Title: How to Convert and Optimize
1- How to Convert and Optimize
- Primary/Secondary Pumping Systems
- to Variable Flow Primary Systems
Presented By Hemant Mehta, P.E.
WMGroup Engineers, P.C.
2History of Variable Primary Flow Projects
- King Saud University - Riyadh (1977)
- Louisville Medical Center (1984)
- Yale University(1988)
- Harvard University (1990)
- MIT(1993)
- Amgen (2001)
- New York-Presbyterian Hospital (2002)
- Pennsylvania State Capitol Complex (2005)
- Duke University (2006)
- NYU Medical Center (2007)
- Memorial Sloan-Kettering Cancer Center (2007)
3King Saud University Riyadh (1977)
- 60,000 ton capacity with 30,000 tons for first
phase - Six 5,000 ton Carrier DA chillers
- Seven 10,000 GPM 240 TDH constant speed pumps
- Major Problem Too much head on chilled water
pumps - Lesson Learned Be realistic in predicting growth
4Louisville Medical Center (1984)
- Existing system (1984)
- Primary/Secondary/Tertiary with 13,000 ton
capacity - Current System (2007)
- 120 feet TDH constant speed primary pumps with
building booster pumps 30,000 ton capacity - Changed the heads on some of the evaporator
shells to change number of passes - Primary pumps are turned OFF during winter, Early
Spring and Late Fall. Building booster pumps are
operated to maintain flow.
5Yale University (1988)
- Existing system (1988)
- Primary/Secondary/Tertiary with 10,500 ton
capacity - Current System (2007)
- 180 feet TDH VFD / Steam Turbine driven variable
flow primary pumps 25,000 ton capacity - Changed the heads on some of the evaporator
shells to change number of passes
6Amgen (2001)
- Creation of a computerized hydraulic model of the
existing chilled water plant and distribution
system - Identification of bottlenecks in system flow
- Evaluation of existing capacity for present and
future loads - Two plants interconnected Single plant operation
for most of the year, second plant used for
peaking - Annual Energy Cost Savings 500,000
7Additional Variable Primary Flow Projects
- Harvard University (1990)
- MIT(1993)
- New York-Presbyterian Hospital (2002)
- Pennsylvania State Capitol Complex (2005)
- Duke University (2006)
- NYU Medical Center (2007)
- Memorial Sloan-Kettering Cancer Center (2007)
8Duke University Background
- CCWP-1 plant was built four years ago
- CCWP-2 design was 90 complete (Primary/Secondary
pumping) - We were retained by Duke to peer review the
design - Peer review was time sensitive
- Plant design for CCWP-2 was modified to Variable
Primary pumping based on our recommendations
9Duke CCWP-1 Before
10Duke CCWP-1 After
- Dark blue pipe replaces old primary pumps
11Duke Levine Science Research Center CHW System
12Duke CIEMAS Building CHW System
90 closed
Triple duty valves 50 closed
13Duke CIEMAS Building AHU-9
Balancing valve 50 closed
14NYU Medical Center (2007)
- Plant survey and hydraulic model indicated
unnecessary pumps - 1,300 horsepower of pumps are being removed,
including 11 pumps in two brand new chiller
plants - 300,000 implementation cost
- 460,000 annual energy savings
15NYU Medical Center (2007)
- Plant survey and hydraulic model indicated
unnecessary pumps - 1,300 horsepower of pumps are being removed,
including 11 pumps in two brand new chiller
plants - 300,000 implementation cost
- 460,000 annual energy savings
8 Pumps Removed
3 Pumps Removed
7 Pumps Removed
3 Pumps Removed
16Memorial Sloan-Kettering - Before
17Memorial Sloan-Kettering - After
Bypass or removal of pump
Bypass or removal of pumps
18Pump Cemetery
To date we have removed several hundred large
pumps from our clients chilled water systems
19Good Engineers Always Ask Why?
- Why does the industry keep installing
Primary/Secondary systems? - Why dont we get the desired system ?T?
- Why does the industry allow mixing of supply and
return water?
20Good Engineers Always Ask Why?
- Why does the industry keep installing
Primary/Secondary systems? - Why dont we get the desired system ?T?
- Why does the industry allow mixing of supply and
return water? - Answer To keep consultants like us busy!
- Why change?
21Reasons to Change
- Chiller manufacturing industry supports the
concepts of Variable Primary Flow - Evaporator flow can vary over a large range
- Less space is required for fewer pumps
- Lower first cost and operating costs
22Change is Starting Around the World
- Most of the large district cooling plants in
Dubai currently use Primary/Secondary pumping - By educating the client we were able to convince
them that this is not necessary - We are now currently designing three 40,000 ton
chiller plants in Abu Dhabi using Variable
Primary Flow as part of a 6.9 billion
development project
23Design Guidelines of A Primary Variable Flow
System
- Main Equipment
- Minimize amount of installed equipment
- Estimate maximum chiller capacity required with
full build-out of your campus - Use 350 SF/Ton as a guideline for most building
types - Multiple Plants/ Virtual Central System
- Review your existing system and decide your needs
for ultimate build-out
24Design Guidelines of A Primary Variable Flow
System
- Chillers
- Renegotiate with manufacturer to provide maximum
capacity based on the chiller selection. - Keep flow velocity around 6.5 ft/sec at peak
- Chilled Water Pumps
- Variable Frequency Drive
- Review feasibility of oversizing pumps in lieu of
providing a standby pump
25Design Guidelines of A Primary Variable Flow
System
- Condenser Water Pumps
- Variable Speed Condenser Water Pumps?
- Cooling Towers
- Design for at least 2F higher wet bulb
temperature than normal design wet bulb - Specify full flow coverage at 50 of peak flow
- Pressurization Tank
- City water pressure may be adequate
- Tank May not be required for large system
- Air Separators
- Not required
26Design Guidelines of A Primary Variable Flow
System
- Controls
- Flow control valves on CHWR and CWR lines to each
chiller - Chilled water differential pressure bypass valve
at the plant - Differential pressure sensors at the
hydraulically most remote buildings - Flow meters on CHWR and CWR lines to each chiller
- Outside air weather station
- Temperature and humidity sensors for cooling
tower controls - Learn the behavior of your system
- Remember
- You can not manage what you do not measure
27Design Guidelines of A Primary Variable Flow
System
- Chilled water flow controls and site differential
pressure - Master Control
- CHWP VFD is controlled to maintain required
differential pressure at remote buildings - Sub Master Control
- Provide to maintain individual chiller minimum
flow
28Variable Volume Primary System Flow Diagram
29Variable Volume Primary System Flow Diagram
Chillers
30Variable Volume Primary System Flow Diagram
CHW Pumps
31Variable Volume Primary System Flow Diagram
DP Bypass
32Variable Volume Primary System Flow Diagram
Condensers
33Variable Volume Primary System Flow Diagram
Control Valves
34Variable Volume Primary System Flow Diagram
CW Pumps
35Variable Volume Primary System Flow Diagram
Cooling Towers
36Summary
- There are many chilled water plants with
significant opportunities for improvement - WM Group has a proven record of providing smart
solutions that work - We will be happy to review your plant logs with
no obligation
37- Thank You
- Hemant Mehta, P.E.
- President
- WMGroup Engineers, P.C.
- (646) 827-6400
- hmehta_at_wmgroupeng.com