CATSHV SATURATED LOAD STUDY
CATSHV
12
to Winchester
LEGEND
EXISTING LINE EXISTING BUS NEW CATSHV BUS
230kV LINE 500kV LINE
N
.
LOOP
230
2CATS HV Saturated Load StudyPhase 1 Existing
System
3CATS HV Saturated Load StudyPhase 2 Proposed
Substations
4CATS HV Saturated Load StudyPhase 3 Receiving
Station areas
5CATS HV Saturated Load StudyPhase 4 Generation
Transmission
6CATS HV Saturated Load StudyGeneration Dispatch
7CATS HV Saturated Load StudyLoads
- Loads distributed at existing and proposed
substations - 50 load case 5199 MW
- 75 load case 7799 MW
- 100 load case 10399 MW
8CATS HV Saturated Load StudyPreliminary N-0
50, 75, and 100 load findings
- Added elements do not overload
- N-0 Overloads (rtg 1) 100 load case
- Coolidge-Sundance 230kV line (115)
- Santa RosaCats01 230kV line (118)
- (loop in of existing Santa Rosa-Tatmomli-Saguaro
230kV line) - Cholla-Saguaro 500kV line (157)
9CATS HV Saturated Load StudyPreliminary N-1
50, 75, and 100 load findings
- Overload Issues
- Numerous Severe (rtg 2) mostly outside study
region! - Overloads to note (for 100 load case)
- Jojoba-Kyrene 500kV line (103) for loss of Pinal
West Santa Rosa 500kV - Pinal West Santa Rosa 500kV line (132) for
loss of Jojoba-Kyrene - TestTrack-Casa Grande 230kV (146) for loss of
Casa Grande Desert Basin 230kV - Coolidge-Sundance 230kV (180) for loss of
parallel line, was 115 in base case
10CATS HV Saturated Load StudyNext Steps
- Further Analyze 50, 75 and 100 cases
- Draft Report for 1/12/06 Meeting
- Final report for 1/31/06 submittal to ACC