Title: Overcurrent Protection (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004)
1Overcurrent Protection(Note All the mentioned
tables in this course refer to, unless otherwise
specified, Low Voltage Electrical
Installation Handbook, by Johnny C.F. Wong,
Edition 2004)
2General
- Purpose
- Safety of Personnel (Shock) and Property (Fire
Hazards) - Maintain reliable life of equipment and systems
- Overcurrent
- a current exceeding the rated value of a circuit
or the current-carrying capacity of a conductor - Overload
- Fault
- Short-circuit fault
- Earth fault
- This part, we are concerned with the
short-circuit fault only.
3Devices for Overcurrent Protection
- Examples are
- Fuses (HBC/HRC)
- Miniature circuit breakers (MCBs)
- Combined MCB and RCD (RCBOs)
- Moulded case circuit breakers (MCCBs)
- Air circuit breaker IDMTL relay
4Devices for Overcurrent Protection
- Protection for the NEUTRAL conductor is NOT
required for TT and TN systems - 100 Neutral should be used
- Protection already provided by the live conductor
protective device - Neutral link (not protective device)
- If the neutral breaks, the live supply must break
too - LOSS OF NEUTRAL must be avoided to eliminate the
risk of raising the potential of the load star
point to dangerous level
5Protection against Overload
- Main purpose is to avoid sustained temperature
that causes deterioration of insulation - e.g. only a short duration of overload current is
allowed to flow in a motor circuit - the starting
duration should be short. Otherwise larger
cables shall be installed
6Selection of Overload Protective Device
- design current Ib ? nominal current or rated
current In ? lowest CCC, Iz
7Position of Overload Protective Device
- At the point where there is a reduction of Iz
(CCC) such as - CSA of conductor is reduced
- Worsening of environmental condition
- Change of cable type or installation method
- Overload protective device and fault current
protective device may be the same device and may
be 2 different devices
8Overload Protection of Conductors in Parallel
- The Iz in this case is the sum of Iz of the
individual cables provided they are in accordance
with the conditions for parallel running cables. - Standard ring final circuits are not in this
context.
9Omission of Overload Protective Device
- Overload current is unlikely to flow
- Refer to Fig. 6.5 for illustration
10Omission of Overload Protective Device
- Unexpected loss of supply is more dangerous than
overloading of circuit - Refer to Fig. 6.6 for illustration
11Omission of Overload Protective Device
- CT secondary circuit should not be broken. If
this is the case, dangerous high voltage will
appear at the CT secondary side - Refer to Fig. 6.7 for illustration
12Omission of Overload Protective Device
- Protection is afforded by electricity suppliers
protective device (not normally accepted by power
companies in Hong Kong) - Refer to Fig. 6.8 for illustration
13Protection against Fault Current
- Cause - Insulation failure, faulted switching
operation and invariably associated with arcs - Effect - Thermal and mechanical stress produced
in conductors, associated support and plant
components - Fault current protection is to prevent this
14Protection for Maximum prospective fault current,
Isc
- Maximum prospective fault current, Isc
- 3-phase calculation based on symmetrical fault
impedance, - Isc Up / Z
- where Up phase voltage
- Z phase conductor impedance at
supply source - 1-phase calculation based on line-neutral
impedance at 20oC, - Isc Up / (Z Zn)
- where Zn neutral conductor impedance at
supply source - The above should base on fault appeared just
after the protective device - Breaking capacity of fault current protective
devices should exceed the max. prospective fault
current, Isc
15Minimum Prospective Fault Current, I
- Minimum prospective fault current, I
- Calculation bases on total phase-neutral
impedance values, up to the remote end - I Up / (Z Zn Z1 Z2)
- where Z1 phase conductor impedance at
consumer side - Z2 neutral conductor impedance
at consumer side - Significant in determining fault disconnection
time, t
16Protection for Minimum Prospective Short Circuit,
I
- Basic equation to satisfy
- k2S2 gt I2t
- Where
- k - a constant associated with the type of
conductor insulation - S - Cross-sectional Area (CSA) of conductor
- I - minimum prospective fault current (fault
occur at remote end) - t - disconnection time
- I2t - let-through energy
17Guidelines in fault current protection
- Max. prospective 3-ph symmetrical short-circuit
at the l.v. source of supply provided by the
supply company is 40kA. - All fuses and MCCBs at source of energy must have
breaking capacity gt 40kA - Fault current protective devices with smaller
breaking capacities are generally acceptable if
they are backed up by fuses to BS88-2.1 or BS88-6
(Backup protection will be discussed later in
Chapter 10) - The further away from the source of supply, the
smaller the prospective short circuit current.
18Fault Current Protection in General
- Example The following single phase circuit is
protected by 63A BS88 fuse, the prospective short
circuit current at the fuse is known to be 3 kA.
A connected load, with circuit distance 87m from
the fuse, is to be supplied by using 16mm2 1/C
PVC copper cable. Please check whether the fuse
can provide short circuit protection for the
cable.
Source
Installation side
Source voltage Up
Z
Z1
63A fuse
Load
1.68 ? / km
Zn
Z2
19Fault Current Protection in General
- At fuse position, it is given that the 1-?
prospective short circuit current is 3 kA, - i.e. Isc Up / (Z Zn)
- Z Zn 3000 / 220 0.073 ?
- The total impedance from the fuse to the
remote load end, - Z1 Z2 2 x 87m x 1.68 ?/km 0.292 ?
- So, the minimum short circuit current at the
load end, - I Up / (Z Zn Z1 Z2)
- 220 / (0.073 0.292)
- 603 A
20Fault Current Protection in General
- Whether k2S2 gt I2t ??
- From I-t characteristic of BS88 fuse, t
0.18 s when I 603 A - PVC copper cable is used ? k 115
- S 16 mm2
- k2S2 1152 x 162 3,385,600 A2S
- I2t 6032 x 0.18 65,450 A2S
- k2S2 gt I2t ? O.K
21Fault Current Protected by Overload Protective
Device
- The protective device is assumed to be adequate
if it - satisfies conditions for overload protective
device. That is, we sizes cable and protective
device by using the principle - Ib In Iz and
- Breaking capacity of protective device Maximum
prospective fault current, Isc - This is the most common way to protect a circuit,
since only ONE protective device is needed.
22Position of fault current protective device
- Normally placed at or before the point where a
reduction in the conductors current-carrying
capacity (Iz) occurs. Such change may be due to
a change in - cross-sectional area, method or installation,
type of cable or conductor, or in environmental
conditions
23Fault current protection of conductors in parallel
- A single device may provide protection against
fault current for conductors in parallel provided
the parallel conductors are in accordance with
Section 5.8
24Omission of short-circuit protective devices
- Conductor between a transformer and its control
panel - Refer to Fig. 6.18 for detailed illustration