How to Convert and Optimize - PowerPoint PPT Presentation

About This Presentation
Title:

How to Convert and Optimize

Description:

How to Convert and Optimize Primary/Secondary Pumping Systems to Variable Flow Primary Systems Presented By: Hemant Mehta, P.E. WMGroup Engineers, P.C. – PowerPoint PPT presentation

Number of Views:154
Avg rating:3.0/5.0
Slides: 38
Provided by: Adm91101
Category:

less

Transcript and Presenter's Notes

Title: How to Convert and Optimize


1
  • How to Convert and Optimize
  • Primary/Secondary Pumping Systems
  • to Variable Flow Primary Systems

Presented By Hemant Mehta, P.E.
WMGroup Engineers, P.C.
2
History of Variable Primary Flow Projects
  • King Saud University - Riyadh (1977)
  • Louisville Medical Center (1984)
  • Yale University(1988)
  • Harvard University (1990)
  • MIT(1993)
  • Amgen (2001)
  • New York-Presbyterian Hospital (2002)
  • Pennsylvania State Capitol Complex (2005)
  • Duke University (2006)
  • NYU Medical Center (2007)
  • Memorial Sloan-Kettering Cancer Center (2007)

3
King Saud University Riyadh (1977)
  • 60,000 ton capacity with 30,000 tons for first
    phase
  • Six 5,000 ton Carrier DA chillers
  • Seven 10,000 GPM 240 TDH constant speed pumps
  • Major Problem Too much head on chilled water
    pumps
  • Lesson Learned Be realistic in predicting growth

4
Louisville Medical Center (1984)
  • Existing system (1984)
  • Primary/Secondary/Tertiary with 13,000 ton
    capacity
  • Current System (2007)
  • 120 feet TDH constant speed primary pumps with
    building booster pumps 30,000 ton capacity
  • Changed the heads on some of the evaporator
    shells to change number of passes
  • Primary pumps are turned OFF during winter, Early
    Spring and Late Fall. Building booster pumps are
    operated to maintain flow.

5
Yale University (1988)
  • Existing system (1988)
  • Primary/Secondary/Tertiary with 10,500 ton
    capacity
  • Current System (2007)
  • 180 feet TDH VFD / Steam Turbine driven variable
    flow primary pumps 25,000 ton capacity
  • Changed the heads on some of the evaporator
    shells to change number of passes

6
Amgen (2001)
  • Creation of a computerized hydraulic model of the
    existing chilled water plant and distribution
    system
  • Identification of bottlenecks in system flow
  • Evaluation of existing capacity for present and
    future loads
  • Two plants interconnected Single plant operation
    for most of the year, second plant used for
    peaking
  • Annual Energy Cost Savings 500,000

7
Additional Variable Primary Flow Projects
  • Harvard University (1990)
  • MIT(1993)
  • New York-Presbyterian Hospital (2002)
  • Pennsylvania State Capitol Complex (2005)
  • Duke University (2006)
  • NYU Medical Center (2007)
  • Memorial Sloan-Kettering Cancer Center (2007)

8
Duke University Background
  • CCWP-1 plant was built four years ago
  • CCWP-2 design was 90 complete (Primary/Secondary
    pumping)
  • We were retained by Duke to peer review the
    design
  • Peer review was time sensitive
  • Plant design for CCWP-2 was modified to Variable
    Primary pumping based on our recommendations

9
Duke CCWP-1 Before
10
Duke CCWP-1 After
  • Dark blue pipe replaces old primary pumps

11
Duke Levine Science Research Center CHW System
12
Duke CIEMAS Building CHW System
90 closed
Triple duty valves 50 closed
13
Duke CIEMAS Building AHU-9
Balancing valve 50 closed
14
NYU Medical Center (2007)
  • Plant survey and hydraulic model indicated
    unnecessary pumps
  • 1,300 horsepower of pumps are being removed,
    including 11 pumps in two brand new chiller
    plants
  • 300,000 implementation cost
  • 460,000 annual energy savings

15
NYU Medical Center (2007)
  • Plant survey and hydraulic model indicated
    unnecessary pumps
  • 1,300 horsepower of pumps are being removed,
    including 11 pumps in two brand new chiller
    plants
  • 300,000 implementation cost
  • 460,000 annual energy savings

8 Pumps Removed
3 Pumps Removed
7 Pumps Removed
3 Pumps Removed
16
Memorial Sloan-Kettering - Before
17
Memorial Sloan-Kettering - After
Bypass or removal of pump
Bypass or removal of pumps
18
Pump Cemetery
To date we have removed several hundred large
pumps from our clients chilled water systems
19
Good Engineers Always Ask Why?
  • Why does the industry keep installing
    Primary/Secondary systems?
  • Why dont we get the desired system ?T?
  • Why does the industry allow mixing of supply and
    return water?

20
Good Engineers Always Ask Why?
  • Why does the industry keep installing
    Primary/Secondary systems?
  • Why dont we get the desired system ?T?
  • Why does the industry allow mixing of supply and
    return water?
  • Answer To keep consultants like us busy!
  • Why change?

21
Reasons to Change
  • Chiller manufacturing industry supports the
    concepts of Variable Primary Flow
  • Evaporator flow can vary over a large range
  • Less space is required for fewer pumps
  • Lower first cost and operating costs

22
Change is Starting Around the World
  • Most of the large district cooling plants in
    Dubai currently use Primary/Secondary pumping
  • By educating the client we were able to convince
    them that this is not necessary
  • We are now currently designing three 40,000 ton
    chiller plants in Abu Dhabi using Variable
    Primary Flow as part of a 6.9 billion
    development project

23
Design Guidelines of A Primary Variable Flow
System
  • Main Equipment
  • Minimize amount of installed equipment
  • Estimate maximum chiller capacity required with
    full build-out of your campus
  • Use 350 SF/Ton as a guideline for most building
    types
  • Multiple Plants/ Virtual Central System
  • Review your existing system and decide your needs
    for ultimate build-out

24
Design Guidelines of A Primary Variable Flow
System
  • Chillers
  • Renegotiate with manufacturer to provide maximum
    capacity based on the chiller selection.
  • Keep flow velocity around 6.5 ft/sec at peak
  • Chilled Water Pumps
  • Variable Frequency Drive
  • Review feasibility of oversizing pumps in lieu of
    providing a standby pump

25
Design Guidelines of A Primary Variable Flow
System
  • Condenser Water Pumps
  • Variable Speed Condenser Water Pumps?
  • Cooling Towers
  • Design for at least 2F higher wet bulb
    temperature than normal design wet bulb
  • Specify full flow coverage at 50 of peak flow
  • Pressurization Tank
  • City water pressure may be adequate
  • Tank May not be required for large system
  • Air Separators
  • Not required

26
Design Guidelines of A Primary Variable Flow
System
  • Controls
  • Flow control valves on CHWR and CWR lines to each
    chiller
  • Chilled water differential pressure bypass valve
    at the plant
  • Differential pressure sensors at the
    hydraulically most remote buildings
  • Flow meters on CHWR and CWR lines to each chiller
  • Outside air weather station
  • Temperature and humidity sensors for cooling
    tower controls
  • Learn the behavior of your system
  • Remember
  • You can not manage what you do not measure

27
Design Guidelines of A Primary Variable Flow
System
  • Chilled water flow controls and site differential
    pressure
  • Master Control
  • CHWP VFD is controlled to maintain required
    differential pressure at remote buildings
  • Sub Master Control
  • Provide to maintain individual chiller minimum
    flow

28
Variable Volume Primary System Flow Diagram
29
Variable Volume Primary System Flow Diagram
Chillers
30
Variable Volume Primary System Flow Diagram
CHW Pumps
31
Variable Volume Primary System Flow Diagram
DP Bypass
32
Variable Volume Primary System Flow Diagram
Condensers
33
Variable Volume Primary System Flow Diagram
Control Valves
34
Variable Volume Primary System Flow Diagram
CW Pumps
35
Variable Volume Primary System Flow Diagram
Cooling Towers
36
Summary
  • There are many chilled water plants with
    significant opportunities for improvement
  • WM Group has a proven record of providing smart
    solutions that work
  • We will be happy to review your plant logs with
    no obligation

37
  • Thank You
  • Hemant Mehta, P.E.
  • President
  • WMGroup Engineers, P.C.
  • (646) 827-6400
  • hmehta_at_wmgroupeng.com
Write a Comment
User Comments (0)
About PowerShow.com