Title: Resistance to Internal Faults
1Resistance to Internal Faults
Martin SchaakOlaf BischurThomas Stommel
2Topics
- Resistance to internal faults
- Causes and physical effects
- Basic standard IEC 62271-200
- Test object NXPLUS C
- Live test
- Analysis and review
- Open questions
3Causes of Internal Faults
- Ageing of insulating materials under electrical
stress - Corrosion
- Overstressing
- Ferroresonance, overvoltages
- Defective installation, incorrect maintenance
- Maloperation
- Pollution, humidity, small animals penetrating in
the switchgear
4Electrical Accidents
Reported electrical accidents in the sphere of
activity of BGFE
80
Electrical effects of high voltage
67.5
Institute for the research of electrical accidents
60
1996-2000
49.3
47.1
2001-2005
40
27.0
27.4
20.8
20
5.8
1.5
0
Electric shock
Arcing fault
Electric shock and arcing fault
Arcing fault with electro-ophthalmia and burns
- 1 internal arcing fault per 10,000 GIS panels and
year
5Physical Effects of an Internal Fault
Energy balance
Radiation
Temperature riseand pressure rise
Evaporation
Thermal conduction, melting
Electric arc, plasma beam with a temperature of
about 20,000 C
6Possible Effects of an Internal Fault
- Light effect (blinding, shock)
- Noise development (hearing damage)
- Thermal load (heat, burns)
- Smoke development (breathing)
- Projection of parts (cuts)
- Toxic effects (intoxication)
- Pressure development (damage to buildings / walls
and door), physiological influence on a person
(shock, falling caused by defensive reaction,
circulatory insufficiency)
7Avoidance of Internal Faults
- Quality during design, production and
installation - Training of personnel (avoidance of maloperation)
- Maintenance (replacement of worn-out parts,
cleaning) - Active systems for fault detection
Other measures for avoidance of internal arcs are
described in IEC 62271-200, Table 2 Locations,
causes and examples of measures to reduce the
probability of internal faults
8Comparison of the Internal Arcing Test IEC 60298
vs. IEC 62271-200
9Comparison of the Internal Arcing Test
Consequences from IEC 62271-200
- Classification with IAC ? Tested and passed
according to standard conditions - Classification without IAC ? Not tested or not
passed - Existing switchgear assemblies tested to IEC
60298 are still allowed to operate, however they
might not be comparable with other switchgear. - Consequence for operators (as comparisons are
hardly possible) ? Request tests according to the
prescribed general standard, i.e. IEC 62271-200. - This provides the quality feature of
standardized comparability.
?
?
10Designation of the Internal Arc Classification
Classification IAC ( Internal Arc
Classified ) Accessibility A (F, L, R) B
(F, L, R) C Test values Current kA and
duration s
F Front L Lateral R Rear
Example 1 IAC A FLR 25 kA 1 sExample
2 IAC B FL 25 kA 1 s
11Test Procedure
- For switchgears with internal arc classification
(IAC) according to IEC 62271-200 - Test object consists of 2 panels as a minimum
- Test in every compartment and at least in the
end panel - Completely equipped test specimen (reproductions
are accepted) - Test only on not pre-stressed functional
compartments - Defined distances (walls, ceiling)
- 40 to 50 of the surface must be covered with
indicators - Defined direction of power flow and points of
arc initiation - SF6-insulation may be replaced by air
- Evaluation of all five criteria
Busbar compartment
Circuit-breaker compartment
Cable compartment
12Test Arrangement Conditions (1)
(a) Height of ceiling - Height of test object
600 mm 100 mm - If height of test object
1.5 m gt Min. height of ceiling 2 m (b) Rear
wall - Non-accessible 100 mm 30 mm -
Accessible 800 mm 100 mm (c) Indicators -
Covering 40 to 50 (checker pattern)
13Test Arrangement Conditions (2)
For the test object in the room mock-up
For the indicators
14Acceptance criteria
new
new
15Test Setup
Current test object, open vessel and ignition
wire
16Test Parameters
- Type of accessibility A
- Free-standing arrangement
- Short-circuit current 25 kA
- Short-circuit duration 1 s
- Height of ceiling 2.8 m
- Switch position of all devices CLOSED
- Operating tool inserted
- Infeed via right-hand disconnector panel
- 3-phase arc initiation in gas vessel of CB-panel
at cable connection bushings - Direction of power flow as feeder panel ? IAC A
FLR 25 kA 1 s
17High-Power Test Laboratory at the Location
Frankfurt am Main
18Test Preparations
Arrangement of test object in room mock-up
19Live Test
Performance of internal arcing test (Changeover
to high-power testing laboratory)
20Flashback (Slow Motion of Live Test)
Test recorded from different camera positions
21Acceptance Criteria
22Resulting Document
As an example from previous tests
23Discussion / Questions
24Thank you very muchfor your attention!