Branch Circuits Section 11 Unit 33 - PowerPoint PPT Presentation

1 / 37
About This Presentation
Title:

Branch Circuits Section 11 Unit 33

Description:

Hot wires are attached to brass colored screws. ... What is the resistivity of a 1/2 inch steel rod that is 12 feet long? Steel = 100 ohm-cmil/foot ... – PowerPoint PPT presentation

Number of Views:203
Avg rating:3.0/5.0
Slides: 38
Provided by: harry2
Category:

less

Transcript and Presenter's Notes

Title: Branch Circuits Section 11 Unit 33


1
Branch CircuitsSection 11Unit 33
2
Introduction
  • For an electrical system to be as safe as
    possible, all conductors, devices and connections
    must follow the current National Electrical Code
    (NEC).
  • Buildings without finished interior walls have
    special requirements.

3
Service Entrance Panel (SEP)
  • The entrance panel (load center) is the entry
    point for the electricity into the building.
  • The size (amp capacity) of the load center is
    determined by the number of circuits and total
    amp load for the building.
  • Current NEC regulations require that the load
    center have a master disconnect.
  • The entrance panel must be grounded with a NEC
    approved earth connection.

4
Service Entrance Panel SEP Load Center
  • Master Disconnect

120/240 V Service
Service Entrance Neutral
Service Hot Conductors
Metal Box
Breaker
Non-conducting base
Grounding Bar
Non-conducting Attachment bars
Circuit Neutral Ground Connections
Conducting Attachment bars
Ground
Bonding Screw
Neutral
240 V Circuit
120 V
120 V
120 V Branch Circuit Hot (black) Conductor
Earth Ground
120 V Branch Circuit Ground (bare) Conductor
120 V Branch Circuit Neutral (white) Conductor
5
SEP--cont.
  • The 120/240 service is attached to the master
    disconnect (breaker).
  • From master breaker each hot conductor is
    connected to one of the conducting breaker bars.
  • The 120/240 neutral conductor is attached to the
    grounding bar.
  • The grounding bar must be attached to an approved
    earth ground.
  • A 120 volt breaker attaches by snapping onto one
    conducting and one non-conducting bar in the load
    center.
  • For a 240 volt circuit two individual breakers
    may be used and the levers are pined together or
    a combination breaker may be used.

6
Electrical Boxes
  • All electrical connections must occur inside an
    enclosure.
  • Electrical boxes are the most common type of
    enclosure.
  • Hold conductors and conduit so stress cannot be
    applied to the connections.
  • Attached to building for switches, fixtures and
    other electrical devices.
  • Prevent mice and other vermin from chewing on and
    nesting around electrical connections.

Boxes are available in plastic or steel,
rectangular or octagonal shapes, and different
widths and depths.
7
Electrical Box Wiring Requirements
  • Boxes must be securely fastened to building.
  • Cable or conduct must be clamped to the box.
  • Cables (conductors) must run inside walls, floors
    and ceilings and be attached close to the box and
    periodically along the length of the cable.
  • Metal boxes must be grounded.
  • Wires must be connected to each other using
    solderless connectors.
  • No more than one wire per terminal on switches,
    receptacle and other electrical devices. Fig
    33-4 not acceptable everywhere
  • Hot wires are attached to brass colored screws.
  • Neutral wires are attached to aluminum colored
    screws.
  • Ground wires are attached to green colored
    screws.
  • When the white (neutral) conductor is used as a
    hot conductor (switch loop) it must be marked
    with black paint or tape. Fig 33-5

8
Sizing Conductors
  • When discussing the differences between series
    and parallel circuits the assumption was made
    that the conductors had no resistance.
  • This assumption can not be made when determining
    conductor size.
  • Conductor size is based on voltage drop and
    voltage drop is caused by resistance.

9
Conductor Sizing
  • Two systems are used to define the sizes of a
    conductor
  • AWG
  • cmils
  • AWG
  • Numbers run from 40 to 0000
  • AWG numbers only apply to non-ferrous metals.
  • The larger the number--the smaller the diameter
    of the wire.
  • cmils
  • Circular-mils (cmils) is a unit used to describe
    the cross-sectional area of wire.
  • A mil 0.001 inch
  • AWG sizes greater than 0000 are sized in
    thousands of circular mils (kcmil)
  • AWG 8 and higher are usually multiple strands.
  • The diameter of multiple strand wire in cmils is
    the cmils of each strand times the number of
    strands.

10
Conducting Materials
  • All materials will conduct some electricity.
  • Good conducting materials have low resistance.
  • The resistance of a conductor depends on the
    physical properties of the material (?), the
    length (ft) of the conductor and the
    cross-sectional area of the conductor (cmils).
  • Expressed in an equation

A cross-sectional area in cmils (diameter in
mils)2 1mil 0.001 in
11
Example--Circular mills (cmils)
  • What is the diameter (in) for a AWG 12 wire?

Electricity for Agricultural Applications, Bern
12
Example--Resistance
  • What is the resistivity of a 1/2 inch steel rod
    that is 12 feet long?
  • Steel 100 ohm-cmil/foot

Electricity for Agricultural Applications, Bern
13
Insulating Materials
  • The required characteristics of electrical
    insulation are
  • environmentally durable
  • high dielectric strength.

Electricity for Agricultural Applications, Bern
  • Electrical insulating materials are rated on
    their dielectric strength.
  • Dielectric strength voltage per 0.001 inch of
    thickness at which their resistance reaches a
    breakdown point and they become conductors.

14
Conductor Size
  • The conductor size is determined by seven (7)
    factors.
  • the load on the circuit
  • the voltage of the circuit
  • the distance from the load to the source
  • the circuit power factor
  • the type of current (phases)
  • the ampacity of the conductor
  • the allowable voltage drop

The type of insulation is determined by the
environment.
15
Insulation
  • The common types used in Agriculture are

Electricity for Agricultural Applications, Bern
16
Environment--cont.
  • The selection of insulation is very important
    because the life of the conductor is usually
    determined by the life of the insulation.
  • Conductors never wear out.
  • Insulation deteriorates over time.
  • Insulation reacts with oxygen, ammonia, oil,
    gasoline, salts and water.

17
Determining Conductor Size
  • The first step is to determine answers for five
    of the seven factors. These are
  • the load on the circuit
  • the voltage of the circuit
  • the distance from the load to the source
  • the circuit power factor
  • the type of current (phases)
  • Once these are known, the remaining two factors
    are used to determine the conductor size.
  • the ampacity of the conductor
  • the allowable voltage drop

18
Determining Conductor Size--cont.
  • Circuit load
  • The circuit load is the amperage used by the
    electrical device, or the size of over current
    protection device that will be used.
  • Circuit voltage
  • Circuit voltage is the source voltage.
  • Distance from source
  • The distance between the source and the load is
    not used as often as the run.
  • The run is the total amount of conductor that is
    used to connect the load to the source.
  • Power factor
  • The power factor for reactive loads is less than
    one.
  • The power factor for resistance loads is equal to
    one.
  • The number or phases must be know.
  • Three phase current can use smaller diameter
    wires.

19
Determining Conductor Size--cont.
  • Once values are known for the first five factors,
    the last two are used to determine the minimum
    conductor size.
  • Ampacity is the largest load that a conductor is
    designed to carry regardless of length.
  • Voltage drop is the amount of energy that is lost
    from the electricity passing through the
    resistance of the conductors.

20
Ampacity
  • Ampacity refers to the current carrying ability
    of the conductor.
  • Ampacity is dependent on the conductor
    resistance, the allowable operating temperature
    of the insulation and the heat dissipation
    ability of the conductor.
  • Ampacity increases with conductor size.
  • Ampacity for copper is higher than the ampacity
    for aluminum.
  • Ampacity is higher for conductors which have
    higher temperature ratings.
  • Exceeding the ampacity rating increases the heat
    of the insulation.
  • The amount of damage that occurs is a function of
    the amount of overload and the duration of the
    overload.
  • Ampacity ratings for conductors can be determined
    from tables such as 32-19.

21
Ampacity-cont.
  • Ampacity can be calculated, but tables such as
    32-19 present this information in the left side
    of the table.
  • Example what is minimum size of conductor with
    TW insulation in conduit, operating on 120 volts
    that should be used to carry 15 amps?

AWG 12
Note According to the NEC, 12 is smallest size
of wire that can be used under any conditions
using 120 V.
22
Sizing Conductors by Voltage Drop
  • Voltage drop is the result of a current passing
    through a resistance.
  • Example
  • What is the percent voltage drop at the service
    entrance panel for the building in the
    illustration?

23
Example--cont.
  • The first step is to determine the total
    resistance of the circuit.

In this example the resistance for each conductor
is determined separately.
24
Example--cont.
This circuit diagram illustrates the resistance
of the conductors.
25
Example--cont.
  • The next step is to determine the voltage drop
    and the percentage drop.
  • Voltage drop is
  • Percent voltage drop is
  • This is an unacceptable voltage drop.
  • Picking the wire size first must not be the best
    way.

The conductor size is determined by calculating
the allowable resistance for the desired voltage
drop.
26
Voltage Drop Example--cont.
  • A voltage drop of 4.09 is excessive.
  • Results of excessive voltage drop.
  • The heat output of a resistance heater will
    decrease more than 8 because power output is
    proportional to the square of the voltage.
  • The useable light from an incandescent lamp will
    drop about 10.
  • Five (5) possible solutions
  • Decrease the load.
  • Use larger conductors.
  • Reduce the distance between the load and the
    source.
  • Use a conductor that has a lower resistance.
  • Use a higher voltage.
  • Of these 5 options, number 2 and 5 are usually
    the only practical solution.

27
Voltage Drop Example--cont.
  • If the voltage is increased to 240 V, what will
    be the percent voltage drop?
  • 2.04 is an acceptable loss for this electrical
    service.

28
Designing For Acceptable Voltage Drop
  • Because all conductors have resistance, it can
    not be eliminated from the circuit.
  • Therefore, circuits are designed for a specific
    voltage drop.
  • Maximum of 2 in branch circuits is common
    standard
  • NEC allows up to 3 maximum in branch circuit at
    farthest power outlet
  • NEC allows 5 maximum drop in feeder and branch
    circuit combined
  • Equation for calculating the conductor size for a
    specified voltage drop

Note it is common practice to add 10 to the
length to account for the resistance of the
connections.
29
Conductor Size Example
  • Using the restivity equation, determine the size
    of conductor that should be used to power an grow
    lamp that draws 6.6 amps and is operating on
    single phase and 120 volts. The grow lamp is
    located 75 feet from the nearest source. Copper
    conductors will be directly buried and a 2
    voltage drop is acceptable.
  • The first step is to determine the minimum size
    based on ampacity.
  • AWG 12 minimum recommended for all circuits.
  • The next step is to determine the size based on
    voltage drop by using the resistivity equation.

30
Conductor Size Example-cont.
4705.39 cmil AWG 12 Ampacity 12 Voltage
Drop 12
Note 10 has been added for connections.
31
Resistivity Equations
  • Because of inductance in the conductor, the
    equation for copper is usually changed for design
    purposes to
  • 22 constant for copper
  • I Circuit load (amp)
  • l Run (distance)
  • E Allowable voltage drop (V)
  • The resistivity equation for aluminum conductors
    is changed to

Note in these equations the length is the one
way length, not the total length.
32
Conductor Size Example 2
  • Using the table method, determine the size of
    copper conductor that should be used to provide
    electrical service to a livestock building that
    is located 70 feet from the source. The service
    is 120 V and the estimated load for the building
    is 35 amps. THW in conduct will be used.

Ampacity
8
Voltage drop
6
33
Conductor Size Example 3
  • Determine by calculation, using the standard
    equation, the size of conductor that will be
    required to provide service to a 120 V, 1-1/2 hp
    water pump that is located 250 feet from its
    source. The conductors with be copper and
    directly buried. A 2 voltage drop is
    acceptable. The motor has a power factor of
    0.70.
  • The standard equation for copper requires values
    for amperage, voltage and length. The value for
    amperage must be determined first.
  • 1 hp 746 watts, but when determining conductor
    sizes for electric motors it is common practice
    to use 1,000 watts per horsepower.
  • This accounts for motor efficiency.

34
Conductor size 3--cont.
  • For this circuit with a 8.75 load, the circular
    mills of the conductors can be determined by

The conductor size is
AWG 6 26,240 cmil 8 16,510 cmil. 26,240
cmil gt 22,057 cmil gt 16,510 cmil Minimum
ampacity AWG 12 VD AWG 6 should be used.
35
Conductor Sizing Example 4
  • Determine the size of conductor that will be
    required to supply a 40 amp load when TW wire in
    conduct, will be used. The load is 25 feet from
    the source. A 2 voltage drop is desired.
  • Based on ampacity

8
Voltage drop
8
36
Conductor Sizing Conclusion
  • For short distances, ampacity determines the
    minimum conductor size.
  • For long distances, voltage drop determines the
    minimum size.

Because long and short are relative terms, both
ampacity and voltage drop must be checked when
sizing conductors.
37
Questions ?
Write a Comment
User Comments (0)
About PowerShow.com