Title: Branch Circuits Section 11 Unit 33
1Branch CircuitsSection 11Unit 33
2Introduction
- For an electrical system to be as safe as
possible, all conductors, devices and connections
must follow the current National Electrical Code
(NEC). - Buildings without finished interior walls have
special requirements.
3Service Entrance Panel (SEP)
- The entrance panel (load center) is the entry
point for the electricity into the building. - The size (amp capacity) of the load center is
determined by the number of circuits and total
amp load for the building. - Current NEC regulations require that the load
center have a master disconnect. - The entrance panel must be grounded with a NEC
approved earth connection.
4Service Entrance Panel SEP Load Center
120/240 V Service
Service Entrance Neutral
Service Hot Conductors
Metal Box
Breaker
Non-conducting base
Grounding Bar
Non-conducting Attachment bars
Circuit Neutral Ground Connections
Conducting Attachment bars
Ground
Bonding Screw
Neutral
240 V Circuit
120 V
120 V
120 V Branch Circuit Hot (black) Conductor
Earth Ground
120 V Branch Circuit Ground (bare) Conductor
120 V Branch Circuit Neutral (white) Conductor
5SEP--cont.
- The 120/240 service is attached to the master
disconnect (breaker). - From master breaker each hot conductor is
connected to one of the conducting breaker bars. - The 120/240 neutral conductor is attached to the
grounding bar. - The grounding bar must be attached to an approved
earth ground.
- A 120 volt breaker attaches by snapping onto one
conducting and one non-conducting bar in the load
center. - For a 240 volt circuit two individual breakers
may be used and the levers are pined together or
a combination breaker may be used.
6Electrical Boxes
- All electrical connections must occur inside an
enclosure. - Electrical boxes are the most common type of
enclosure. - Hold conductors and conduit so stress cannot be
applied to the connections. - Attached to building for switches, fixtures and
other electrical devices. - Prevent mice and other vermin from chewing on and
nesting around electrical connections.
Boxes are available in plastic or steel,
rectangular or octagonal shapes, and different
widths and depths.
7Electrical Box Wiring Requirements
- Boxes must be securely fastened to building.
- Cable or conduct must be clamped to the box.
- Cables (conductors) must run inside walls, floors
and ceilings and be attached close to the box and
periodically along the length of the cable. - Metal boxes must be grounded.
- Wires must be connected to each other using
solderless connectors. - No more than one wire per terminal on switches,
receptacle and other electrical devices. Fig
33-4 not acceptable everywhere - Hot wires are attached to brass colored screws.
- Neutral wires are attached to aluminum colored
screws. - Ground wires are attached to green colored
screws. - When the white (neutral) conductor is used as a
hot conductor (switch loop) it must be marked
with black paint or tape. Fig 33-5
8Sizing Conductors
- When discussing the differences between series
and parallel circuits the assumption was made
that the conductors had no resistance. - This assumption can not be made when determining
conductor size. - Conductor size is based on voltage drop and
voltage drop is caused by resistance.
9Conductor Sizing
- Two systems are used to define the sizes of a
conductor - AWG
- cmils
- AWG
- Numbers run from 40 to 0000
- AWG numbers only apply to non-ferrous metals.
- The larger the number--the smaller the diameter
of the wire. - cmils
- Circular-mils (cmils) is a unit used to describe
the cross-sectional area of wire. - A mil 0.001 inch
- AWG sizes greater than 0000 are sized in
thousands of circular mils (kcmil)
- AWG 8 and higher are usually multiple strands.
- The diameter of multiple strand wire in cmils is
the cmils of each strand times the number of
strands.
10Conducting Materials
- All materials will conduct some electricity.
- Good conducting materials have low resistance.
- The resistance of a conductor depends on the
physical properties of the material (?), the
length (ft) of the conductor and the
cross-sectional area of the conductor (cmils). - Expressed in an equation
A cross-sectional area in cmils (diameter in
mils)2 1mil 0.001 in
11Example--Circular mills (cmils)
- What is the diameter (in) for a AWG 12 wire?
Electricity for Agricultural Applications, Bern
12Example--Resistance
- What is the resistivity of a 1/2 inch steel rod
that is 12 feet long? - Steel 100 ohm-cmil/foot
Electricity for Agricultural Applications, Bern
13Insulating Materials
- The required characteristics of electrical
insulation are - environmentally durable
- high dielectric strength.
Electricity for Agricultural Applications, Bern
- Electrical insulating materials are rated on
their dielectric strength. - Dielectric strength voltage per 0.001 inch of
thickness at which their resistance reaches a
breakdown point and they become conductors.
14Conductor Size
- The conductor size is determined by seven (7)
factors. - the load on the circuit
- the voltage of the circuit
- the distance from the load to the source
- the circuit power factor
- the type of current (phases)
- the ampacity of the conductor
- the allowable voltage drop
The type of insulation is determined by the
environment.
15Insulation
- The common types used in Agriculture are
Electricity for Agricultural Applications, Bern
16Environment--cont.
- The selection of insulation is very important
because the life of the conductor is usually
determined by the life of the insulation. - Conductors never wear out.
- Insulation deteriorates over time.
- Insulation reacts with oxygen, ammonia, oil,
gasoline, salts and water.
17Determining Conductor Size
- The first step is to determine answers for five
of the seven factors. These are - the load on the circuit
- the voltage of the circuit
- the distance from the load to the source
- the circuit power factor
- the type of current (phases)
- Once these are known, the remaining two factors
are used to determine the conductor size. - the ampacity of the conductor
- the allowable voltage drop
18Determining Conductor Size--cont.
- Circuit load
- The circuit load is the amperage used by the
electrical device, or the size of over current
protection device that will be used. - Circuit voltage
- Circuit voltage is the source voltage.
- Distance from source
- The distance between the source and the load is
not used as often as the run. - The run is the total amount of conductor that is
used to connect the load to the source. - Power factor
- The power factor for reactive loads is less than
one. - The power factor for resistance loads is equal to
one. - The number or phases must be know.
- Three phase current can use smaller diameter
wires.
19Determining Conductor Size--cont.
- Once values are known for the first five factors,
the last two are used to determine the minimum
conductor size. - Ampacity is the largest load that a conductor is
designed to carry regardless of length. - Voltage drop is the amount of energy that is lost
from the electricity passing through the
resistance of the conductors.
20Ampacity
- Ampacity refers to the current carrying ability
of the conductor. - Ampacity is dependent on the conductor
resistance, the allowable operating temperature
of the insulation and the heat dissipation
ability of the conductor. - Ampacity increases with conductor size.
- Ampacity for copper is higher than the ampacity
for aluminum. - Ampacity is higher for conductors which have
higher temperature ratings. - Exceeding the ampacity rating increases the heat
of the insulation. - The amount of damage that occurs is a function of
the amount of overload and the duration of the
overload. - Ampacity ratings for conductors can be determined
from tables such as 32-19.
21Ampacity-cont.
- Ampacity can be calculated, but tables such as
32-19 present this information in the left side
of the table. - Example what is minimum size of conductor with
TW insulation in conduit, operating on 120 volts
that should be used to carry 15 amps?
AWG 12
Note According to the NEC, 12 is smallest size
of wire that can be used under any conditions
using 120 V.
22Sizing Conductors by Voltage Drop
- Voltage drop is the result of a current passing
through a resistance. - Example
- What is the percent voltage drop at the service
entrance panel for the building in the
illustration?
23Example--cont.
- The first step is to determine the total
resistance of the circuit.
In this example the resistance for each conductor
is determined separately.
24Example--cont.
This circuit diagram illustrates the resistance
of the conductors.
25Example--cont.
- The next step is to determine the voltage drop
and the percentage drop. - Voltage drop is
- Percent voltage drop is
- This is an unacceptable voltage drop.
- Picking the wire size first must not be the best
way.
The conductor size is determined by calculating
the allowable resistance for the desired voltage
drop.
26Voltage Drop Example--cont.
- A voltage drop of 4.09 is excessive.
- Results of excessive voltage drop.
- The heat output of a resistance heater will
decrease more than 8 because power output is
proportional to the square of the voltage. - The useable light from an incandescent lamp will
drop about 10. - Five (5) possible solutions
- Decrease the load.
- Use larger conductors.
- Reduce the distance between the load and the
source. - Use a conductor that has a lower resistance.
- Use a higher voltage.
- Of these 5 options, number 2 and 5 are usually
the only practical solution.
27Voltage Drop Example--cont.
- If the voltage is increased to 240 V, what will
be the percent voltage drop?
- 2.04 is an acceptable loss for this electrical
service.
28Designing For Acceptable Voltage Drop
- Because all conductors have resistance, it can
not be eliminated from the circuit. - Therefore, circuits are designed for a specific
voltage drop. - Maximum of 2 in branch circuits is common
standard - NEC allows up to 3 maximum in branch circuit at
farthest power outlet - NEC allows 5 maximum drop in feeder and branch
circuit combined - Equation for calculating the conductor size for a
specified voltage drop
Note it is common practice to add 10 to the
length to account for the resistance of the
connections.
29Conductor Size Example
- Using the restivity equation, determine the size
of conductor that should be used to power an grow
lamp that draws 6.6 amps and is operating on
single phase and 120 volts. The grow lamp is
located 75 feet from the nearest source. Copper
conductors will be directly buried and a 2
voltage drop is acceptable. - The first step is to determine the minimum size
based on ampacity. - AWG 12 minimum recommended for all circuits.
- The next step is to determine the size based on
voltage drop by using the resistivity equation.
30Conductor Size Example-cont.
4705.39 cmil AWG 12 Ampacity 12 Voltage
Drop 12
Note 10 has been added for connections.
31Resistivity Equations
- Because of inductance in the conductor, the
equation for copper is usually changed for design
purposes to
- 22 constant for copper
- I Circuit load (amp)
- l Run (distance)
- E Allowable voltage drop (V)
- The resistivity equation for aluminum conductors
is changed to
Note in these equations the length is the one
way length, not the total length.
32Conductor Size Example 2
- Using the table method, determine the size of
copper conductor that should be used to provide
electrical service to a livestock building that
is located 70 feet from the source. The service
is 120 V and the estimated load for the building
is 35 amps. THW in conduct will be used.
Ampacity
8
Voltage drop
6
33Conductor Size Example 3
- Determine by calculation, using the standard
equation, the size of conductor that will be
required to provide service to a 120 V, 1-1/2 hp
water pump that is located 250 feet from its
source. The conductors with be copper and
directly buried. A 2 voltage drop is
acceptable. The motor has a power factor of
0.70. - The standard equation for copper requires values
for amperage, voltage and length. The value for
amperage must be determined first.
- 1 hp 746 watts, but when determining conductor
sizes for electric motors it is common practice
to use 1,000 watts per horsepower. - This accounts for motor efficiency.
34Conductor size 3--cont.
- For this circuit with a 8.75 load, the circular
mills of the conductors can be determined by
The conductor size is
AWG 6 26,240 cmil 8 16,510 cmil. 26,240
cmil gt 22,057 cmil gt 16,510 cmil Minimum
ampacity AWG 12 VD AWG 6 should be used.
35Conductor Sizing Example 4
- Determine the size of conductor that will be
required to supply a 40 amp load when TW wire in
conduct, will be used. The load is 25 feet from
the source. A 2 voltage drop is desired. - Based on ampacity
8
Voltage drop
8
36Conductor Sizing Conclusion
- For short distances, ampacity determines the
minimum conductor size. - For long distances, voltage drop determines the
minimum size.
Because long and short are relative terms, both
ampacity and voltage drop must be checked when
sizing conductors.
37Questions ?