Title: Seismic Restraint


1
Seismic Restraint
  • Example
  • Using ANSI/SMACNA SEISMIC RESTRAINT MANUAL
    GUIDELINE FOR MECHANICAL SYSTEMS THIRD EDITION

2
Example
  • Single run of rectangular duct
  • Top of duct is 5-8 from to supporting structure
  • Duct size 58 x 24
  • Cs .80 so SHLA Provided by designer

3
Example
  • First determine the applicable figures in Chapter
    4.
  • Can not use Figures 4-2 thru 4-4
  • too far from the structure
  • Figures 4-5 thru 4-7 qualify
  • Note Figure 4-8 is for floor supports
  • Because of preference and jobsite conditions we
    will use Figure 4-7

4
Example
  • Figure 4-7
  • Note 3, Since L 5-8 we need to use table 5-3,
    6-3, 7-3, or 8-3
  • In our case SHL A (Chapter 5)
  • Use Table 5-3

5
Example
6
Example
7
Example
8
Example