Title: Precepten Conventional Control Panels
1Precepten Conventional Control Panels
- EN54 approval
- 2,4,8,16 32 zones
- Key-switch user control access
- Multi-language display options
- Semi-flush / fully-flush bezel options
- Removable chassis for installation
- 4 alarm circuits as standard on 4 zone panel
upwards
2Precepten Conventional Control Panels
- Up to 5 fully functional repeaters connected via
2 core RS485 data cable - Remote panel inputs
- Class change
- Evacuate
- Silence alarms
- System reset
3Precepten Conventional Control Panels
- Remote panel outputs
- Evacuate
- Buzzer active
- Disablement active
- Configurable panel outputs
- (See later slide)
4Precepten Conventional Control Panels
- 8-Way panel enhancement modules
- (See Later Slide)
- Comprehensive end user facilities
- (See later slide)
- Extensive DIL-switch options
- (See later slide)
- Disable buzzer for commissioning
5Cabinet Options
Surface Cabinets Cabinet colour reference is
RAL 7035 textured (Light Grey) All cabinets
are manufactured from sheet steel and finished in
satin texture epoxy powder stove paint.
Semi-Flush Cabinets The semi-flush bezel
locates to the rear of the bevelled edge of the
back box, leaving the bevelled edge and door
raised out from the wall. It is finished in the
same colour as the back box and is fitted by
means of pinch bolts, thus avoiding the need to
drill the cabinet. Fully Flush
Cabinet Custom-made to a high quality,
full-flush bezels are available in brass,
stainless steel, or painted. This option is
achieved by fixing a flat bezel assembly to the
standard back box, replacing the standard door.
The panel comes with assembly already fitted but
may be supplied for later on-site fitting (this
may be a little time-consuming).
6Mechanical Assembly
Multiple earth termination points located
adjacent to cable entries.
Mounting points for the motherboard chassis.
Display and motherboard chassis are removable for
ease of wall mounting.
24V battery set.
7Typical Terminations (16 Zone)
8Panel Configuration Options
- On-board panel options configurable by DIL
switch, display or motherboard links as
appropriate - Selected/all detection zones configurable as -
- Latching / non-latching
- Short circuit to fire for older type detectors
- Delay / non-delay
- Standard / Intrinsically safe
- Sounders Enable / disable fire protection output
operation for non-latch zone operation - Alarm Sounder circuits configurable as standard
or zonal operation - Relays configurable as either Powered fault
monitored or volt free - Inhibit or enable earth fault monitoring
- Enable / disable latching fault indications
- Alarms to operate on any fire evacuate or on
evacuate only - One-man test to be silent or 2 second sounder
operation
9Panel Configuration Options
- One man sounder test
- Delay configuration options
- Any zone to be configured as delay zone
- Single or 2-stage delay
- 1-9 minute delay if single stage
- 1 minute 1-9 minute delay if 2-stage
- Fire routing, fire protection, sounders can be
any combination - Inhibit silence / reset for 3 minutes after fire
operation - Operate sounders on Evacuate only option
- Reset only possible after Silence option
- Disable panel buzzer
108-Way Panel Enhancement Modules
- 4 options for 8-way enhancement modules
- 8 open collector outputs PSU fault input
- 8 C/O relay contacts PSU fault input
- 8 monitored sounder outputs PSU fault input
- 8 fault monitored, powered fire protection
outputs PSU fault input - Matching cabinets to house enhancement boards and
power supplies - Timer clock counter
- Set as day/night and alarm counter
- Or fire alarm clock display
11Extensive User Facilities
- Full disablement facilities
- Individual zones
- Fire routing
- Fire protection
- Fault routing
- Sounder circuits
- One man zone test
- One man sounder test
- Enable / disable delay mode
- Override delay mode
- Extend delay (from 1st to 2nd stage)