Title: IBC 2006 Chapter 3 Use
1IBC 2006 - Chapter 3 Use Occupancy
Classification
2Equivalent Risk
- How to maintain the same level of safety with a
wide variety of occupancies and construction
types - Originates with property protection
- Primary Goal Life Safety
3Use and Occupancy Classification (302.1)
- Based on what the structure or portion of the
structure is being used for - If a space is occupied at different times for
different purposes, it must comply with all of
the requirements for each purpose
4Assembly Group (303.1)
- Structure, building or portions of used for the
gatherings for the purposes such as civic,
social, religious, recreational functions, the
consumption of food or drink, or waiting areas - Exceptions
- Building lt 50 occupants Group B
- Room/Space lt 50 occupants Group B
- Room/Space lt 750 sq. ft. and Accessory- Group B
or part of Occupancy
5Assembly Group A-1
- Performing arts or motion pictures usually fixed
seating - Concert Halls and Theaters
- Motion Pictures Theaters
- TV and Radio Studios admitting audience
6Assembly Group A-2
- Food and/or drink consumption
- Banquet halls
- Night Clubs
- Restaurants
- Taverns and bars
7Assembly Group A-3
- Worship, recreation, amusement and other uses not
classified elsewhere - Art galleries, exhibition hall and museums
- Amusement arcades
- Bowling alleys
- Churches
- Courtroom
- Lecture halls
- Libraries
- Indoor sports areas (no spectators)
- Dance and Community halls
8Assembly Group A-4
- Indoor sporting events with spectators
- Arenas
- Skating rinks
- Swimming pools
- Tennis courts
9Assembly Group A-5
- Participation or viewing outdoor sports
- Amusement park structures
- Bleachers
- Grandstands
- Stadiums
10Business Group B (304.1)
- Office, professional or service-type transactions
- Animal Hospitals
- Banks
- Barber shops, beauty shops
- Clinic - outpatient
- Dry cleaning and laundries pick up/delivery
- Post offices
11Business Group
- Laboratories
- Professional services
- Print shops
- Motor vehicle showrooms
- Clinics - outpatient
- Radio/TV stations
- Car wash
- Educational occupancies above 12th grade
12Educational Group E (305.1)
- Used for educational purposes by 6 or more
persons over 2 ½ years of age through the 12th
Grade - Day care (305.2)
- Education, supervision, or personal care
- More than 5 children
- Older than 2 ½ years old
13Educational Group E Exceptions
- Religious educational rooms accessory to a church
with an occupant load of less than 100 are an A-3
occupancy - Child care facility more than 5 and less than 100
children (308.5.2) - 2 ½ years old and under
- All rooms with these children require exit doors
directly to exterior at the level of exit
discharge
14Factory Group F (306.1)
- Assembling, dissembling, fabricating, finishing,
manufacturing, packaging, repair or processing
operations not classified as Group H or Group S - F-1 Moderate hazard
- F-2 Low hazard
15Factory Group F-1 (306.2)Moderate hazard
- Aircraft
- Appliances
- Automobiles
- Bakeries
- Beverages (gt12 alcohol)
- Boats
- Broom or brushes
- Clothing
- Dry cleaning plants
- Cameras
- Canvas
- Electronics
- Furniture
- Machinery
- Millwork
- Musical instruments
- Optical goods
- Paper mills or products
- Photographic film
- Printing publishing
- Plastics
- RVs
- Refuse incineration
- Shoes
- Soaps
- Textiles
- Tobacco
- Trailers
- Upholstering
- Woodworking (cabinet)
16Factory Group F-2 (306.3)Low hazard
- Beverages (12 alcohol or less)
- Brick and masonry
- Ceramic products
- Foundries
- Glass products
- Gypsum
- Ice
- Metal products (fabrication and assembly)
17High Hazard Group (307.1)
- Manufacturing, processing, generation or storage
of materials quantities in excess of those in
Table 307.7(1) and (2) that are a physical or
health hazard. - Exceptions 15 total
- Control areas
- Wholesale and retail sales and storage per IFC
- Batteries for emergency power
- Cleaning establishments liquid solvents gt200F
- Liquor stores without bulk storage
18High Hazard Group H-1 (307.3)Detonation hazard
- Explosives
- Organic peroxides, unclassified detonable
- Class 4 oxidizers
- Detonable pyrophoric material
- Unstable (reactive) material
19High Hazard Group H-2 (307.4)Deflagration,
accelerated burning hazard
- Class I, II, IIIA flammable or combustible
liquids - Combustible dusts
- Cryogenic liquids, flammable
- Flammable gases
- Organic peroxides, Class I
- Oxidizers, Class 3
- Pyrophoric liquids, solids and gases non
detonable - Unstable reactive material, Class 3, nondetonable
- Water reactive materials, Class 3
20High Hazard Group H-3 (307.5)Readily support
combustion
- Class I, II, IIIA liquids lt 15 psi
- Combustible fibers
- Consumer fireworks
- Cryogenic liquids, oxidizing
- Flammable solids
- Organic peroxides, Class II and III
- Oxidizers, Class 2
- Oxidizers, Class 3 lt 15 psi
- Oxidizing gases
- Unstable reactive material, Class 2
- Water reactive materials, Class 2
21High Hazard Group H-4 (307.6)Health Hazards
- Corrosives
- Highly toxic materials
- Toxic materials
22High Hazard Group H-5 (307.7)Semiconductor
fabrication facilities
- Semiconductor fabrication facilities or
comparable research development - Where hazardous production materials (HPM) used
in quantities in excess of Table 307.7(1) and
307.7(2) - Must be designed according to Section 415.8
Group H5 (special use and occupancy)
23Institutional Group I (308.1)
- For the care or supervision of people having
physical limitations due to health or age are
harbored for medical treatment or other care or
treatment or - In which occupants are detained for penal or
correctional purposes or - Where the liberty of the occupants are restricted
24Institutional Group I-1 (308.2)
- Housing for more than 16 persons on a 24 hour
basis who due to age, mental disability or other
reasons live in a supervised residential
environment but can respond to emergency
situations without physical assistance. - Residential board and care facilities
- Assisted living facilities
- Halfway houses, group homes
- Congregate care facilities
- Social rehabilitation, alcohol and drug centers
25Institutional Group I-1 (308.2)Exceptions
- 6 to 16 persons Classified R-4
- 5 or fewer persons Classified R-3
26Institutional Group I-2 (308.3)
- Medical, surgical, psychiatric, nursing,
custodial care facilities for over 5 persons who
are not capable of self preservation. - Hospitals
- Nursing homes
- Mental hospitals
- Child care on 24 hour basis for more than 5
children under age 2 ½ years of age (308.3.1)
27Institutional Group I-3 (308.4)
- Restraint facilities or security facilities for
more than 5 persons. - Prisons and Jails
- Reformatories
- Detention Centers
- Correctional Centers
- Pre-release Centers
28Institutional Group I-3Conditions
- Condition 1 Free movement allowed throughout
permitted to be considered Group R - Condition 2 Free interior movement, locked exits
- Condition 3 Free movement within a compartment
Egress with remote release - Condition 4 Restricted movement within
compartments remote control release within
compartments and egress - Condition 5 Restricted movement within
compartments Staff controlled manual release
within compartments and egress.
29Institutional Group I-4 (308.5)
- Day Care facilities (for over 5 persons)
- Any Age
- Adult care (A-3 if capable of self preservation)
- Child care under 2 ½ years of age
- Receive custodial care for less than 24 hours
- Does not include places of worship during
religious functions
30Mercantile Group M (309.1)
- Display and sale of merchandise involving stocks
of goods accessible to the public - Department stores
- Drug Stores
- Markets
- Motor fuel stations
- Retail or wholesale stores
- Sales rooms
31Residential Group R (310.1)
- Used for sleeping purposes not classified as
Group I or per IRC - R-1 Multi-unit transient
- R-2 Multi-unit non transient
- R-3 Not classified elsewhere
- R-4 Residential care
32Residential Group R-1
- Occupants are primarily transient in nature (not
more than 30 days) - Hotels
- Boarding Houses
- Motels
33Residential Group R-2
- More than 2 dwelling units per building where
occupants are primarily permanent - Apartments
- Boarding houses (not transient)
- Convents
- Dormitories
- Fraternities or Sororities
- Hotels and Motels (not transient)
- Monasteries
34Residential Group R-3
- Not more than 2 dwelling units per building, not
classified as R-1, R-2, R-4 or I, where occupants
are more permanent - Houses
- Duplex units
- Adult and child day care (less than 24 hours)
with not more than 5 occupants
35Residential Group R-4
- Residential care/assisted living
- 6-16 residents, excluding staff
- 24 hour per day basis
- Greater than 16 residents classified I-1
- Fewer than 6 residents classified R-3
36Storage Group S (311.1)
- For storage not classified as hazardous occupancy
- S-1 Moderate hazard storage
- S-2 Low hazard storage
37Storage Group S-1 (311.2) Moderate hazard storage
- Aerosols, Level 2 and 3
- Aircraft repair hangers
- Bags, burlap, cloth, paper
- Bamboo, rattan, baskets, belts, canvas, leather
- Books, boots, shoes buttons, cardboard, clothing,
wool, furniture, glues, grains, horns, combs,
linoleum, lumber - Motor vehicle repair garage (maximum quantities
of hazardous materials) - Silks, soaps, tires, tobacco, upholstery, wax
candles
38Storage Group S-2 (311.3) Low hazard storage
- Aircraft hanger
- Beverages (up to 12 alcohol) in metal, ceramic
or glass containers - Cement in bags
- Chalk crayons
- Dairy products (in non-waxed coated paper
containers) - Dry cell batteries
- Electrical coils and motors
- Empty cans
- Food products
- Food (noncombustible containers)
- Glass bottles
- Gypsum board
- Meats
- Metals and metal parts
- Mirrors
- Porcelain
- Stoves
- Talc and soap stones
- Washer or dryers
- Parking garages, open and enclosed.
39Utilities and MiscellaneousGroup U (312.1)
- Accessory and miscellaneous structures not
classified in other occupancies - Agriculture buildings
- Aircraft hangers accessory to one or two family
dwellings - Barns
- Carports
- Fences over 6 feet high and retaining walls
- Grain silos accessory to residential occupancy
- Greenhouses
- Livestock shelters
- Private garages
- Sheds
- Tanks and Towers
40New for 2006
- Moves all provisions for Mixed Uses to Ch. 5
- Adds Training and skill development not within a
school or academic program to Group B - Classifies congregate living facilities with lt16
occupants as R-3 - Clarifies that any amount of hazardous material
is regulated by section 414 and IFC
41Questions?
42(No Transcript)
43IBC 2006 - Chapter 4 Special Detailed
Requirements Based on Use Occupancy
44Introduction
- Contains requirements for specific types of
buildings and occupancies - Typically supplemental to other code provisions
- Building Types Malls, High Rises and Parking
Garages - Building Areas Atriums, Stages, Group I and
Group H
45Special Detailed Requirements
- Covered Malls
- High-Rise
- Atriums
- Underground Buildings
- Motor-Vehicle-Related
- Group I-2 I-3
- Motion Picture Projection Rooms
- Stages Platforms
- Special Amusement
- Aircraft-Related
- Hazardous Materials
- Application of Flammable Finishes
- Drying Rooms
- Organic Coatings
- Group I-1, R-1, R-2, R-3
- Hydrogen Cutoff Rooms
46Covered Mall Buildings (402)
- A building three stories or less enclosing two or
more tenants with access to a covered common
pedestrian area - Typically a shopping center but provisions have
been used for airports and offices - Does not include Anchor Building
47Covered Mall Buildings
- Unlimited area
- Construction Types I, II, III, IV
- Fully Sprinklered
- Mall independently of tenants and anchors
- Mall, anchor stores and attached parking
surrounded by 60 feet of open space and - Anchor stores less than 3 stories
- Anchor Stores over 3 stories per Sec. 503
- Parking Garages always per Sec. 406
48Covered Mall Buildings
- Kiosks (temporary or permanent) (402.10)
- Limited combustible construction
- Horizontal separation - 20 foot minimum
- Size 300 ft2 maximum
- Childrens playground structures (402.11)
- Limited combustible construction
- Horizontal separation - 20 foot minimum
- Size 300 ft2 maximum
49High-Rise Buildings (403.1)
- Highest occupied floor over 75 feet above lowest
level of fire department access - Not always noted on plans
- Not readily apparent from exterior
50High-Rise Buildings (403.1)
- Highest occupied floor over 75 feet above lowest
level of fire department access - Not always noted on plans
- Not readily apparent from exterior
51High-Rise Buildings
- Reduction in Construction Type
- Less than 420 feet Type IA to IB
- Other than F-1, M, S-1 Type IB to IIA
- Fire Command Center per 911
- Standby and Emergency Power
52Atriums (404)
- Opening connection two or more stories other than
enclosed stairways, elevators, hoistways,
escalators, or MEP equipment and not a covered
mall - Use of floor area
- Enclosure
- Smoke control
53Motor-Vehicle-Related (406)
- Private garages and carports (406.1)
- Open parking garage (406.3)
- Openings area and perimeter (406.3.3.1)
- Special area and height (406.3.5)
- Enclosed parking garage (406.4)
- Height and area Table 503
- Mechanical Ventilation
- Fuel-dispensing facilities canopies (406.5)
- Repair garages (406.6)
54Group I-2 (407)
- Hospitals and Nursing Homes
- Corridor walls Smoke Partitions
- Smoke barriers stories w/ sleeping or treatment
rooms or lt 50 occupants - Refuge area and independent egress
- Egress to secured yard gt 50 feet from building
55Groups I-1, R-1, R-2, R-3
- Dwelling Unit separation walls and horizontal
separation - 1 hour required
- ½ hour in IIB, IIIB, VB with NFPA 13
56New for 2006
- Adds childrens playground structure
- Adds 420 foot high rise limitations
- Requires doors between garages and dwelling units
to be self-closing - Removes specific limitation on number of control
areas for Group M and S
57Questions?
58IBC 2006 Chapter 5 General Building Heights
Areas
59Building Heights and Areas
- Table 503 Tabular values
- Allowable height and area depends on
- Group
- Type construction
- Overall size is based on the specific fuel load
and fire hazard associated with both the
occupancy and the materials used to construct the
building
60Table 503Allowable Height and Building Areas
61Building Heights and Areas
- Height from the grade plane.
- Maximum number of stories applies only to stories
above grade. - A basement is a story above grade plane when the
finished surface of the floor above the basement
is - More than 6 feet (1829 mm) above grade plane
- More than 12 feet (3658 mm) above the finished
ground level at any point.
62Building Heights and Areas
- Buildings on the same lot (503.1.2)
- Separate buildings
- Portions of the same building
63Height Modifications (504)
- Sprinklers (504.2)
- NPFA 13 (903.1.1) increase of 20 feet and 1
story. - NFPA 13R (903.3.1.2) Group R-1, R-2, and R-4
Buildings increase of 20 feet and 1 story
increase can not exceed four stories or 60
feet. - NFPA 13D (903.3.1.3) Group R-3 increase of 20
feet and 1 story increase can not exceed four
stories or 60 feet.
64Mezzanines (505)
- Considered part of floor below. Does not
contribute to building area or number of stories - Area 1/3 of room open to (2/3 industrial
occupancies or ½ Type I or II) - Openness Must not have walls over 42 in
height, unless one of the following - Occupant load of enclosed space does not exceed
10 - 2 means of egress, w/one having direct access to
an exit - Enclosed space lt 10 of mezzanine area
- Specific industrial and factory applications
65Area Modifications (506)
-
- (Equation 5-1)
- where
- Aa Allowable area per story (sq ft)
- At Tabular area per story in per Table 503 (sq
ft). - If Area increase factor due to frontage as
calculated in accordance with Section 506.2 - Is Area increase factor due to sprinkler
protection per Section 506.3 - Multiple stories 2
- Single Story 3
66Frontage Increase (506.2)
-
- (Equation 5-2)
- where
- If Area increase from frontage.
- F Building perimeter fronting a public way or
open space having - 20 feet (6096 mm) open minimum width (ft).
- P Perimeter of entire building (ft).
- W Width of public way or open space (ft) in
accordance with Section 506.2.1 - W at least 20 feet and W divided by 30 shall
not exceed 1.0. Where the value of W varies it
is based on the weighted average of each portion
of exterior wall and open space where the value
of W is between 20 and 30 feet.
67Total Building Area (506.4)
- Determined by multiplying the allowable area of
the first - floor (Aa), per Section 506.1, by the number of
stories - as listed below.
- For two-story buildings, multiply by 2
- For three-story or higher buildings, multiply by
3 and, - No story shall exceed the allowable area per
floor (Aa), as determined in Section 506.1 for
the occupancies on that floor. - Exceptions
- Unlimited area buildings in accordance with
Section 507 - The maximum area of a building equipped
throughout with an automatic sprinkler system per
Section 903.3.1.2 (NFPA 13R) determined by
multiplying the allowable area per floor (Aa),
per Section 506.1 by the number of stories.
68Building Heights and Areas
- 506.1.1 Basements need not be included in the
total allowable area provided they do not exceed
the area permitted for a one-story building.
69Unlimited Area (507)
- Requires 60ft clear around perimeter
- 60 feet to 40 feet
- Not more than 75 of perimeter of building
- Minimum 3 hour exterior walls in reduced space
- Opening protectives have 3 hour rating in reduced
space - One Story, unsprinklered
- Groups F-2, S-2
- One Story, sprinklered
- Groups B, F, M, or S
- Groups A-4 one story, other than Type V
- Two Story, sprinklered
- Groups B, F, M, or S
70Unlimited Area
- One story, sprinklered, Type II
- Group A-3 used as a church, community hall, dance
hall, exhibition hall, gymnasium, lecture hall,
indoor swimming pool or tennis court - No stage other than platform
- Floor 21 inches of grade and ramps for all exits
- One story, sprinklered, Type II, IIIA, or IV
- Group E
- Each classroom, 2 means of egress with one a
direct exit - Group H-2, H-3, H-4 in F and S if lt 10 building
area - Aircraft paint hangar
- Motion picture theaters of Type I or II
construction - Covered malls and anchor buildings per 402.6
71Example
72Solution
Step One Determine actual area Aact 200
125 25,000 sf Step Two Determine Tabular
height and area, from Table 503 Tabular
height 4 stories, 55 Tabular area, At 19,
000 sf.
73Solution
Step Three Apply Height increase for
sprinklers (1 story, 20) Allowable
height 5 stories, 75 Actual height 5
stories, 72 OK !
74Solution
Step Four Apply area increase for
frontage F 650 P 650 W
(25200301253020030125)/650 W28.46 If
600/600-0.2528.33/30.7115
75Solution
Step Five Apply area increase for
sprinklers for multiple story building,
Is2 Step Six Compute area formula Aa
19,00019,000.711519,0002 Aa 70,518 gt
25,000 OK!
76Solution Amax SAt
Step Eight Compute maximum area Amax SxAt,
where S3, At 70,518 Amax 70,518 3
211,554 Actual area of all floors Afloors
25,000 5 125,000
Building complies !
77Mixed Occupancies
- Two or more uses that are in different Groups
within the same building - Accessory occupancies
- Nonseparated occupancies
- Separated occupancies
78Incidental Use Area (508.2)
- Classified according to portion of building
containing incidental use area - Dwelling Unit exception
- Sprinklers protection required only in incidental
use area - Sprinklers require area to be separated by smoke
resistant construction
79IBC Table 508.2
80Accessory Occupancies (508.3.1)
- Similar to Incidental
- Subset of Mixed Occupancies
- No separation required
- Limited to 10 of the area of the story
- Can not exceed Table 503 values
- Area
- Height
81Accessory Assembly (508.3.1)
- Accessory Assembly lt 750 sq ft not considered
separate occupancies - Limited in area to 750 sq ft
82Example 1
83Example 2
84Nonseparated Occupancies(508.3.2)
- Each portion individually classified as to use
- Most restrictive type construction used for
entire building - Apply most restrictive parts of Chapter 9 (fire
protection) and Section 403 (high-rise) to entire
building - Apply other code sections based on the use of
each part of the building
85Separated Occupancies (508.3.3)
- Separated by fire barrier walls or horizontal
assemblies per Table 508.3.3 - Each fire area must comply with height
limitations based on use - Ratio of floor area/allowable area shall not
exceed 1 - Notes on Table 302.3.2
- Storage in B or M
- Commercial kitchens
86Table 508.3.3Required Separation of Occupancies
87Special Provisions (509.2)
- Pedestal Buildings - Enclosed Parking Garage
(S-2) with A, B, M or R above - Separate buildings
- Area Limitation
- Continuity of Fire Walls
- Number of Stories
- Type of Construction
- NOT Building Height
88Typical Pedestal Building
89Basic Requirements
- Basement/First Story is IA construction and
separated with a 3 hour horizontal assembly. - Building above is Group A (max. 300 Occupants),
B, M, or R - Shafts through separation assembly rated 2 hours
90Exceptions
- Shafts
- 3 hours rated below separation
- 1 hour above when less than 4 stories
- 1 hour opening protectives required
- Use below separation other than S-2
- Entry Lobbies, Mechanical Rooms
- Group A (300 max), B or M
91New for 2006
- Moved Mixed Occupancy provisions
- Mezzanine area to 50 in Type I and II
- Group A-1 A-2 in single story unlimited area
buildings - Occupancy separation now based on dissimilar risk
- Groups B and M under opening parking
92Questions?
93(No Transcript)
94IBC 2006 Chapter 6 Types of Construction
95Construction Types
- Specified by the designer
- Type I and II - Concrete and Steel
- Non-combustible
- Type III Masonry exterior and wood interior
- Non-combustible exterior
- Combustible interior
- Type IV Heavy Timber
- Non-combustible exterior (FRT in some cases)
- Sawn or laminated timber interior
- Type V Wood frame
- Combustible
96Combustibles in Type I and II
- List of 22 permitted uses
- FRT Wood
- Non-bearing partitions lt2 hours rated
- Unrated non-bearing exterior walls
- Roof construction in some cases
- Interior finishes, trim and millwork
- Blocking for handrails, millwork, etc
- Materials to protect joints and penetrations in
fire rated assemblies - Ducts, Piping and Wiring methods
97Table 601Fire resistance requirements for
Building Elements
98Table 602Fire resistance requirements for
exterior walls based on fire separation distance
99New for 2006
- Provided dimensions for Glulam members in Type IV
construction
100IBC 2006 Chapter 7 Fire Resistance-Rated
Construction
101Fire Rated Walls/Assemblies
- Many Levels of Separation
- Exterior walls
- Fire Walls
- Party Walls
- Fire Barriers
- Shaft Enclosures
- Fire Partitions
- Smoke Barriers
- Horizontal Assemblies
102Exterior Walls (704)
- Measured at a right angle from the building face
to the closest interior lot line, or the center
line of a street alley or public way, or an
imaginary line between two buildings on the lot.
103Exterior Wall Openings
- NFPA 13 system in other than group H-1, H-2 and
H-3 permits the maximum allowable area of
unprotected openings to be the same as the
tabulated limitations for protected openings.
104Exterior Walls
- Fire-resistance rating for fire separation
distance of - lt 5 feet for exposure from both sides
- gt 5 feet rated for exposure from the inside
- Projections - the more restrictive of the
following - A point one-third the distance to the lot line
from an assumed vertical plane located where the
protected openings are required in accordance
with section 704.8 - More than 12 inches into areas where openings are
prohibited
105Fire Walls (705)
- Used to create separate buildings
- Structurally independent
- Ratings not reduced by sprinklers
- Continuous from Foundation to Roof
- Imaginary Lot Lines
- Noncombustible except Type V
106Fire Walls Table 705.4
- Openings are limited in size and protected
107Firewall
108Firewall
109Fire Wall - Horizontal Continuity
- Required to extend 18 beyond exterior
- Exceptions
- 1 Hour exterior wall with opening protectives 4
feet to each side of the wall - Non-combustible exterior sheathing with
non-combustible exterior finish/siding - Non-combustible exterior sheathing with building
sprinkler system
110Option 2
111Option 3
112Fire Wall Continuity
- Vertical (705.6)
- Extend from the foundation to a termination point
at least 30 inches above both adjacent roofs. - 5 exceptions most common is 4 of non
combustible roof sheathing or decking with no
openings. - Horizontal Projecting Elements (705.5.2)
- Extend to the outer edges of horizontal
projecting elements such as balconies, roofs,
overhangs, canopies, marquees and architectural
projections that are within 4 feet of the fire
wall. - Exceptions 3, see text
- Stepped buildings (705.6.1)
- Terminate gt 30 inches above the lower roof level
- Exterior wall to 15 feet above the lower roof is
1 hour fire resistance rated from both sides - 2 exceptions
113Vertical Continuity (705.6)
- Maryland Exception
- 6. In Groups R-2 and R-3 as applicable in Section
with Type III, IV, and V construction walls
permitted to terminate at roof sheathing or deck,
if - 6.1
114Vertical Continuity (705.6)
- Exception 6 - Groups R-2 and R-3 with Type III,
IV, and V construction walls permitted to
terminate at roof sheathing or deck, if - 6.1 Noncombustible or FRT for 4 feet to each side
of walls - 6.2 Group R-2 NFPA 13 or 13R
- 6.2 Group R-3 NFPA 13, 13R, or 13D
- 6.3
- 5/8 Type X gypsum underside of roof to 4 feet
each side - No openings within 4 feet of fire wall
- Roof covering a minimum of Class C
115Party Walls
- Special type of Fire Wall
- Located on a lot line
- All penetrations are prohibited
116Fire Barriers (706)
- Only walls/vertical
- Shafts
- Exit enclosures
- Exit passageways
- Horizontal exits
- Incidental use areas
- Separation of mixed occupancies
- Single occupancy fire areas
117Fire Barriers (706)
- Less restrictive than Fire Walls
- Continuous from top of floor/ceiling assembly to
the floor or roof slab/deck above - Supporting construction of at least equal rating
118Shaft Enclosures (707)
- Sub-set of Fire Barriers
- Protect openings and penetrations through
floor/ceiling assemblies - 13 exceptions
- Rating based upon stories connected and floor
ratings - Continuous through concealed spaces
- Supported by same fire resistance rating
- Openings limited to those required for use of
shaft - Enclosures at top and bottom
119Fire Partitions (708)
- Dwelling unit separation walls
- Sleeping unit separation walls
- Tenant separation walls in covered malls
- Corridor walls
- Elevator lobby separation
- 1 hour rating
- NFPA 13 Type IIB, IIIB, VB - ½ rating
120FirePatition
121Smoke Barriers (709)
- One hour fire-resistance rating
- Continuous from floor slab to deck above and from
outside wall to outside wall - Primarily used in group I occupancies
- Permits occupants to be moved to other
compartments rather than evacuated - Penetrations and openings per 712 and 715
122Smoke Partitions (710)
- Corridors in Group I-2 occupancies
- Not fire rated walls
- Resists the passage of smoke
- Air transfer openings need smoke dampers
- Self closing doors
123Horizontal Assemblies (711)
- Fire resistance rating not be less than that
required by - Type of construction
- Occupancy separation
- Fire area separation
- Dwelling Unit separation
124Penetrations (712)
- Listed fire stop systems for
- Fire-resistance-rated walls
- Fire-resistance-rated assemblies
- Rated membrane penetrations
- Non-fire-resistance-rated assemblies
125Opening Protective (715)
- Openings in
- Rated exterior walls
- Fire barriers
- Shafts
- Fire partitions
- Smoke barriers
- Require
- Fire-resistance-rated glazing
- Fire doors
- Fire shutters
- Fire windows
126Determination of Fire-resistance
- Fire resistance ratings and fire test (703)
- Tested per ASTM E 119 and listed
- Calculated fire resistance ratings (721)
- Generally done by a fire protection engineer
- Only as prescribed in this section of the code
- Prescriptive ratings and tests (720)
- Tables 720.1(1), 720.1(2) 720.1(3)
127New for 2006
- Redefines Fire Barrier to be vertical only
- Adds labeling requirement for fire
resistance-rated glazing - Adds elevator lobby exceptions for shaft
pressurization and smoke partitions - Adds testing requirements for smoke barrier
penetrations
128Questions?
129(No Transcript)
130IBC 2006 Chapter 10 Means of Egress
131Means of Egress
- Occupant Load
- Size and capacity of egress system
- Number and location of exits
- Specific egress components
132General (1001.1)
- Means of egress requires may be covered
concurrently in - State Fire Prevention Code
- Enforced by State Fire Marshal or fire official
- Public Safety Article, 6-101 6-602, Annotated
Code of Maryland - COMAR 29.06.01
133Definitions
- Exit Access
- Leads from any occupied point to an exit
- Exit
- Separated from other interior spaces by fire
barriers to provide protected path from Exit
Access to Exit Discharge - Exit Discharge
- Between termination of an exit and the public
way - Exit Passageway
- Horizontal exit component
- Exit Enclosure
- Vertical or horizontal exit component
134General Means of Egress (1003)
- Ceiling Height
- Minimum 7 with some exceptions
- Protruding Objects
- Minimum 6-8 required under projections
- Max. 4 horizontal projection between 27 and 80
- Elevation Change
- lt 12 and the floor slopes at 120 or less,
stairs or a ramp are not required. - Continuity
- The path of egress from any occupiable point in
the building to the public way must be
uninterrupted.
135Occupant Load (1004)
- Without fixed seating
- Determined per Table 1004.1.1
- If not listed Building Official determines
- Building official can approve a smaller load
- Floor area/floor area per occupant occupant
load - Add occupant loads where occupants from an
accessory area discharge through a primary space
136Table 1004.1.1 (Partial)
137Determining Occupant Load
- The designer may increase the occupant load up to
one occupant for every 7 SF. - Seating/aisle/furniture plan may be required to
be posted by the building official - Posting of Occupant Load
- Assembly rooms must be posted
- Sign near main exit
- Approved legible, permanent design
138Determining Occupant Load
- Treat outdoor areas like a room in the building
- Legitimate means of egress required from fenced
areas. - An outdoor area will increase the occupant load
if the means of egress is back through the
building - The occupant loads from stacked stories are NOT
added together - Where floor levels converge from above and below
coverage on an intermediate discharge level, the
occupant loads ARE added - Add mezzanines occupant load to the floor below
139Determining Occupant Load
- Fixed Seating
- Count seats or 18 per occupant on benches and
24 per occupant in dining booths - Multiple Occupancies
- Each occupancy must meet its minimum egress
requirements. - Shared egress elements must meet the requirements
for stricter occupancy.
140(No Transcript)
141Occupant Load Solution
142Egress Width (1005)
- Occupant load egress width per occupant.
- Doors net 32 clearance (34 for doors that open
180 deg.) - When 2 means of egress are required, no single
doorway can account for more than 50 of the
required width - Corridors, ramps net width as required elsewhere
143Table 1005.1Egress Width per Occupant Load
144Means of Egress Illumination (1006)
- Illumination Required at all times space is
occupied - Illumination Level of 1 foot candle at walking
surface - Emergency Power for at least 90 minutes for
egress elements in buildings requiring two exits.
These include corridors, stairs, exterior
stairs, and interior and exterior discharges
145Accessible Means of Egress (1007)
- One required where one means of egress is
required. - Two required when more than one means of egress
is required. - NOT required in alternations to existing
buildings - Continuous to the public way unless area of
refuge is provided
146Accessible Means of Egress
- Elevator on emergency power required when
building is four or more stories - Unless fully sprinklered and horizontal exit or
ramp is provided. - Enclosed Stairways at least 48 wide between
handrails and one 48 30 area of refuge per 200
occupants - NFPA 13/13R 48 wide not required but area of
refuge still needed.
147Area of Refuge (1007.6)
- Minimum 3048 outside the required egress width
- Separated by smoke barrier or stairways in
nonsprinklered buildings. - Direct access to stair or elevator with emergency
power - 2 way communication (w/instructions) required.
- AREA OF REFUGE sign required.
148Doors (1008)
- Minimum 32 clear width w/ 4 project at least
34 AFF permitted. 3-0 doors typ. meet this
requirement - Side-hinged swinging with 6 exceptions
- Swing in the direction of travel where serving a
space with an occupant of 50 or more. - Door swings can never reduce the required width
by more than ½. - Door swings shall never project more than 7 into
the required width.
149Special Doors
- Revolving doors are usually NOT part of means of
egress - Power-operated doors must swing open under 50 lb
force. - Horizontal sliding doors - 8 specific
requirements. - Access-controlled egress doors - 6 specific
requirements. - Security grilles - Groups B, F, M, and S only.
- Operable from egress side without the use of a
key or special knowledge or effort. - No more than ½ of the means of egress doorways
- Always full-open when occupied by public
150Doors
- Floor Elevation must be same on both sides of
door - ½ drop at exterior doors
- 4 other exterior door exceptions
- Landings at Doors
- Minimum width must equal door or stair it serves
and at least 44 long - Door arrangement
- Min. of 48 between one door and the arc of the
other door. - Both doors must swing in the same direction or
out of the enclosed space.
151Door Operations
- Readily operable from the egress side without the
use of a key or special knowledge or effort. - Hardware shall not require tight grasping or
twisting of the wrist to operate and mounted 34
to 48 high - Locks and Latches effectively an exception to
above - Detention facilities
- Keyed dead bolt in Group A (lt300 Occupants),
Groups B, F, M, S and churches - Readily identifiable
- Unlocked when occupied
- Group R (e.g. hotel door chains)
152Doors Locks
- Bolt Locks
- Manually operated flush bolts not permitted
- Unlatching
- Unlatching the door shall not require more than
one operation - Delayed Egress Locks
- Must meet all 6 specific requirements.
- Stairway Doors
- Locked from outside at the discharge door
- Doors per 403.12
- Locked from inside in buildings 4 stories or less
153Stairways (1009)
- Stairway Width
- Minimum 44 except 36 for lt 50 occupants
- Headroom
- 6-8 (80) minimum
- Treads and Risers
- 7 max. riser. 11 min. tread
- 3/8 max. dimension change
- Stairway Landings
- Width as stair
- Length same as width up to 48
154Tread and Risers (1009.3)
- Removed exceptions 4 and 5 and replaced them with
the following - Exception 4
- Group R-3 and R-2 (inside dwelling unit and Group
U accessory to R-3 - Riser Height 8-1/4 max
- Tread Depth 9 min
- Winder Depth 9 min _at_ walking line and 6
minimum - Nosing (Tread depth lt 11) ¾ min and 1-1/4 max
- Exception 5
- See Maryland Rehabilitation Code for replacement
of existing stairways
155Stairways
- Stairway Construction
- Materials same as construction type
- Prevent accumulation of water
- Circular Stairways
- Same riser limitations as a regular stair
- Some variation in tread
- Winders
- Not permitted in a means of egress except in a
dwelling unit
156Stairways
- Stairway to roof - buildings 4 or more stories
- Exceptions for sloped roofs and unoccupied roofs.
- Spiral Stairways
- Only a means of egress in dwelling or space lt 250
SF and lt 5 occupants - Special consideration for treads, risers, width,
and headroom. - Alternating Tread Devices
- Means of egress in limited applications
- 250 SF mezzanines in Groups F, H and S
- Unoccupied roof
- Group I-3 Guard and observation tower
157Ramps (1010)
- Slope
- Maximum of 112
- Non-pedestrian to 18
- Cross slope maximum of 148
- Maximum rise for any run is 30
- Minimum dimensions
- Width same as a corridor, 36 minimum between
handrails - Headroom is 6-8 minimum
- Ramp width shall not reduce in direction of
travel - Doors shall not reduce width to lt42
158Ramps
- Landings
- Minimum 60 long and equal to ramp width
- Change in direction requires a 60 60 landing
- Construction
- Materials same as construction type
- Slip-resistant surface
- Prevent accumulation of water
- Edge Protection
- Must provide railings or curb
- Guards
- Provide where the ramp surface gt 30 above grade
or floor
159Handrails (1012)
- Handrails
- Both sides of stairs and ramps
- Exceptions for R occupancies and aisle stairs
- Intermediate handrails within 30 of the required
stairway width - Graspable and continuous
- Required to extend past top and bottom risers
- Clearance of 1-1/2 between wall and handrail
160Graspability (1012.3)
- Exception for Group R-3 and R-2 (in dwelling
unit) - Circular cross section
- 1.25 min to 2.625 max
- Other Shapes
- equivalent grasping surface
- Edges
- 0.125 radius min.
161Exit Signs (1011)
- Visible from any direction of egress travel such
that no point in corridor is more than 100 foot
or listed viewing distance from next sign. - Only if more than one exit is required
- Not in main exit if obviously identifiable
- Not required in Group R-1, R-2, R-3 units
- Not required in Group I-3 sleeping rooms
- Not required in Group A-4 and A-5 in specific
areas
162Exit Signs
- Internally or externally illuminated at 5
foot-candles with a minimum of 90 minute
emergency power - Exceptions for tactile signs
- Graphics
- Legible letter, 6 inches high and ¾ inch wide
strokes in high contrast - Letters in EXIT 2 inches wide except I
- Minimum spacing between letters .375 inch
163Guards (1013)
- Where required
- Floor is 30 inches above floor or grade below
- Mechanical equipment or roof hatch within 10 feet
of roof edge - Guard height at least 42
- Opening Limitations
- lt 4 up to 34 and lt8 above that
- Group R-2 and R-3 Units lt 4.375
- Loads on Guards (1607.7.1)
- 50 plf applied at top and 200 psf concentrated
load - For one and two family only single 200 pound
concentrated load.
164Exit Access (1014)
- Egress through Intervening Spaces
- One tenant cannot pass through another
- Exception small tenant inside large tenant, a
bank in a supermarket or coffee shop in big box
store (1014.2.1) - Common Path of Egress Travel (1014.3)
- 75 of travel before occupants have separate and
distinct paths of travel to 2 exits. - Group B, F and S with NFPA 13 - 100
- Group B, S and U with lt 30 occupants - 100
- Group I-3 - 100
- Group R-2 with NPFA 13 125
165(No Transcript)
166Aisles (1014.4)
- An exit access component that defines and
provides an path of egress travel - Group B and M
- Width per Table 1005.1, minimum of 36
- Group M with merchandise pad - Aisle Accessway
- Width minimum of 30 (Non-accessible)
- Common path of travel 30
- 75 lt 50 occupants
- Seating at tables and counters
- Width measured of 19 from edges of tables and
counters
167Exit and Exit Access Doorways (1015)
- Two Doorways are required when
- Occupant load exceeds Table 1015.1
- Common path of travel exceeds 1014.3
- Where required for special rooms
- Doorway Arrangement
- Unobstructed
- Separation of doors from multiple exits.
- Two exits separated by ½ (or 1/3) diagonal
- Three or more exits at least two exits separated
by ½ (or 1/3) diagonal
168Exit Access Travel Distance (1016)
- Table 1016.1
- Exit Access Travel Distance
- Total travel distance from most remote point to
the nearest exit from Table 1016.1 - If egress path includes open stairs, measure down
stairs to exit discharge from building - Can get increases for roof vents in S-1 and F-1
- Can get an increase for egress across an exterior
balcony
169Corridors (1017)
- Table 1017.1
- Corridor Fire-Resistance Rating
- Required rating per Table
- Not required in Group E where each room has a
direct discharge to the exterior - Not required in a Group R unit
- Not required in an open parking garage
- Not required in Group B that requires only 1
means of egress
170Corridors Width (1017.2)
- Width not less than 44
- 24 for utility access
- 36 with an occupant capacity lt 50
- 36 in a dwelling unit
- 72 with an occupant capacity gt 100 in an E
- 72 Group I surgery
- 72 I-2 where beds are moved
171Dead Ends (1017.3)
- Dead ends limited to 20 in spaces requiring 2 or
more means of egress - Group B and F with NFPA 13 -50
- Can extend to 2.5 times its least width
- Rated corridors continuous from point of entry to
an exit - Rated foyers, lobbies and reception rooms
172Ventilation in Corridors
- Air Movement in Corridors
- Can not be used for supply, return, exhaust,
relief, or ventilation - Corridor Ceiling
- Can use the space above the ceiling in a corridor
as a return air plenum under any of five specific
conditions
173Exits (1018)
- Shall not be used for any purpose that interferes
with its function as a means of egress - Once a level of protection is given it shall be
continuous to the exit discharge
174Number of Exits and Continuity (1019)
- All occupants shall have access to the minimum
number of exits required for the building - Based on Table 1019.1
- Occupant load 1 500 2 exits
- Occupant load 501 1000 3 exits
- Occupant load Over 1000 4 exits
- Parking structures require 2 exits for every
level. Vehicle ramps not considered exits. - Exit Continuity
- Exits must be continuous from the point of entry
to exit discharge.
175Number of Exits and Continuity
- Table 1019.2
- Building with One Exit
- Buildings with one exit
- Based on Table 1019.2 with maximum 1 basement
level - Group R-3
- Single level building where the space served is a
single means of egress space per 1015.1
176Vertical Exit Enclosures (1020)
- Two hour fire barrier where connecting 4 or more
stories. Otherwise one hour. - 9 exceptions
- Openings limited to those required for egress and
must be protected - Penetrations limited to required exit doors,
sprinkler service, and required services.
177Vertical Exit Enclosures
- Ventilation independent of other systems and must
connect directly to the exterior or be separated
from the building. - Exterior walls of interior stairs rated if
exposed to the buildings exterior walls at angle
lt 180 - Discharge must be identified clearly and have a
barrier to keep occupants from passing it - High-rise and underground buildings, a
smoke-proof enclosure is required for stairs or
stairs pressurized per 909.20
178Exit Passageways (1021)
- Appear to be corridors, but part of an exit, same
protection as enclosed exit stair - Size as a corridor
- Fire Rating minimum 1 hour unless serving a 2
hour stair - Openings same as stair
- Penetrations same as stair
179Horizontal Exits (1022)
- An egress path through a fire wall or barrier
where occupants remain on the same level - Cannot be the only exit.
- Not more than ½ of the total exits or exit width
- Two hour separation down to grade or supported on
two hour floors and must extend from exterior
wall to exterior wall - Provide an area of refuge at 3 sf per occupant
for both sides of exit
180Exterior Exit Ramps and Stairways (1023)
- Use in a Means of Egress
- Group I-2 Not permitted
- Other Groups - lt 6 stories or lt 75 above fire
department access - Open on at least one side at each floor or
landing to a yard, court or public way with
minimum 35 SF opening - Separated from building interior the same as
interior stairs - 4 exceptions
181Exit Discharge (1024)
- Exits shall discharge to the exterior at grade or
provide direct access to grade and shall not
re-enter building - 3 exceptions
- Up to 50 of number and capacity may discharge
onto unobstructed, sprinklered floor areas - Up to 50 of number and capacity may discharge
into a 10 30 vestibule separated from the rest
of the building - Open parking stairs may discharge inside the
building on the level of exit discharge
182Exit Discharge
- Exit discharge location at least 10 from
property lines and buildings - Egress Courts
- Sized per 1005.1
- gt 44 wide and 84 tall
- Rated one hour unless at least 10 feet wide
- Access to Public Way
- Direct and unobstructed access to a public way
- Safe dispersal area provided at least 50 from
the building
183(No Transcript)
184Assembly (1025)
- Main Exit
- Occupant load gt 300
- Sized for at least 50 of total occupant load
- Other Exits
- Occupant load gt 300
- Sized at least 50 of total occupant load
- Foyers and Lobbies Group A-1
- Separated from the required egress aisles by
fixed barriers
185Emergency Escape and Rescue (1026)
- Group R and I-1at least one exterior emergency
escape - Basements
- Sleeping rooms below fourth story
- Seven exceptions
- Minimum size and height
- 5.7 sf and 24 high and 20 wide
- 44 max. above floor
- Window wells
- 3 3 minimum
- Ladder if over 44 deep
186New in 2006
- Limits minimum SF/occupant to 7
- Reduced panic hardware threshold to 50
- Removed Area of Refuge exception for sprinklered
buildings - Increased common path of travel to 125 ft for
NFPA 13 sprinklered Group R-2
187IBC 2006 Chapter 16 Structural Design
188Construction Documents (1603)
- Design Details
- Structural Members
- Size
- Section
- Relative location
- Dimensions
- Floor levels
- Column centers
- Offsets dimensioned
- Structural Loading
- Floor live loads
- Roof live loads
- Roof snow loads
- Wind design data
- Seismic design data
- Dead loads
189Roof Live Loads (1603.1.1)
- Live loads
- Per Table 1607.1
- Partition Loads
- Live load lt 80 psf
- Additional load of 15 psf
- Dead loads
- Building material
- Permanent fixed equipment (i.e. mechanical
equipment)
190Roof Live Loads (1603.1.2)
- Live loads
- Per Table 1607.1
- Minimum of 20 psf
- Dead loads
- Building material
- Permanent fixed equipment (i.e. mechanical
equipment)
191Roof Snow Load (1603.1.3)
- Ground Snow Load - Pg
- Flat-Roof Snow Load - Pf
- Snow Exposure Factor - Ce
- Snow Load Importance Factor - I
- Thermal Factor - Ct
192Wind Design Data (1603.1.3)
- Basic Wind Speed (3-sec gust)
- Wind Importance Factor
- Wind Exposure
- Internal Pressure Coefficient
- Component and Cladding (psf)
193Earthquake Design Data (1603.1.5)
- Seismic Importance Factor I and Occupancy
Category - Mapped Spectral Response Acc. SS and S1
- Site Class
- Spectral Response Coefficients SDS and SD1
- Seismic Design Category
- Basic Seismic Force Resisting System
- Design Base Shear
- Seismic Response Coefficient CS
- Response Modification Factor
- Analysis Procedure Used
194Flood Design Data (1603.1.6)
- For buildings in a Flood Hazard Area
- Not subject to wave action
- Elevation of lowest proposed floor including
basement - Elevation of non-residential building to be dry
flood proofed - Subject to wave action
- Elevation of lowest proposed structural member
including basement
195New for 2006
- Changed simplified wind load and seismic design
procedures to ASCE 7 references - Provided formula to convert Fastest Mile wind
speeds to 3 Second Gust - Reduced partition load to 15 psf
196IBC 2006 Chapter 18 Soil Foundation
197Foundation and Soils Investigations (1802)
- Where required
- Questionable soil
- Expansive soil
- Ground wat