Title: Modbus Slave
1Modbus SlaveModbus Master in S7
- Refer to the Modbus Serial Pack v2 zip.
- Project Modbus v2
- Manuals for drivers and hardware
2Preparation..
- To enable the Modbus functionality of the CP
cards, you must do three things - Install Point to Point software from
http//support.automation.siemens.com/WW/view/en/2
7013524 - Install Modbus Master and Slave drivers from
http//support.automation.siemens.com/WW/view/en/2
7774018 http//support.automation.siemens.com/WW/v
iew/en/27774276 - Fit the Modbus dongle to the rear of the CP
- Install the driver to the CP
Preperation
3Summary of the GOULD-MODBUS Protocol
- The type of data exchange between MODBUS systems
is controlled by Function Codes (FCs). - The following FCs can be used to carry out data
exchange bit-by-bit - FC 01 Read coil (output) status,
- FC 02 Read input status,
- FC 05 Force single coil,
- FC 15 Force multiple coils.
- The following FCs can be used to carry out data
exchange register-by-register - FC 03 Read holding registers,
- FC 04 Read input registers,
- FC 06 Preset single register,
- FC 16 Preset multiple registers.
Gould-Modbus
4Summary of the GOULD-MODBUS Protocol
It will save considerable time and frustration to
have a good idea upfront of the mapping of Modbus
data to S7 data. The Modbus slave will define the
function codes to be used by virtue of the fact
that specific data is held in specific Modbus
registers.
Function Code Modbus Address Range Access
Output Coils Function Codes 01, 05, 15 00001 - 09999 Read/Write
Input Coils Function Code 02 10001 - 19999 Read Only
Internal Registers Function Code 04 30001 - 39999 Read Only
Holding Registers Function Codes 03, 06, 16 40001 - 49999 Read/Write
Gould-Modbus
5Configure the Hardware as Modbus Slave
- With the software installed you can now open the
Hardware Configuration and configure the CP341 in
your rack. Double click the CP to open its
properties and click on the Parameter button. The
Point to Point configuration software will now
open. - From the drop down box at the top left, select
Modbus Slave as the Protocol. Next double click
the Protocol icon in the middle of the screen.
S7-300 Slave
6Configure the Driver..
- You are now presented with a number of tabs. The
first tab "General" shows the driver versions in
use. This is for information only. The second tab
"Modbus-Slave" allows you to define the
communications properties of the system, baud,
stop bits etc.
S7-300 Slave
7Configure the Driver..
- On the tab labelled FC01, 05, 15, you can enter
the Modbus address ranges to be mapped into M
area, Outputs, Timers and Counters. If any areas
are not used, enter 0.
S7-300 Slave
8Configure the Driver..
- On the tab FC02, you can define the mapping for M
area and Inputs to be read from.
S7-300 Slave
9Configure the Driver..
- On the tab FC03, 06, 16 you only need to enter a
DB number. These function codes use the address
range starting from Modbus address 40000. The DB
number specified is the start DB of a range of
DB's that are generated by the user and must be
512 words long. If your Modbus address is say
40513, you would need to generate another
consecutively numbered DB of 512 words long.
Modbus address 40513 would be the first address
in the second DB (word 0 of the second DB, the
513 word in total).
S7-300 Slave
10Configure the Driver..
- The tab labelled FC4 is configured in the same
way but for the 30000 address range.
S7-300 Slave
11Configure the Driver..
- The next tab is labelled "Limits". This is where
you can define the range of DB's, Memory and
Outputs to be written to by FC05, FC15, FC06 and
FC16. If you were to use the Modbus address
40513, this would reside in the second DB at word
0. You would therefore need to set the limits
here to DB1 and DB2 (assuming DB1 is the DB
selected for use by FC03, 06, 16). This is
similar for M and Q areas. The final tab defines
any electrical properties.
S7-300 Slave
12Download Hardware Configuration and Modbus
Driver..
- Save and Compile the Hardware Configuration then
download to the controller. Once the
configuration is downloaded we can install the
driver to the CP. To do this you must have an
online connection and use the Load Drivers button
from the Driver Parameters (as we have just
configured).
S7-300 Slave
13Movement of Modbus Data between the CP to the
User Program.
- Now the driver is configured. It knows what to do
when it receives a Modbus telegram read or
write data to or from a specific Simatic area.
Now that the Modbus data can be interpreted by
the Modbus driver on the CP341, we need to move
the data from the CP to the CPU of the PLC. This
is done by use of FB80 MODB_341. This block can
be found in the library entitled "Modbus". The
block is called as part of the cyclic user
program via OB1. It needs to know the logical
address (LADDR) of the CP341 from the hardware
configuration which can be found by highlighting
the CP in the rack in Hardware Configuration. The
address will be shown under the I-address column
of the bottom half of the window.
S7-300 Slave
14Movement of Modbus Data between the CP to the
User Program.
- Block Dependencies
- When you add the FB80 block to the user program,
you will be required to generate an Instance Data
Block. BEFORE generating this block, ensure that
the FB7 and FB8 blocks are also present in the
blocks folder (these are found in the same Modbus
library). This is because FB80 uses these blocks
to communicate with the CP.
S7-300 Slave
15Movement of Modbus Data between the CP to the
User Program.
- OB100 Startup OB
- The only coding that the user must perform is in
OB100, where we set a bit on and a bit off to
initialise the FB on start-up of the CPU, used at
the parameters CP_START and CP_START_FM.
S7-300 Slave
16Movement of Modbus Data between the CP to the
User Program.
- OB1 Main Cyclic OB
- Call FB80 in OB1 and assign addresses for status
reporting. Also assign the CP_Start and
CP_Start_FM bits generated in OB100. - Download all program blocks to the controller and
test!!!
S7-300 Slave
17Configure the Hardware as Modbus Master
- To configure the Modbus Master, we start in
Hardware Configuration. Perform the same steps as
for the slave (selecting Modbus Master as the
Protocol) and click on the Protocol icon in the
middle of the screen.
S7-300 Master
18Configure the Driver..
- Here you have three tabs. The first, "General"
identifies the driver version, as in the slave.
The second, "Modbus Master" is where you define
the communications properties, stop bits, baud
etc.
S7-300 Master
19Configure the Driver..
- The final tab defines any electrical properties.
This is the hardware configured for operation. We
must now send and receive data to/from the CP341.
S7-300 Master
20Movement of Modbus Data between the CP to the
User Program.
- OB1 Main Cyclic OB
- In the cyclic user program we must call two
blocks, P_SND_RK and P_RCV_RK, found in the
Modbus library. The Modbus Master will send a
request for data to its slave (reading values) or
simply send it data (writing).
S7-300 Master
21Movement of Modbus Data between the CP to the
User Program.
- The send block is used to send a number of bytes
that are structured in a specific way and
populated with specific data, depending upon the
function code to be used. For example, FC03
requires the first byte to contain the slave
address, the second byte to contain the function
code number, the third and fourth bytes (DBW2)
must contain the Modbus start address and bytes
five and six (DBW4) contain a value representing
the number of registers required.
S7-300 Master
(All of the structures of data for the various
function codes can be found in section 5 of the
Modbus master manual).
22Movement of Modbus Data between the CP to the
User Program.
- OB1 Main Cyclic OB
- You will need to define a DB that can be used to
receive the data into. You call the receive
block, and populate its parameters similarly to
the send block, telling it the LADDR of the CP341
and the DB to which the data is to be received.
S7-300 Master
23Movement of Modbus Data between the CP to the
User Program.
- With these blocks now configured, you can
download to the hardware and you should have a
working Modbus master. Of course, the blocks will
need code writing around them for timing the send
and receives and also error handling, but I
recommend using a VAT (variable table) to
manually trigger sends etc until you are happy
that the system is functioning. This way you are
in control of the requests and also the data that
is sent.
S7-300 Master
24S7-400 Modbus Master and Modbus Slave
- The configuration is similar when using the
S7-400. Differences include the possibility to
install two interface modules to one CP441-2,
which can be configured independently for
different functions. These interface modules are
fitted to the front of the CP, with the type
dependant upon the electrical connection to the
system (RS232, RS485, RS422). The driver
configuration is identical to when using the
S7-300.
S7-400
25S7-400 Modbus Master and Modbus Slave
- There are differences in the blocks used for both
slave and master functions in the S7-400. - Firstly, the slave uses block FB180 MODB_441.
This can be found in the same location as the
block used in the S7-300. - Secondly, the master uses different blocks to the
S7-300. The S7-400 uses the System Function
Blocks SFB12 and 13 (BSEND and BRCV).
S7-400
26S7-400 Modbus Master and Modbus Slave
- The main difference with both the master and
slave blocks is the requirement of a connection
between the devices. This connection is
configured in Netpro and the ID of this
connection is entered as a parameter to the send
and receive blocks. The connection type is Point
to Point. Once a new connection of the type Point
to Point is added to the configuration, you can
view the properties of it. Here you can set the
CP to be used and select which of the CPs
interfaces are to be connected. You also find the
connection ID, whose value needs to be entered to
the send and receive blocks.
S7-400
27Diagnostics
- Sometimes you may have configured the system but
devices do not communicate in the manner you
expected. Things may appear to be healthy but
data is not being successfully transferred. If
this is the case then you have a number of
options available. - The first place to check would be on the block
calls. The blocks will generate status and error
information. - Secondly, you can check the Module Information of
the CPU and CP for any diagnostic entries. - Error codes generated on the block calls and in
Module Information can be found in the manuals
included in the Modbus Serial Pack. - A further option is to monitor the network using
a network analyzer. This will enable you to see
the raw data present on the network media and
determine if it is present and correct. You
should be seeing telegrams with the format
matching that described in chapter 5 of the
Modbus master manual, depending upon the function
code being implemented (byte 1 should contain the
slave address, byte 2 should contain the function
code etc).
Diagnostics
28Multipoint Connection Details..
RS422 Multipoint
- In the RS422 mode CP341 and CP441-2 can only be
used as a Master
29Multipoint Connection Details..
RS485 Multipoint
30Multipoint Connection Details..
- The following applies for both modules
- GND (PIN 8 by CP341 / CP441-2) must always be
connected on both sides - The casing shield must be installed everywhere
- A terminating resistor of approx. 330 O is to
be soldered into the connector on the last
receiver of a node sequence - Recommended cable type LIYCY 3 x 2 x 0,14
R(A)/R(B) and T(A)/T(B) twisted pairs - A wiring with Stub is not allowed
Multipoint