Title: NASCC 1
1Wind Design Considerations for Steel Joists and
Joist Girders
Perry S. Green, PhD, Technical Director Steel
Joist Institute Myrtle Beach, SC Tim Holtermann,
PE, Corporate Engineering Manager, Canam Steel
Corp. Washington, MO Mark Perry, PE, General
Manager, Quincy Joist Company Quincy, FL Joe
Pote, PE, Director Engineering, Research and
Development, CMC Joist Deck Hope, AR
2Introduction
- Commercial manufacture of open web steel joists
began in 1923 - The Steel Joist Institute was formed in 1928
- The use of steel joists has continued to grow
year after year for both floors and roofs. - Millions of steel joists and Joist Girders are
put in service each year.
3General Nature of Wind Loads
- Typical Steel Joist and Joist Girder Buildings
- Windstorms
- Building type commercial, industrial
- Building shape low rise, rectangular
- Roofing systems
4Windstorm Damage to Roof in Texas 05 March 2004
5Windstorm Damage to Roof in Texas 05 March 2004
6Hurricane Charley Category 4 Storm Across Florida
13-14 August 2004
7Hurricane Charley Category 4 Storm Across Florida
13-14 August 2004
8EF-2 Tornado Damage Near Ft. Worth, TX 24 April
2008
9EF-2 Tornado Damage Near Ft. Worth, TX 24 April
2008
10EF-2 Tornado Damage Near Ft. Worth, TX 24 April
2008
11EF-2 Tornado Damage Near Ft. Worth, TX 24 April
2008
12Population Trends in Hurricane-Prone Regions of
the U.S.
- Southeast and Gulf of Mexico Most rapid coastal
growth in recent decades and will continue to
grow. - Southeast 8 million (1960) ? 23 million
projected (2015) - Gulf of Mexico 8 million (1960) ? 22 million
projected (2015)
13Top 10 Deadliest Hurricanes to Strike the US
1851-2005
Footnotes Could be as high as 12,000. Could
be as high as 3,000. Midpoint of 1,000 2,000
range. AP total as of Dec. 11, 2005.
Midpoint of 1,100-1,400 range. Sources
NOAA Insurance Information Institute.
Hurricane Katrina was the deadliest hurricane to
strike the US since 1928
14Roof Design to Resist Wind Loads
- Codes and Standards
- 2005 SJI Standard Specifications and Code of
Standard Practice - Provisions from 2006 International Building Code
- Provisions from ASCE/SEI 7-05
- Design for Lateral Wind Loads
- Design of Joist Bearing Seats for Wind Uplift
- Design Example - Placement of Joist Bridging
- Summary and Conclusions
15Standards and Codes
- 2005 SJI Standard Specifications and Code of
Standard Practice - Provisions from 2006 International Building Code
- Provisions from ASCE/SEI 7-05
16Roof Design to Resist Uplift Loads
- The nominal loads and load combinations shall be
as stipulated by the applicable code under which
the structure is designed, and as shown by the
Specifying Professional in the contract
documents. In the absence of a specified
building code such as the International Building
Code (IBC 2006), the ASCE/SEI 7-05 (ASCE 2005)
Minimum Design Loads for Buildings and Other
Structures shall be used as the basis for the
loads and load combinations.
1742nd Edition SJI Catalog 2005
- K-Series Standard Specifications
- K-Series Load Tables
- KCS Joists
- LH- and DLH-Series Standard Specifications
- LH- and DLH-Series Load Tables
- Joist Girders Standard Specifications
- Joist Girder Weight Tables
182005 SJI Standard Specification for Open Web
Steel Joists, K-Series
- 5.11 UPLIFT
- Where uplift forces due to wind are a design
requirement, these forces must be indicated on
the contract drawings in terms of NET uplift in
pounds per square foot (Pascals). The contract
documents shall indicate if the net uplift is
based upon LRFD or ASD. When these forces are
specified, they must be considered in the design
of joists and/or bridging. A single line of
bottom chord bridging must be provided near the
first bottom chord panel points whenever uplift
due to wind forces is a design consideration. -
-
192005 SJI Standard Specification for Longspan
Steel Joists, LH-SeriesDeep Longspan Steel
Joists, DLH-Series
- 104.12 UPLIFT
- Where uplift forces due to wind are a design
requirement, these forces must be indicated on
the contract drawings in terms of NET uplift in
pounds per square foot (Pascals). The contract
documents shall indicate if the net uplift is
based upon LRFD or ASD. When these forces are
specified, they must be considered in the design
of joists and/or bridging. A single line of
bottom chord bridging must be provided near the
first bottom chord panel points whenever uplift
due to wind forces is a design consideration.
202005 SJI Standard Specification for Joist Girders
- 1004.9 UPLIFT
- Where uplift forces due to wind are a design
requirement, these forces must be indicated on
the contract drawings in terms of NET uplift in
pounds per square foot (Pascals). The contract
drawings must indicate if the net uplift is based
on ASD or LRFD. When these forces are specified,
they must be considered in the design of Joist
Girders and/or bracing. If the ends of the
bottom chord are not strutted, bracing must be
provided near the first bottom chord panel points
whenever uplift due to wind forces is a design
consideration.
212005 SJI Code of Standard Practice
- 1.4 DESIGN
- In the absence of ordinances or specifications to
the contrary, all designs prepared by the
specifying professional shall be in accordance
with the Steel Joist Institute Standard
Specifications Load Tables Weight Tables of
latest adoption.
222005 SJI Code of Standard Practice
- 6.1 PLANS FURNISHED BY BUYER
- (a) Loads
- The Steel Joist Institute does not presume to
establish the loading requirements for which
structures are designed. - Â
- The Steel Joist Institute Load Tables are based
on uniform loading conditions and are valid for
use in selecting joist sizes for gravity loads
that can be expressed in terms of "pounds per
linear foot" (kiloNewtons per Meter) of joist.
The Steel Joist Institute Joist Girder Weight
Tables are based on uniformly spaced panel point
loading conditions and are valid for use in
selecting Joist Girder sizes for gravity
conditions that can be expressed in kips
(kiloNewtons) per panel point on the Joist Girder.
232005 SJI Code of Standard Practice
- 6.1 PLANS FURNISHED BY BUYER
- (a) Loads (contd)
- The specifying professional shall provide the
nominal loads and load combinations as stipulated
by the applicable code under which the structure
is designed and shall provide the design basis
(ASD or LRFD). - The specifying professional shall calculate and
provide the magnitude and location of ALL JOIST
and JOIST GIRDER LOADS. This includes all
special loads (drift loads, mechanical units, net
uplift, axial loads, moments, structural bracing
loads, or other applied loads) which are to be
incorporated into the joist or Joist Girder
design. For Joist Girders, reactions from
supported members shall be clearly denoted as
point loads on the Joist Girder. When necessary
to clearly convey the information, a Load Diagram
or Load Schedule shall be provided.
242005 SJI Code of Standard Practice
- 6.1 PLANS FURNISHED BY BUYER
- (a) Loads (contd)
- The specifying professional shall give due
consideration to the following loads and load
effects - 1. Ponded rain water.
- 2. Accumulation of snow in the vicinity of
obstructions such as penthouses, signs,
parapets, adjacent buildings, etc. - 3. Wind.
- 4. Type and magnitude of end moments and/or
axial forces at the joist and Joist Girder end
supports shall be shown on the structural
drawings. For moment resisting joists or Joist
Girders framing near the end of a column, due
consideration shall be given to extend the
column length to allow a plate type connection
between the top of the joist or Joist Girder
top chord and the column.
25Specifying Design Loads and Load Combinations for
Joists Used as Part of the Lateral Load Resisting
System
- For clear definition of loads for joists used as
part of the lateral load resisting system, the
following guidelines should be followed - All externally applied loads should be defined by
Load Category (Live, Dead, Snow, Wind,
Earthquake, Collateral, etc.). - a. Avoid use of pre-combined load callouts such
as Total Load, Factored Load, or Net Uplift
Load, as these cannot be readily separated into
their various load components, for correct
assembly of load combinations with appropriate
multipliers. - b. For Dead Loads, if Net Uplift is a design
consideration, be sure to include both a maximum
dead load for inclusion with gravity loads, and
a minimum dead load for inclusion with upward
acting loads. One convenient method of
managing this is to specify the minimum dead as
Dead Load (D) and specify the difference between
minimum dead and maximum dead as Collateral Load
(C).
26Specifying Design Loads and Load Combinations for
Joists Used as Part of the Lateral Load Resisting
System
- System internal forces which behave linearly, and
may be algebraically summed, such as strut forces
from a deck diaphragm, braced frame, shear wall,
etc. should also be defined by Load Category,
just the same as the externally applied loads. - All potentially controlling design load
combinations must be specified to the joist
manufacturer, for investigation during the design
of the joists and girders. Along with the
required joist design load combinations, the
Specifying Professional must also indicate
whether the design procedure is to be ASD or
LRFD. Either method may be specified, but it is
important for the load combinations and design
methodology to be properly aligned. - 4. System internal forces which behave
non-linearly, such as joist end moments and axial
loads determined via a second-order frame
analysis must be specified for each individual
load combination. These second-order analysis
system internal forces do not behave linearly,
and therefore cannot be algebraically summed by
the joist manufacturer.
27Standards and Codes
- 2005 SJI Standard Specifications and Code of
Standard Practice - Provisions from 2006 International Building Code
- Provisions from ASCE/SEI 7-05
282006 International Building Code
- SECTION 2206 STEEL JOISTS
- 2206.1 General
- 2206.2 Design
- The registered design professional shall indicate
on the construction documents the steel joist
and/or steel joist girder designations from the
specifications listed in Section 2206.1 and shall
indicate the requirements for joist and joist
girder design, layout, end supports, anchorage,
non-SJI standard bridging, bridging termination
connections and bearing connection design to
resist uplift and lateral loads. - 2206.3 Calculations
- 2206.4 Steel joist drawings
- 2206.5 Certification
292006 International Building Code
- SECTION 1605 LOAD COMBINATIONS
- 1605.2 Load combinations using strength design or
load and resistance factor design - 1605.2.1 Basic load combinations
1.4D (Eqn 16-1) 1.2D 1.6L 0.5(Lr or
S or R) (Eqn 16-2) 1.2D 1.6(Lr or S or R)
(f1L or 0.8W) (Eqn 16-3) 1.2D 1.6W f1L
0.5(Lr or S or R) (Eqn 16-4) 1.2D 1.0E
f1L f2S (Eqn 16-5) 0.9D 1.6W
(Eqn 16-6) 0.9D 1.0E (Eqn 16-7)
302006 International Building Code
- SECTION 1605 LOAD COMBINATIONS
- 1605.3 Load combinations using allowable stress
design - 1605.3.1 Basic load combinations
D (Eqn 16-8) D L (Eqn 16-9) D
(Lr or S or R) (Eqn 16-10) D 0.75L
0.75(Lr or S or R) (Eqn 16-11) D (W or
0.7E) (Eqn 16-12) D 0.75((W or 0.7E)
L (Lr or S or R)) (Eqn 16-13) 0.6D W
(Eqn 16-14) 0.6D 0.7E (Eqn 16-15)
31Standards and Codes
- 2005 SJI Standard Specifications and Code of
Standard Practice - Provisions from 2006 International Building Code
- Provisions from ASCE/SEI 7-05
32ASCE 7-05 Specified Wind Loads
- Basic parameters
- Wind speed, importance, exposure
- Significance / importance of exposure category
- Exposure C is default, while charts are based
on B - The difference is often 30 to 40 percent
33ASCE 7-05 Basic Wind Speed Map
34ASCE 7-05 Specified Wind Loads
- It all looks simple when the building structure
appears to be a simple rectangle made up of large
monolithic elements as described in Figure 6-3. - The reality is when the building shape is more
complex comprised of numerous elements then it is
not as easy to determine the loadings on joists
in corners and Joist Girders that pass through
both edge and corner zones.
35ASCE 7-05 Specified Wind Loads
36ASCE 7-05 Specified Wind Loads
37Chapter 6 Wind Loads
- When wind uplift is a design consideration, it
should be specified as net uplift on the steel
joists and Joist Girders. - The Specifying Professional knows the design dead
load and if there are collateral dead loads that
should not be deducted from the gross uplift. - Steel joists are considered components and
cladding (CC). - The joist tributary width need not be less than
one-third the joist span.
38Chapter 6 Wind Loads
- Joist Girders can be considered part of the main
wind force-resisting system (MWFRS). Most often,
separate MWFRS pressure values are not provided
for the Joist Girders, and the joist supplier
applies the end reaction (net) uplift forces from
the joists (CC) to the Joist Girders. - Is this conservative?
- Joist Girder tension webs must be designed to
resist, in compression, 25 percent of their axial
force. - Hence, uplift loads on a Joist Girder of less
than 25 percent of the gravity loads have minimal
or no effect on the girder design.
39Positive Wind Pressure Considerations
- The total joist load for the purposes of
selecting a joist designation should represent
the maximum result of the load combinations of
IBC Section 1604, which may include a downward
(positive) wind force in the controlling load
case. - Per ASCE 7-05 Section 6.1.4.2, the design wind
pressure for components and cladding shall not be
less than 10 psf. - The applicable load cases from IBC 2006 are
- For LRFD
- 1.2D 1.6(Lr or S or R) (f1L or 0.8W)
(Eqn 16-3) - 1.2D 1.6W f1L 0.5(Lr or S or R) (Eqn
16-4) -
- For ASD
- D (W or 0.7E) (Eqn 16-12)
- D 0.75((W or 0.7E) L (Lr or S or R))
(Eqn 16-13)
40Positive Wind Pressure Considerations
- Example (ASD)
- D 20 psf
- Lr 20 psf
- W 10 psf
- TL D Lr 40 psf
- Or
- TL D 0.75 (W Lr) 42.5 psf ? Governs
- Joist Span 46 0
- Joist Spacing 6 0
- Total Uniform Load 42.5 psf x 6 0 255 plf
- Live Load 20 psf x 6 0 120 plf
41Positive Wind Pressure Considerations
- Example (ASD) Contd
- Choose a 28K9 from the SJI ASD Economy Load Table
42Positive Wind Pressure Considerations
- Example (ASD) Contd
- Choose a 28K9 from the SJI ASD Economy Load Table
- Note If the positive wind pressure of 10 psf
was not considered in the joist selection
process, a 28K8 would have been selected. Also,
one could have selected a 24K10 as it does not
require erection stability bridging. - Conclusion
- It is not appropriate to select a joist
designation based on D Lr only and then provide
a positive wind pressure expecting the joist
manufacturer to check the designation.
43ASCE 7-05 Specified Wind Loads
- Maximum Dead Load (for gravity loading)
- Minimum Dead Load (for wind uplift)
- Or
- DLmin DLmax - Collateral Load (also for wind
uplift)
44ASCE 7-05 Specified Wind Loads
- What Constitutes Net Uplift?
- For ASD,
- the uplift load combination is 0.6D W
- For LRFD,
- the uplift load combination is 0.9D 1.6W
- The EOR may need to differentiate between
minimum and maximum dead load.
45ASCE 7-05 Specified Wind Loads
- What constitutes Net Uplift? Lets look at the
ASD Basic Load Combinations - Amplified DL resistance by 1.65 for uplift is not
desirable! So instead,
46Wind Loads Net Uplift Zone Diagram
47Properly Applying Wind Loads to Steel Joists and
Joist Girders
- Many steel joist structures will qualify for the
Method 1 Simplified Procedure in ASCE7-05. - Conditions required for use of the Simplified
Procedure include - Roof height less than 60 feet
- Enclosed structure
- Regular-shaped building
- Roof is not steeply sloped
48Properly Applying Wind Loads to Steel Joists and
Joist Girders
- Note that even if the Main Wind Force Resisting
System (MWFRS) does not qualify for the
Simplified Procedure, the Components and Cladding
may. - Net pressure vs. net uplift
49Properly Applying Wind Loads to Steel Joists and
Joist Girders
- Clarifications and Interpretations
- ASCE simplified method described in Section
6.4.2.2 provides a formula for net design wind
pressure. This is NOT the same as SJI section
5.11 NET uplift. - ASCE net is the sum of internal and external
pressures. - SJI net, is the final resultant pressure, less
appropriate dead load result of the load
combination
50Properly Applying Wind Loads to Steel Joists and
Joist Girders
- The chart on the following slide is a typical
components and cladding roof wind pressures chart
provided on the contract documents. - Roof pressure needs to be converted to NET
uplift, or more correctly the result of the
appropriate load combination for wind forces
acting upward.
51Properly Applying Wind Loads to Steel Joists and
Joist Girders
52Properly Applying Wind Loads to Steel Joists and
Joist Girders
- Per ASCE definition of Effective Width, take span
times an effective width that is not less than
one third the span. - Note This is specifically referenced for the
ASCE Method 2 charts, but it should also apply to
ASCE Method 1 (simplified).
53Properly Applying Wind Loads to Steel Joists and
Joist Girders
- So for steel joists, a simple rule is that for
all joist spans of 18 foot or greater, use the
100 square foot values, i.e. 18 x 6 106 gt 100
ft.2 - So if a project does not have any spans less than
18 feet, there is no need for a detailed chart
with values by square foot. - The light weight of joists under 18 foot spans
often allows for a conservative uplift value to
be used rather than a detailed interpolation for
the exact square footage.
54Properly Applying Wind Loads to Steel Joists and
Joist Girders
- For spans of at least 13 feet (1313/3 56.33
ft.2), just use the 50 square foot value, or if
no values are listed for 50 sq. ft., use the
average of 10 and 100 sq. ft. values. - For joist spans less than 13 feet, the 10 sq. ft.
value could conservatively be used.
55Wind Design Considerations for Steel Joists and
Joist Girders
- Other considerations
- Overhangs have significant uplift
- TCXs automatically have same capacity as
downward gravity. - But uplift on overhangs can easily exceed
gravity, particularly in coastal areas or
hurricane prone regions.
56Properly Applying Lateral Wind Loads to Steel
Joists and Joist Girders
- Lateral Load Resisting Systems
- Diaphragm and Shear Walls
- Braced Frames
- Rigid Frames
- Local Wind Bracing (Kickers)
- Roof Wind Screens
57Lateral Load Resisting Systems Diaphragm and
Shear Walls
58Lateral Load Resisting Systems Joist Seat
Rollover
Note Force V should be given on the structural
drawings as a joist design requirement.
59Lateral Load Resisting Systems Deck Support
Angle
60Deck Support Angle and Joist Seat Rollover
61Shear Collector with K-Series Joist
Lateral Load Resisting Systems Alternate Detail
to Joist Seat Rollover
62Shear Collector with LH-Series Joist
Lateral Load Resisting Systems Alternate Detail
to Joist Seat Rollover
63Lateral Load Resisting Systems Braced Frames
Steel joists may be used as diaphragm chord
elements, or as collector elements in frame lines.
64Chord Forces - Axial
- Chord Forces are carried as additional axial
loads by the top chords of joists and/or Joist
Girders. - Chord Forces may vary from one end of the chord
to the other. The additional axial load for each
joist and/or Joist Girder must be indicated. - Connections to transfer additional axial loads
from one joist to another or from joist to
supporting structure must be indicated. - Type and magnitude of axial forces at the joist
and Joist Girder end supports shall be shown on
the structural drawings. - Avoid resolving joist or Joist Girder axial
forces through the bearing seat connection.
65Diaphragm Chord
F
F
66Properly Applying Lateral Loads to Steel Joists
and Joist Girders
All top chord axial loads and end moments are
transmitted directly via the tie plates or tie
angles. The eccentricity of horizontal forces
transferred through the bearing seats is avoided.
M
F
e
F
67Joist Tie Plate
68Joist Tie Angles
69Lateral Load Resisting Systems Rigid Frames
70Rigid Frames End Moments
- The Specifying Professional is responsible for
the rigid frame design. Also, that unless
specially designed and detailed as wind only
flexible connections, rigid frame action will
induce live load moments, which need to be
specified. - Type and magnitude of end moments at the joist
and Joist Girder end supports shall be shown on
the structural drawings. - Avoid resolving joist or Joist Girder end moments
through the bearing seat connection. - The top and bottom chord moment connection
details shall be designed by the Specifying
Professional. The joist designer shall furnish
the Specifying Professional with the joist detail
information if requested.
71Rigid Frames Axial and End Moments
72Wind Bracing Kickers
73Wind Bracing Kickers
- Specifying Professional to provide horizontal and
vertical components of wind bracing forces being
transmitted to joists. - Specifying Professional to provide location of
attachment to joists, or if possible add note to
structural drawings to allow flexibility to
require attachment to nearest panel point.
74Roof Screens
- This Detail is Not Recommended
75Roof Screens Perpendicular to Joist
76Roof Screens Parallel to Joist
77Design of Bearing Seats to Resist Uplift Loads
- Research
- 2005 SJI Standard Specifications
- Recommended Design Procedure
78Typical Roof Framing using K-Series Open Web
Steel Joists
79End Bearing Seat Connections
80Profile of SJI Standard K-Series Open Web Steel
Joists
81Components of Uplift Resistance for Test Program
- Anchorage
- Weld
- Strength
- Ductility
- Seat Angle
- Strength
- Ductility
82Joist Seat Test Program Parameters
- Vary seat angle size (leg and thickness)
- S1 L 1 x 1 x 7/64
- S2 L 1-1/2 x 1-1/2 x 1/8
- S3 L 2 x 2 x 3/16
- S4 L 2 x 2 x 1/4
- Vary seat length
- 4, 6, 8 nominal
- Vary anchorage weld length
- 1, 3, 5 nominal
- Specimen Nomenclature SAS-SL-FWS-WL
83Typical Test Specimen Configuration
PULL PLATE
JOIST SEAT
ANGLES
3/4" BASEPLATE
9/16" DIA. HOLE FOR ¾ A325N BOLT ( 4 PLACES)
84Experimental Test Setup
85End View During and After TestTest Specimen
S3-4-1/8-3
0.30 in. Vertical Displacement at 6.5 kips
Applied Load
Failure Mechanism
86Typical Load-Deformation BehaviorTest Specimen
S3-4-1/8-3
87Profile and End View After TestTest Specimen
S1-6-1/8-1
Â
88Yield Line PatternsShort and Long Anchorage Welds
89Yield Line Analysis Model for Prediction of
Uplift Capacity
90Yield Line Analysis Using Virtual Work
We (Pu / 2) D We External Work Pu
Predicted ultimate uplift load D Distance
which the load moves thru Wi Mp q (Lyl) Wi
Internal Work Mp Plastic moment capacity of
plate, per unit length Fy Z q Angle
through which YL rotates Lyl Length of yield
line, the lesser of Lw pa and Ls
91Yield Line Analysis Using Virtual Work
Wi We 0 (Pu / 2) D - Mp q (Lyl) 0 But
since tan q q for small angles, q D /
a Solving for Pu gives Pu 2 Mp Lyl /
a Assumption of a 2.3 t provides
reasonably good prediction of ultimate uplift
strength of joist bearing seat
92Research Programs Recommendations
- The flexural resistance of K-Series joist bearing
seats can be predicted using a yield line
approach. - The yield line model is based on principles of
basic mechanics, not on empirical curve fitting. - A 5/32 fillet weld is adequate to develop the
flexural strength of the yield line.
932005 SJI Standard Specification for Open Web
Steel Joists, K-Series
- 5.6 END ANCHORAGE
- (b) Steel
- Ends of K-Series Joists resting on steel
supports shall be attached thereto with a minimum
of two 1/8 inch (3 millmeters) fillet welds 1
inch (25 millmeters) long, or with two 1/2 inch
(13 millimeters) ASTM A307 bolts, or the
equivalent. When K-Series Joists are used to
provide lateral stability to the supporting
member, the final connection shall be made by
welding or as designated by the specifying
professional. - (c) Uplift
- Where uplift forces are a design consideration,
roof joists shall be anchored to resist such
forces (Refer to Section 5.11 Uplift).
942005 SJI Standard Specification for Longspan
Steel Joists, LH-SeriesDeep Longspan Steel
Joists, DLH-Series
- 104.7 END ANCHORAGE
- (b) Steel
- Ends of LH- and DLH-Series Joists resting on
steel supports shall be attached thereto with a
minimum of two 1/4 inch (6 millmeters) fillet
welds 2 inches (51 millmeters) long, or with two
3/4 inch (19 millimeters) ASTM A307 bolts, or
the equivalent. When LH/DLH-Series Joists are
used to provide lateral stability to the
supporting member, the final connection shall be
made by welding or as designated by the
specifying professional. - (c) Uplift
- Where uplift forces are a design consideration,
roof joists shall be anchored to resist such
forces (Refer to Section 104.12 Uplift).
952005 SJI Standard Specification for Joist Girders
- 1004.6 END ANCHORAGE
- (b) Steel
- Ends of Joist Girders resting on steel supports
shall be attached thereto with a minimum of two
1/4 inch (6 millmeters) fillet welds 2 inches (51
millmeters) long, or with two 3/4 inch (19
millimeters) ASTM A307 bolts, or the
equivalent. In steel frames, bearing seats for
Joist Girders shall be fabricated to allow for
field bolting. - (c) Uplift
- Where uplift forces are a design consideration,
roof Joist Girders shall be anchored to resist
such forces (Refer to Section 1004.9 Uplift).
96ASD Design Procedure
- Pn 2 Mp Lyl / a
- Where
- Pn Nominal uplift capacity
- Mp Plastic moment capacity of plate per
unit length - Fy Z
- Z t2 / 4
- Lyl Length of yield line
- a 2.3 t
- W 1.67 (AISC-ASD safety factor for
bending) - Pn/W Allowable uplift strength
97LRFD Design Procedure
- Pn 2 Mp Lyl / a
- Where
- Pn Nominal uplift capacity
- Mp Plastic moment capacity of plate per
unit length - Fy Z
- Z t2 / 4
- Lyl Length of yield line
- a 2.3 t
- f 0.90 (AISC-LRFD resistance factor for
bending) - fPn Design uplift strength
98ASD and LRFD Design Example
Seat Angles L 1-1/2 x 1-1/2 x 1/8 Ls 4 Lw
2-1/2 Fy 50 ksi Allowable and Design
Uplift Strengths Z 0.125 2 / 4 0.00391
in.3 / in. a 2.3 (0.125) 0.28750 in. Lyl
2.50 p (0.2875) 3.403 in. lt Ls Mp
50 (0.00391) 0.1953 in.-kip / in. Pn
2 (0.1953)(3.403) / 0.2875 4.62 kips Pn/W
4.62 / 1.67 2.77 kips fPn 0.9
(4.62) 4.16 kips
99Recommended Bearing Seat Design to Resist Uplift
Loads
100Recommended Bearing Seat Design to Resist Uplift
Loads
101Recommended Bearing Seat Design to Resist Uplift
Loads
- The Pweld strength given in the preceeding tables
does not account for the transverse loading of
the weld due to uplift and thus could be
multiplied by 1.5. - Where a joist seat has been detailed for a bolted
connection, and for any reason the bolt is not
utilized, the empty slot in the bearing seat leg
severely diminishes uplift capacity. In such a
condition, if a weld and no bolt is to be used on
a slotted bearing seat, then the weld should be
applied within the empty slot.
102Typical Bolted Joist Connection
1032005 SJI Standard Specification for Open Web
Steel Joists, K-Series
- 5.11 UPLIFT
- Where uplift forces due to wind are a design
requirement, these forces must be indicated on
the contract drawings in terms of NET uplift in
pounds per square foot (Pascals). The contract
documents shall indicate if the net uplift is
based upon LRFD or ASD. When these forces are
specified, they must be considered in the design
of joists and/or bridging. A single line of
bottom chord bridging must be provided near the
first bottom chord panel points whenever uplift
due to wind forces is a design consideration. -
-
1042005 SJI Standard Specification for Longspan
Steel Joists, LH-SeriesDeep Longspan Steel
Joists, DLH-Series
- 104.12 UPLIFT
- Where uplift forces due to wind are a design
requirement, these forces must be indicated on
the contract drawings in terms of NET uplift in
pounds per square foot (Pascals). The contract
documents shall indicate if the net uplift is
based upon LRFD or ASD. When these forces are
specified, they must be considered in the design
of joists and/or bridging. A single line of
bottom chord bridging must be provided near the
first bottom chord panel points whenever uplift
due to wind forces is a design consideration.
1052005 SJI Standard Specification for Joist Girders
- 1004.9 UPLIFT
- Where uplift forces due to wind are a design
requirement, these forces must be indicated on
the contract drawings in terms of NET uplift in
pounds per square foot (Pascals). The contract
drawings must indicate if the net uplift is based
on ASD or LRFD. When these forces are specified,
they must be considered in the design of Joist
Girders and/or bracing. If the ends of the
bottom chord are not strutted, bracing must be
provided near the first bottom chord panel points
whenever uplift due to wind forces is a design
consideration.
106Design Example
- Building Location
- Near Orlando, FL in open terrain minimum slope
¼ / ft. - Topography Homogenous
- Exposure Category C (Sections 6.5.6.2 and
6.5.6.3) - Building Framing and Layout
- Flat roof system consisting of steel joists,
Joist Girders, and structural roof deck. CMU
walls on all four sides with debris-resistant
windows and door infill. Building has a parapet
height of less than 3-0 and is considered a
closed building. - Building Classification Building Category II
- Importance Factor 1.0 (Table 6-1)
107Design Example
- Dimensions
- Length, l 121-4
- Width, w 80-0
- Height, h 20-0 above the ground
- Roof slope is less than or equal to 5 degrees
- Roof live load deflection is based on L/240
- Design Roof Loads
- Dead Load, D 15.0 psf
- Roof Live Load, Lr 20.0 psf
- Total Load 35.0 psf
- Note 10 psf positive wind load is not used in
this example
108ASCE 7-05 Basic Wind Speed Map
ORLANDO
109Design Example
- Basic wind speed, from Figure 6-1b for Orlando,
Florida area V 110 mph. - Design approach is based on the Simplified
Procedure (Method 1) for both Components and
Cladding and Main Wind Force System since the
following conditions exist - Simple diaphragm building (Section C6.2).
- Building shape is basis and has a symmetrical
cross section in both directions and a flat roof. - There is no expansion joints in the building.
- Its a low-rise building with a mean roof height,
h less than 60 ft. and does not exceed the least
horizontal dimension (Section 6.2).
110Design Example
- Since the building has debris-resistant glazing
and has no dominant opening in any wall it can be
classified as a closed building. (Section
6.5.9.3). - Building has a regular shape.
- Rigid building, where height/width,
- w 20 ft./80 ft. 0.25 lt 4 (Section C6.2).
- The building is not subjected to the topographic
effects of Section 6.5.7 - No torsional effects meets Note 5 of Figure
6-10.
111Steel Joist and Joist Girder Layout
112Wind Zone Definitions
113Steel Joist Design
20K6 Rod Web _at_ 40-0 Considering no uplift -
2-0
18 _at_ 2-0
2-0
3-0
3-0
17 _at_ 2-0
Bottom Chord 2 angles 1.5 x 1.5 x 0.137, A
0.784 in.2 End Web 5/8 in. dia. round bar , A
0.307 in.2
114Steel Joist Design
20K6 Rod Web _at_ 40-0 With (net) uplift -
108 plf
84 plf
8-0
32-0
Bottom Chord 2 angles 1.5 x 1.5 x 0.155, A
0.882 in.2 End Web 7/8 in. dia. round bar , A
0.601 in.2
115Steel Joist Design
Design Data End Web, left end l 37.49 in.
Reduce to 90 for eccentricity at bearing seat
116Steel Joist Design
Design Data Bottom Chord, Pc 10.62 kips
4 rows (40)(12)/(41) 96 in.
117Joist Bridging
Bolted Diagonal Erection Bridging
Horizontal Bridging (typ.)
Bridging Needed for Uplift typical at both ends
(if necessary)
118Placement of Bridging to Resist Uplift Loads
20K6 Bridging Configuration Option 1
5 _at_ 8-0
Erection Stability Bridging
Uplift Bridging
A Common Alternative (not for this case)
4 Rows Equally Spaced
4 Rows Equally Spaced Between Uplift Bridging
119Placement of Bridging to Resist Uplift Loads
20K6 Bridging Configuration Option 2
2 _at_ 8-9
3 _at_ 7-6
7-0
7-6
7-0
7-6
5-0
Design Data Bottom Chord, 2 angles 1.5 x 1.5 x
0.137, A 0.784 in.2 Pc 10.62 kips
120Placement of Bridging to Resist Uplift Loads
At midspan of the joist
For compression, 7-6 space controls Pc 10.54
kips
121Placement of Bridging to Resist Uplift Loads
With revised bridging locations at the TC, check
spacing
Note The 51 ft. is the maximum spacing for four
rows of bridging and a No. 6 section number from
TABLE 5.4-1.
122Placement of Bridging to Resist Uplift Loads
20K6 Bridging Configuration Option 3
9.8 ft.
3 _at_ 6.8 ft.
9.8 ft.
5 Equal Spaces Between First BC Panel Points
5 _at_ 6.8 ft.
End TC space 9.8 ft.
123Joist Girder Bracing Placement
40G8N7K Middle Girder _at_ 40-0 Designed based on
2.62k/PP Uplift Loading (vs. approximately
3.4k/PP Uplift Loading from components and
cladding joist reactions)
No uplift design, i.e. net uplift load 0 1 knee
brace _at_ midspan to limit L/ryy lt 240
With 2.62k/PP uplift load, same Bottom Chord
angles 3 x 3 x 1/4, but now knee brace _at_ 15 ft.
and 25 ft. required.
With 3.4k/PP uplift load, same Bottom Chord
angles 3 x 3 x 1/4, but now 3 knee braces _at_ 10
ft., 20 ft., and 30 ft. required.
124Summary and Conclusions
- Wind forces can have a significant impact on the
design and use of steel joists and Joist Girders - The SJI Standard Specifications pertaining to
wind and uplift have been reviewed the wind load
requirements from ASCE 7-05 have been discussed
and the appropriate 2006 IBC load combinations
containing Wind have been presented. - Particular attention needs to be paid to
- Code specified and calculated wind forces
- Seat anchorage welds
- Joist bridging and Joist Girder bracing placement
125New Resource Soon Available
- SJI Technical Digest No. 6
- Structural Design of Steel Joist Roofs to Resist
Uplift Loads
126Any Questions?
SJI Website http//www.steeljoist.org