Title: ME31B: CHAPTER FOUR
1ME31B CHAPTER FOUR
- DESIGN OF STRUCTURAL MEMBERS
2DESIGN OF MEMBERS IN DIRECT STRESS
- Structural members under direct stress are
mainly ties, cables, and short columns.
3(No Transcript)
4Solution Concluded
5Design of Short Columns
6Example
- A square concrete column(pier) which is 0.5 m
high is made of a nominal concrete mix of 124,
with a permissible direct stress of 5.3 N/mm2.
What is the required cross-sectional area if the
column is required to carry an axial load of 300
kN? - Solution
- Area Force/stress 300 x 103 N 56600
mm2 - 5.3
N/mm2 - ie. the column should be minimum 240 mm
square.Â
7(No Transcript)
8Note
- Maximum compressive stress (fc) occurs in the
section where the bending moment is maximum. In
the design of simple beams, section modulus (Z)
should be selected such that fc does not
exceed the allowable value. Allowable working
stress values can be found in building codes or
Engineering handbooks. - For safe bending, fw gt f Mmax/Z
where fw is the allowable bending stress f is
the actual stress and Mmax is the maximum bending
moment.
9(No Transcript)
10b)Â Â Â Â Deflection of Beams
- Excessive deflections cause cracking of plaster
in ceiling and can lead to jamming of doors and
windows. - Most building codes limit the amount of
allowable deflection as a - proportion of the member's length ie. 1/180 ,
1/240, or 1/360 of the length.
11(No Transcript)
12(No Transcript)
134.2.1 Steps in the Design of Simple beams
- a) Calculate loading on the beam
- b) Calculate the bending moment, shear forces,
etc. - c) For the maximum bending moment (Mmax),
provide a suitable section - Z Mmax/fw , fw is allowable stress
(from tables). - d) Check for shear stress, deflection and
buckling of web if necessary.
14Example
- Consider a floor where beams are spaced at 1200
mm and have a span of 4000 mm. The beams are
seasoned cypress with the following properties
fw 8 N/mm2 , E 8400 N/mm 2 ,
density 500kg/m3 . Loading on floor and
including floor is 2.5 kN/m2 . Allowable
deflection is L/240. Design the beam. Allowable
shear stress is 0.7 N/mm2
15 16(No Transcript)
17(No Transcript)
18(No Transcript)
194.2.2 Bending Moment Caused By Askew Loads
- When the resulting bending moment on a beam is
not about one of the axis, the moment need be
resolved into components acting about the main
axis. - The stresses are then calculated separately
relative to each axis and the total stress is
found by adding the stresses caused by the
components of the moment.
20Roof Truss Showing Purlin
21Example
- Design a timber purlin, which will span rafters
2.4 m on centre. The angle of the roof slope is
30 and the purlin will support a vertical dead
load of 250 N/m and a wind load of 200 N/m acting
normal to the roof. The allowable bending
stress(fw ) for the timber used is 8 N/mm 2 .
The timber density is 600 kg/m3 -
22Forces in the Purlin
23Solution
- Assume a purlin cross sectional size of 50 x 125
mm - i) Find an estimated self load
- w 0.05 m x 0.125 m x 600 kg/m3 x 9.81
37 N/m - Total dead load 250 37 287 N/m
- ii) Find the components of the loads relative to
the main axes - wx 200 N/m 287 N/m cos 30 448.5
N/m - wy 287 N/m sin 30 143.5 N/m
24Solution Contd.
- iii) Calculate the BM about each axis for a udl.
The purlin is assumed to be a simple beam - Mmax w L 2 /8
- Mmax x wx L2 448.5 x 2.42
- 8 8
- 323 x 103 N mm
- Mmax y wy L2 143.5 x 2.42
- 8
8 - 103 x 10 3 N mm
25Solution Contd.
- iv) The actual stress in the timber must be less
than the allowable stress. - f Mmax x Mmax y lt fw
- Zx Zy
- v) Try the assumed purlin size of 50 x 125 mm
- Zx b d2 50 x 1252 130 x
10 3 mm3 - 6 6
26Solution Concluded
274.2.3 Design Using the Universal Steel Beams
28(No Transcript)
29Example
- A steel beam used as a lintel over a door opening
is required to span 4.5 m between centres of
simple supports. The beam will carry a 220 mm
thick and 3.2 m high brick wall, weighing 20
kN/m3 . Allowable bending stress is 165 N/mm2.
Assume allowable shear stress of 100 N/mm2, E is
2 x 105 N/mm2. Assume self weight of the
beam as 1.5 kN.
30(No Transcript)
31With Z 221 cm3 and I
2070 cm4 , From SDM, choose a UB 254 x 102
x 22 with Z 225 .4 cm3 and I 2863
cm4Check for shear stress Shear stress
Qmax
D. tFrom Table 4.4.
Q max W /2 32.43 kN Shear stress
32.43 x 103 N 22.01
N/mm2 254 mm x 5.8 mmSince 22.01 N/mm2 lt
the allowable shear stress of 100 N/mm2 ,
ie. Beam is very satisfactory.
USE UB 254 x 102 x 22
32(No Transcript)
33Composite Beams
344.3 DESIGN OF COLUMNS
- Columns are compression members but the manner in
which they tend to fail and the amount of load
which causes failure depend on - i) The material of which the column is made eg.
a steel column can carry a greater load than
timber column of similar cross-sectional size. - ii) The shape of the cross-section of the
column. A column having high c/s area compared
to the height is likely to fail by crushing
rather than by buckling.
35Columns Contd.
- iii) The end conditions of the column.
- To account for buckling of slender columns, the
allowable compressive strength is reduced by a
factor k , which depends on the slenderness
ratio and the material used. - Pbw k . cw . A where Pbw is the
allowable load wrt buckling - k is the reduction factor which depends on the
slenderness ratio and - A is the cross-sectional area of the column.
364.3.2 Slenderness Ratio
- Slenderness ratio can be defined as
- k L l
- r rÂ
- Where is slenderness ratio
- k is effective length factor whose value depends
on how the ends of the column are fixed - L is the length of the column r is the radius of
gyration (r I/A and l is the effective
length of the columns (k. l)
374.3.3 Types of End Conditions of a Column
- Columns can either be
- (a) fixed in position nor direction (the weakest
condition) - (b) fixed in position but not in direction
(pinned) - (c) fixed in direction but not in position
- (d) fixed in position and in direction
38(No Transcript)
394.3.4 Design of Axially Loaded Timber Columns
- Timber columns are designed with the following
formulae - k L and Pbw k . cw.
A - r
- NB In some building codes, a value of
slenderness ratio in case of sawn timber is taken
as l/b instead of l/r - Â
40Example
- Design a timber column which is 3 m long with a
compressive load of 15 kN. Allowable compressive
stress ( cw) for the timber is 5.2 N/mm2, kp
is 1.00
41(No Transcript)
42(No Transcript)
43(No Transcript)
44Note
- Actual load/allowable load
- 15 kN/16.9 kN 0.89
- This ratio is all right and shows that the
section is economical. - A ratio of 0.85 to 1.00 is acceptable.
454.3.5 Design of Axially Loaded Steel Columns
- The allowable loads for steel with respect to
buckling can be calculated in the same manner as
for timber. - The relationship between the slenderness ratio
and the reduction factor ( k ) is slightly
different (see Table 4.6).
46(No Transcript)
47(No Transcript)
48(No Transcript)
49(No Transcript)
50(No Transcript)
51(No Transcript)
52Solution Concluded
534.3.7 Axially Loaded Concrete Columns
- Most building codes allow the use of plain
concrete (no reinforcement) only in short columns
ie. where the l/r ratio is lt 15 . - For l/r between 10 and 15, the allowable
compressive strength must be reduced. - The tables of figures relating to l/b in place
of a true slenderness ratio are only approximate,
since radii of gyration depend on both b and d
values in the cross section and must be used with
caution.
54Example
- A concrete column, with an effective length of 4
m has a cross section of 300 x 400 mm. Calculate
the allowable axial load, if a nominal concrete
mix is 124 is to be used. - Solution Slenderness ratio, l/b 4000/300
13.3 - Hence Table 4.7, gives Pcc 3.47 N/mm2 by
interpolation. - Pw Pcc . A 3.47 x 300 x 400
- 416.4 kN
55(No Transcript)
564.3.8 Plain Centrally Reinforced Concrete
Walls
- Walls are designed in the same manner as columns,
but there are a few differences. - A wall is different from a column by having a
length which is more than five times its
thickness. - Plain concrete walls should have a minimum
thickness of 100 mm.
57Plain and Reinforced Concrete Walls Contd.
- Where the load is eccentric, the wall must have
centrally placed reinforcement of at least 0.2
of the cross section if the eccentricity gt 0.20. - This reinforcement may not be included in the
load carrying capacity of the wall.
58Example
- Determine the maximum allowable load per metre of
a 120 mm thick wall, with an effective height of
2.8 m and made from concrete grade C 15 (a)
when the load is central and (b) when the load
is eccentric by 20 mm.
59(No Transcript)
60(No Transcript)
61(No Transcript)
62(No Transcript)
63(No Transcript)
644.4 DESIGN OF ROOF TRUSSES
65Roof Trusses Contd.
- Steel and timber trusses are usually designed
assuming pin-jointed members. In practice,
timber trusses are assembled with bolts, nails - or special connectors and steel trusses are
bolted, riveted or welded. - These rigid joint impose secondary stresses which
are negligible and therefore not used in design.
664.4.2 Steps in Designing a Truss
- a) Select general layout of truss members and
truss spacing - b) Estimate external loads to be applied
including self weight of truss, purlins and roof
covering, together with wind loads. - c) Determine the critical (worst combinations)
loading. It is usual to consider dead loads
alone, and then dead and imposed load combined.
67Steps in Designing a Truss Contd.
- d) Analyse framework to find forces in members.
- e) Select material and section to provide in
each member a stress value which does not exceed
the permissible value.
68(No Transcript)
69(No Transcript)
704.4.2.1 Spacing and Layout
- Roof trusses should as far as possible be spaced
to achieve a minimum of weight and economy of
materials used in the total roof structure. -
- For spans up to 20 m, the spacing of steel
trusses is likely to be about 4 m, and in case of
timber, 2m.
71Spacing and Layout Contd.
- Short spans up to 8 m should have pitched timber
rafters or light weight trusses either pitched or
flat. Medium spans of 7 to 15 m or 16 m require
truss frames designed of timber or steel. - Long spans of over 16 m should if possible be
broken into small units or the roofs should be
designed by specialists.
72Pitch or Slope of a Roof
73Estimation of Roof Loads
74Example
- Determine the critical forces for design for each
of the members in the left hand of the truss
shown above. Assume the following Trusses are
spaced 4 m on centres. The roof deck is of
galvanised sheet weighing 6 kg/m2 . All purlins
weigh 22kg/m. Openings constitute 20 of the
wall surface. Calculate the panel loads.
75Solution
- (a) Dead load
- i) Determine the panel area supported by one
purlin - Distance between the purlins x spacing of
trusses 3.2 m x 4 m 12.8 m2 - ii) Calculate the roof deck load supported by
one purlin - 12.8 m 2 x 6 kg/m 2 x 9.81 753.4
N 0.75 kN. - iii) Weight of each purlin 22 kg/m x 4 m x
9.81 863.28 N 0.86 kN
76Solution Contd.
- Total dead load to be carried by truss
- 0.75 0.86 kN 1.61 kN
- iv)Estimate total truss weight per panel as 10
of the total load to be carried 0.16 kN - v) Total dead load per panel point , P 1.61
0.16 1.77 kN
77(No Transcript)
78Solution Contd.
79(No Transcript)
80(No Transcript)
81(No Transcript)
82(No Transcript)
83(No Transcript)
84(No Transcript)
85(No Transcript)
86Final Design Diagram
874.5 FOUNDATIONS AND FOOTINGS DESIGN
- 4.5.1 Introduction Foundation is the part of
the structure through which the load of the
structure is transmitted to the ground. - A combination of footing and foundation
distributes the load on the bearing surface (the
soil) and keeps the building level and plumb and
reduces settling to a minimum. - Footing and foundation are normally made of
concrete, no matter the construction material.
88Footing and Foundation Contd.
- Before design of footing and foundation can be
made, the total load from the building as well as
soil bearing characteristics should be
determined.
89 Soil Bearing Capacity
- Strength of the soil required to resist the loads
resting in it. - This is after the top soil has been removed (See
Table 5.6, FAO book for values of soil bearing
capacities). Detailed investigations of the soil
is not usually required for small scale buildings
90Soil Bearing Capacities
914.5.3 Foundation Footings
- 4.5.3.1 Description A footing is an
enlarged base for a foundation designed to
distribute the building load over a larger area
of soil and to provide a firm, level surface for
constructing the foundation wall.
Foundation wall
Footing
92Footings and Foundation Contd.
- The footing is wider than the foundation wall
because the soil's bearing stress is less than
that of the material (concrete) of the wall e.g.
concrete has a strength of about 1000 kN/m2 . - A 1 3 5 ratio of cement, dry sand, and
gravel is suggested for footings with 31 litres
of water per 50 kg sack of cement.
93(No Transcript)
94Note
- Unlike the continuous wall footings, the pier and
column footings are heavily loaded. - It is very important to correctly estimate the
proportion of building load to be carried by each
pier or column. - If wall footings are very lightly loaded, it is
advisable to design any pier or column footings
required for the building with approximately the
same load per unit area. - If any settling occurs, it should be uniform
throughout.
95Example
- For the building below, the loads are as follows
- a) The roof framing plus the expected wind load
130 kN - b) The wall above the foundation is 0.9 kN/m
- c) The floor will be used for grain storage and
will support as much as 7.3 kN/m2 . The floor
structure is an additional 0.5 kN/m2 - The foundation walls and piers are each 1 m high
above the footing. The wall is 200 mm thick and
the piers 300 mm square. The soil on the site is
compacted clay in a well drained area. Find the
size of the foundation and pier footing that will
safely support the loads. Assume that the weight
of the mass 1 kg approximately equals 10 N. The
mass of concrete is 24 kN/m3.
96(No Transcript)
97Solution
- Note that each pier(column) carries 4/32 ie.
1/8 of total floor load. Each wall carries 7/32
of floor load ie. (2 x 3) 1/2 1/2 - 1) The division of load on each foundation wall
is as follows - a) Roof load 50 on each wall i.e. 50 of
130 kN 65 kN - b) Wall load for each side 16 m x 0.9
kN/m 14.4 kN - c) Floor load each side of wall carries 7/32
- Total floor load (7.3 0.5) x 16 x 8
998.4 kN - i.e. floor load carried by each wall 7/32 x
998 kN 218.4 kN
98Solution Contd.
99(No Transcript)