Title: 19.4.4 Design Example
119.4.4 Design Example
- Select resonant tank elements to design a
resonant inverter that meets the following
requirements - Switching frequency fs 100 kHz
- Input voltage Vg 160 V
- Inverter is capable of producing a peak open
circuit output voltage of 400 V - Inverter can produce a nominal output of 150 Vrms
at 25 W
2Preliminary calculations
- The requirements imply that the inverter tank
circuit have an open-circuit transfer function of
The required short-circuit current can be found
by solving the elliptical output characteristic
for Isc
hence
Use the requirements to evaluate the above
3Matched load
- Matched load therefore occurs at the operating
point
Hence the tank should be designed such that its
output impedance is
4Solving for the tank elements
- Lets design an LCC tank network for this example
The impedances of the series and shunt branches
can be represented by the reactances
5Analysis in terms of Xs and Xp
- The transfer function is given by the voltage
divider equation
The output impedance is given by the parallel
combination
Solve for Xs and Xp
6Evaluate tank element values
- The capacitance Cp should therefore be chosen as
follows
The reactance of the series branch should be
7DiscussionChoice of series branch elements
- The series branch is comprised of two elements L
and Cs, but there is only one design parameter
Xs 733 ?. Hence, there is an additional degree
of freedom, and one of the elements can be
arbitrarily chosen. - This occurs because the requirements are
specified at only one operating frequency. Any
choice of L and Cs, that satisfies Xs 733 ?
will meet the requirements, but the behavior at
switching frequencies other than 100 kHz will
differ. - Given a choice for Cs, L must be chosen according
to
For example, Cs 3Cp 3.2 nF leads to L 1.96
µH
8Rcrit
- For the LCC tank network chosen, Rcrit is
determined by the parameters of the output
ellipse, i.e., by the specification of Vg, Voc,
and Isc. Note that Zo? is equal to jXp. One can
find the following expression for Rcrit
Since Zo0 and H ? are determined uniquely by the
operating point requirements, then Rcrit is also.
Other, more complex tank circuits may have more
degrees of freedom that allow Rcrit to be
independently chosen. Evaluation of the above
equation leads to Rcrit 1466 ?. Hence ZVS for
R lt 1466 ?, and the nominal operating point with
R 900 ? has ZVS.
9(No Transcript)
10(No Transcript)
11(No Transcript)
12(No Transcript)
13(No Transcript)