
    between the sleeve and the assembly shall be
    protected.
  • Insulation and coverings on or in the penetrating
    item shall not penetrate the assembly unless
    tested by ASTM

57
712 Penetrations Contd
  • In a masonry wall, mortar or cement may be used.
  • Tape and sheetrock mud does not produce a
    fire-resistance rating around pipe, conduit, etc.
  • UL Directories, Factory Mutual and others provide
    accepted, listed methods and materials.

58
Chapter 8
  • Interior Finishes

59
IFC Interior Finish, Decorative Materials
Furnishing
  • Furnishing or decorations of an explosive or
    highly flammable character shall not be used.
  • Fire-retardant coatings shall be maintained so as
    to retain the effectiveness of the treatment
    under service conditions encountered in actual
    use.

60
Interior Finishes Contd
  • Furnishings or other objects shall not be placed
    to obstruct exits, exit access or egress or
    visibility

61
IFC Section 803.3.1Storage in corridors and
lobbies
  • Clothing and personal effects shall not be stored
    in corridors and lobbies
  • Exceptions
  • - Corridors protected by an -automatic
    sprinkler system
  • - Corridors protected by an approved
    smoke detection system
  • - Storage in metal lockers

62
803.3.2 Artwork in Corridors
  • Artwork and teaching materials shall be limited
    on the walls of corridors to not more than 20
    percent of the wall area.

63
IFC Section 804Decorative Vegetation
  • Natural cut trees allowed in sprinklered
    buildings only.
  • Support device should hold the tree securely and
    be sized large enough so the tree wont fall over
  • 2-day supply of water
  • When full, water shall cover tree stem at least
    2-inches, check daily

64
Decorative Vegetation Contd
  • Check daily for dryness-discard when needles are
    dry, brittle, and fall off easily when shaken
  • Do not obstruct required width of means of egress
  • Do not use candles or open flame near tree and
    keep a distance from heat source

65
Decorative Vegetation
  • Use lights that are listed
  • Live vegetation shall be flame-retardant treated
    (SFMO)
  • Artificial vegetation shall e flame resistance
    or flame retardant treated with documentation
  • Use lights that are listed on artificial
    vegetation
  • No lights on metal trees

66
IBC Interior Finishes
  • Purpose This chapter contains the performance
    requirements for controlling fire growth within
    buildings by restricting interior finish
    materials and decorations.

67
IBC Section 805 Decorations Trim
  • Curtains, draperies, hangings and other
    decorative materials suspended from walls or
    ceilings shall be flame resistant or
    noncombustible.
  • Noncombustible decorative materials shall not be
    limited

68
Decorations Trim Contd
  • The amount of flame-resistant decorative material
    shall not exceed 10 of the aggregate area of
    walls and ceilings.
  • Foam plastics basically cannot be used. Has to
    be covered by thermal barrier or subjects to
    rigorous testing

69
Chapter 9
  • Fire Protection Systems

70
IFC Section 901
  • Fire Protection Systems shall be maintained
  • Non-required systems shall meet the requirements
    of the IBC and the IFC
  • Any device that has the appearance of life safety
    or fire protection equipment but does not perform
    as such shall be prohibited

71
Fire Protection Systems Contd
  • It shall be unlawful to occupy any portion of a
    building or structure until the required fire
    detection, alarm and suppression systems have
    been tested and approved
  • Fire Protection Systems shall be operational at
    all times and shall be repaired or replaced when
    defective

72
Fire Protection Systems Contd
  • Records of all system inspections, tests and
    maintenance required by referenced standards
    shall be maintained on the premises for three
    years and made available to the code official

73
Fire Protection Systems Contd
  • Systems Out of Service When systems are out of
    service, notify the fire department and the code
    official. When required by the code official,
    the building shall be evacuated or a fire watch
    provided
  • Fire watch shall have at least one method to
    notify the fire department, the fire watch is the
    only duty

74
Fire Protection Systems Contd
  • Any system or portion of a system that is out of
    service shall be tagged indicating exactly what
    has been identified as a problem
  • If a system is planned to be taken out of
    service, a Preplanned Impairment Program is
    required

75
Fire Protection Systems Contd
  • An Impairment Program requires
  • The extent expected duration
  • Evaluate the risk to the area or building
  • Recommendations have been submitted to the
    building owner
  • Notify the Fire Department

76
Impairment Plan Contd
  • Notify the insurance carrier, the alarm
    monitoring company, building owner and code
    official
  • Notify supervisors in affected area
  • Place the impairment tag on system
  • Assemble necessary tools and materials

77
Fire Protection Contd
  • Emergency Impairment
  • During unplanned impairments, appropriate actions
    shall be take to minimize potential injury and
    damage.
  • Implement steps of a Preplanned Impairment Program

78
Fire Protection Systems Contd
  • Restoring systems to service
  • Perform inspections and testing to verify proper
    operation of system
  • Advise supervisors that system is restored
  • Advise Fire Department of restoration

79
Fire Protection Systems Contd
  • Advise building owner, alarm company, insurance
    carrier and other interested parties of
    restoration
  • Remove impairment tag

80
Fire Protection Systems Contd
  • Removal or Tampering with Equipment
  • It is unlawful for any person to remove, tamper
    with or otherwise disturb any fire hydrant, fire
    detection and alarm system, suppression system or
    other fire appliance

81
Sprinkler System
  • In E occupancies
  • A sprinkler system is required throughout all
    fire areas greater than 20,000 sq. ft.
  • Throughout all portions of building below the
    level of exit discharge unless every classroom
    throughout has exterior door at ground level

82
Sprinkler System Contd
  • Sprinklers are required in spray finishing areas,
    booths or rooms.
  • Existing buildings
  • Sprinklers can provide a reasonable degree of
    safety in existing structures not complying with
    the minimum requirements of the IBC

83
Hood Suppression System
  • A hood suppression system is required over
    kitchen equipment which produces smoke and grease
    laden vapors or grease of appreciable depth (1/4
    inch)

84
Hood Systems Contd
  • Shall meet the requirement of UL 300
  • Automatic and manual operation
  • System interconnection for fuel and power shutoff
  • Requires K-type extinguisher within 30 feet of
    the appliances

85
Hood System Contd
  • Ventilation system required with specific rate of
    air movement
  • Classified grease filters shall be in place when
    grease hood is in use
  • Clean regularly to prevent accumulation of
    grease, records of cleaning are to be kept on
    premises
  • Service every 6 months Certificate of
    Inspection shall go to code official

86
Standpipes
  • Class III standpipes are required on each side of
    a stage.
  • Shall be equipped with a 1.5 inch and a 2.5 inch
    hose connection
  • Hose and cabinet shall have sufficient length of
    1.5 inch hose to protect the entire state area

87
Portable Fire Extinguisher
  • Required as required by NFPA 10 but can be
    limited to special hazard areas if the building
    is equipped throughout with quick-response
    sprinklers
  • Required within 30 feet of commercial cooking
    equipment
  • Required where flammable or combustible liquids
    are stored, used or dispensed

88
Portable Fire Extinguishers Contd
  • Required in special hazard areas including
    laboratories, computer rooms, and generator
    rooms, where required by the fire code official
  • Located in conspicuous locations in the normal
    path of travel
  • Not obstructed or clearly marked
  • Mounted not more that 5-feet above the floor

89
Fire Alarm Systems
  • Required in schools with an occupant load over 50
  • No pull stations at exits if building is equipped
    with a sprinkler system
  • Visual and audible appliances
  • Duct detectors connected to fire alarm system,
    access provided
  • Monitored off site

90
Fire Department Connections
  • Located on street side of buildings, fully
    visible and recognizable from street
  • Existing buildings-Wherever a FDC is not visible,
    a sign shall be mounted on street side indicating
    FDC location. Letters FDC shall be 6-inches
    high. Words shall be 2-inches high

91
Chapter 10
  • Means of Egress

92
IFC IBC Section 1001General
  • Every building and portion thereof shall be
    provided with a means of egress system
  • It shall be unlawful to alter a building or
    structure in a manner that will reduce the
    required number of exits
  • Means of egress systems shall be maintained in
    accordance with the IFC

93
Section 1003.6
  • Clear path of egress travel
  • Obstructions shall not be placed in the required
    width of a means of egress
  • The required capacity of a means of egress system
    shall not be diminished along the path of egress
    travel

94
Section 1016 Corridors
  • Minimum corridor width shall not be less than 44
    inches.
  • In group E - Required width of 6-feet where the
    capacity is 100 or more.
  • Required width of 3-feet where the capacity is
    less than 50

95
Section 1006Means of Egress Illumination
  • The means of egress, including the exit
    discharge, shall be illuminated at all times the
    building is occupied

96
Section 1006.3Illumination Emergency Power
  • In the event of a power failure, an emergency
    electrical system shall automatically illuminate
  • Exit access corridors, passageways and aisles in
    rooms with two exits
  • Exit stairways
  • Exterior egress components at othe than the level
    of exit discharge

97
Emergency Illumination Contd
  • Interior exit discharge elements in buildings
    required to have two or more exits
  • The portion of the exterior exit discharge
    immediately adjacent to exit discharge doorways
    in buildings required to have two or more exits.
  • Emergency power system shall provide power for 90
    minutes

98
Section 1011 Exit Signs
  • Exits and exit access doors shall be marked by
    and approved exit sign readily visible from any
    direction of egress travel
  • Exit sign placement shall be such that no point
    in an exit access corridor is more than 100 feet
    from the nearest visible exit sign

99
Exit Signs Continued
  • Shall be illuminated at all times
  • May be internally or externally illuminated
  • Shall be connected to an emergency power system,
    battery or generator
  • Shall remain illuminated not less than 90 minutes
    after a power outage

100
Section 1008 Doors
  • Means of egress doors shall be easily
    recognizable as doors and shall not be concealed
    by curtains, drapes, decorations or similar
    materials
  • Minimum clear width of a door is 32 inches of
    clear opening between the face of the door and
    the stop when the door is open 90 degrees

101
Doors Continued
  • Egress doors shall be side-hinged swinging.
  • Doors shall swing in the direction of egress
    travel where serving an occupant load of 50
  • In Group E with an occupant load of 100 or more a
    door shall not be provided with a latch or lock
    unless it is panic hardware or fire exit hardware

102
Doors Continued
  • Egress door shall be readily openable without the
    use of a key or special knowledge or effort
  • Doors in rated corridors shall be automatic or
    self closing

103
Doors Continued
  • Manually operated flush bolts or surface bolts
    are not permitted
  • Exception
  • The inactive leaf on a pair of doors serving
    storage or equipment rooms
  • Gates serving in the means of egress system shall
    comply with the requirements of doors

104
Doors Continued
  • Where two or more doors are required, they shall
    remain clear and unobstructed
Write a Comment
User Comments (0)
About PowerShow.com