AEE presentation - PowerPoint PPT Presentation

1 / 24
About This Presentation
Title:

AEE presentation

Description:

Why were these projects successful? Lumen Maintenance of Lamp ... Eurostar station, Brussels (Belgium) No disturbances to heavy passenger traffic. LED VS Neon ... – PowerPoint PPT presentation

Number of Views:58
Avg rating:3.0/5.0
Slides: 25
Provided by: usb95
Category:

less

Transcript and Presenter's Notes

Title: AEE presentation


1
AEE presentation
  • Lighting Technologies
  • T5, T8, Ceramic MH,
  • Induction, LED
  • Successful projects
  • Why were these projects successful?

2
Lumen Maintenance of Lamp Families
100
T8 HV T5
95
MasterColor
85
90
Percent Lumen Maintenance
80
Pulse Start
75
70
60
Standard MH
60
0
1
2
3
4
5
6
7
8
Lamp Life - Hours (000's)
3
T5HO Ballasts
  • 400 Watt Metal Halide VS 4 Lamp T5HO
  • Lamp Type Wattage
  • 400 W MH 458 Watts
  • 4 T5HO Lamps 234 Watts
  • Watts Saved 224 Watts

4
HID to T5HO Fluorescent
  • Existing system 35 fixtures 250watt Metal
    Halide 25-30 footcandles - with 295 watts per
    fixture.
  • New system 21 fixtures 2x4 6lamp T5HO 50-60
    footcandles with 351 watts per fixture.

Before
After
5
HID to T5HO Fluorescent
  • Existing system 120 fixtures 400watt High
    Pressure Sodium 20 to 40 footcandles 455
    watts per fixture no motion sensors.
  • New system 120 fixtures 2x4 4lamp T5HO 30 to
    40 footcandles 234 watts per fixture with
    motion sensors in aisle areas employees thought
    light level was doubled.

Before
After
6
T5HO Ballasts
  • Whats available today?
  • 2 lamp
  • 2 lamp with 90 degrees C case temp rating
  • 2 lamp, 347-480 Volt with 90 degrees C case temp
    rating
  • 4 lamp, bi-level switching with 90 degrees C case
    temp rating (120-277V Version 347-480V Version)

7
T5 Fluorescent Lamps
Lumens vs. Ambient Temperature
100
90
T5, T5HO
80
T12, T8,T5 Circular
Percent Lumens
70
60
50
15
20
25
30
35
40
45
50
55
Ambient Temperature (ºC)
8
Before Lighting Retrofit
After Lighting Retrofit
9
System Comparison
  • 400 watt MH
  • 458 system watts
  • 65CRI
  • 20,000 hour rated life
  • 6 F32T8TL850ALTO with Advance Hi-Output
    electronic ballast 1.2BF
  • 228 system watts
  • 86CRI
  • 25,000 hours rated life
  • Instant on instant restrike

10
Lamp varieties
  • 4T8 lamps, 32 watts, 30 watts, 28 watts, 25
    watts
  • Rated life varies 20,000, 24,000, up to 36,000
    hours
  • Varied lumen package 2400 lumens to 3100 lumens
  • 57 and 70 watt triple tube CFL, 4pin
  • PL-H 4P, 60, 85 and 120 watts
  • 4000, 6000 and 9000 lumens, 20,000 hrs

11
Electronic Ballast varieties
  • Instant Start BF .75. .88, 1.2, 1.32
  • Programmed Start BF .88
  • Energy Efficient IS BF.78, .88
  • Energy Efficient PS BF.78, .88
  • Various combinations of lamps and ballasts for
    lumens and watts and to maximize lamp life.

12
Ceramic Metal Halide
  • Project Parking structure using HPS150
  • Goal convert to White Light (Hospital)
  • Replaced each HPS 150 188 system watts
  • With MHC100/4K electronic HID ballast 110 system
    watts
  • Used coated lamp clear was too bright!!

13
Ceramic Metal Halide
  • HPS150
  • 188 system watts
  • 16,000 lumens
  • CRI 21
  • Life 24,000 hours
  • MHC100/4K
  • 110 system watts
  • 9,000 lumens
  • CRI 92
  • Life 20,000 hours

14
DynaVision Overview
  • 320/350/400 selectable tri-watt pulse-start MH
  • Operates all lamps at rated wattage, regardless
    of
  • Line voltage variation
  • Lamp voltage rise over life
  • 200-277V 50/60Hz applications
  • 120kHz, 2-stage with microprocessor
  • Cost efficient
  • Programmable
  • Size efficient 5¼ x 8 x 2½

15
DynaVision Performance
MH400BU-PS (pulse-start) on DynaVision
MH400BU-PS (pulse-start)
MH400U (probe-start)
16
10 Yr. Cost Comparison
17
DynaVision Standard Features
  • 0-10v continuous dimming (to 50 power minimum)
  • Includes required 15min lamp warm up _at_ 100 power
  • Customer can use any compatible 0-10V dimming
    controls for further energy savings / day-light
    harvesting
  • Could do simple bi-level dimming by opening /
    shorting dimming leads
  • 120v / 250w tap relay for quartz aux.lamp
  • Lamp connects directly to two dedicated ballast
    leads
  • Ballast controls lamp directly no addl relay
    or control needed
  • Quartz lamp automatically shut off when HID lamp
    power reaches 50

18
  • Vessel
  • Power Coupler
  • High Frequency Generator

19
QL Lamp System
  • Complete Revolution in Lighting Technology
  • Electrodeless Lamp results in an amazing 100,000
    hour rated life
  • Best choice for difficult, costly, or hazardous
    areas
  • Resembles PL-T except uses a (HF) Generator and
    Inductive Power Coupler with the Discharge Vessel

20
Induction Lighting
  • Caltrans replacing
  • 175MV 205 watts
  • With 85 watts induction
  • 24,000hrs/100,000hrs
  • 7900lumens/6000
  • CRI 20/82

21
Eurostar station, Brussels (Belgium)
  • No disturbances to heavy passenger traffic

22
LED VS Neon
  • 60 NEON
  • 234 watts
  • high voltage
  • glass
  • 60 LED
  • _at_60 watts
  • 42 V power supply
  • Polycarbonate composite

23
LED Advantages vs Neon
  • All weather
  • Low heat
  • Easy to maintain plug and play
  • Power wash clean
  • 42V power supply
  • 80 NRG savings 1.52 watts/sq.ft.
  • Up to 10 yrs. Maint. free

24
LED
  • Red, Yellow, Amber, Orange NEON
  • Green, Blue, White ½-2X NEON
  • Can be expensive on front endsavings is in
    maint. and safety
  • Cannot be field cut custom order
  • Up to 45degree bend
  • 50,000 hr life at 70 lm
Write a Comment
User Comments (0)
About PowerShow.com