Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004) - PowerPoint PPT Presentation

About This Presentation
Title:

Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004)

Description:

Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook ... – PowerPoint PPT presentation

Number of Views:1143
Avg rating:3.0/5.0

less

Transcript and Presenter's Notes

Title: Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004)


1
Protection against Electric Shock (Note All the
mentioned tables in this course refer to, unless
otherwise specified, Low Voltage Electrical
Installation Handbook, by Johnny C.F. Wong,
Edition 2004)
  • (Textbook Chapter 7)

2
Introduction
  • 3 Approaches
  • Combined protection against both Direct
    Indirect Contact
  • Protection against Direct Contact
  • Protection against Indirect Contact

3
Combined Protection against Both Direct
Indirect Contact
  • By Separated Extra-Low Voltage (SELV) System
  • It is extra-low voltage system without connection
    to earth
  • By Limitation of Discharge of Energy
  • The equipment incorporates means of limiting the
    current which can pass through the body of a
    person to a value lower than that likely to cause
    danger
  • However, the open circuit voltage is not limited
  • E.g. equipment with power source and very
    high internal impedance

4
Protection against Direct Contact
  • By Insulation of Live Parts
  • By Barriers or Enclosures
  • By Obstacles
  • By Placing out of Reach
  • Refer to Fig. 7.5 for illustration

5
Protection again Indirect Contact
  • BS7671 (IEE Wiring Regulations) stipulates 5
    methods of protection against indirect contact
  • Protection by earthed equipotential bonding and
    automatic disconnection of supply (EEBADS)
  • Protection by Class II equipment or by insulation
    equivalent
  • Protection by non-conducting location
  • Protection by earth-free local equipotential
    bonding
  • Protection by electrical separation
  • Method 1 above is commonly adopted in HK.

6
Protection again Indirect Contact
  • IEC61140 classifies methods of protection into 4
    types
  • Class 0 by basic insulation only and no
    provision is made for the earthing of accessible
    conductive parts
  • Class I by basic insulation and earthing of all
    accessible conductive parts
  • Class II by double or reinforced insulation, and
    no provision is made for the connection of a
    protective conductor to the accessible conductive
    parts
  • Class III by SELV supplies

7
SELV
8
Reduced Low Voltage System
55V
55V
9
Reduced Low Voltage System
10
EEBADS
  • Earthed Equipotential Bonding Automatic
    Disconnection of Supply (EEBADS)
  • An established practice in Hong Kong
  • Earthed Equipotential Bonding
  • TT - when l.v. supply is given directly by the
    supply company
  • TN-S - allowed only when the supply transformer
    is owned by the consumer
  • Equipotential Bonding - to create an
    equipotential zone within reach, and all
    equipotential zones should be bonded to each
    other
  • Automatic Disconnection of Supply
  • Purpose - to limit duration and magnitude of the
    touch voltage (voltage that arises between
    simultaneously accessible exposed and extraneous
    conductive parts)

11
EEBADS (Contd)
  • Protective device can be
  • overcurrent protective device (e.g. MCBs, MCCBs,
    fuses, etc)
  • residual current device (in socket outlets and
    where prospective earth fault current is
    insufficient for prompt operation)
  • CoP requirements differ from IEE
    Requirements(BS7671). We mainly focus our
    discussion on CoP requirements.

12
Terms for Earthing and Protective Conductors
extraneous conductive parts
exposed conductive parts
A1
A2
gas pipes, water pipes, lightning down conductor,
A/C ducts, etc
B1
B2
circuit protective conductor(cpc)
supplementary equipotential bonding
main equipotential bonding
main earthing terminal
earthing conductor
earth electrode
13
EEBADS (Contd)
  • Exposed conductive parts Extraneous conductive
    parts (refer to Fig. No. 11(1) of CoP)
  • Refer to Fig. 7.7 for installation component
    illustration
  • Earth fault loop impedance, Zs Z1 Z2 ZE
  • where Zs earth fault loop impedance
  • Z1 phase conductor impedance
  • Z2 CPC impedance
  • ZE earth fault loop impedance
    external to the installation
  • For max. permissible Zs, please refer to CoPs
    Tables 11(8) to 11(14) for different types of
    protective device.

14
Touch Voltage, Vt
  • Refer to Fig. 7.8 for symbols and illustration
  • Earth fault current, Ia Uo/(Z1Z2ZE)
  • ?Vt Ia Z2 Z2
    Uo/(Z1Z2ZE)
  • Generally, the max. disconnection time should not
    exceed those indicated in fig. 7.4 for the
    particular Vt involved,
  • E.g. Z1 0.3O, Z2 0.6O, ZE 0.5O
  • Ia Uo/(Z1Z2ZE) 220 / (0.30.60.5)
    157 A
  • Vt Ia Z2 Z2 Uo/(Z1Z2ZE) 157 x 0.6
    94.2 A
  • From Fig. 7.4, in order to avoid danger, the
    max. disconnection time is 0.34 s

15
Touch voltage
  • Fig. 7.8

Extraneous Conductive parts
16
General requirement for touch voltage
  • However, if the circuit complies with the
    specific requirements as laid down by the IEE
    Regulations or the CoP (see the following
    discussion), the general requirements for touch
    voltage are deemed to be complied.

17
EEBADS according to COP (see Table 7.14)
  • Socket Outlet Circuits
  • must be protected by a residual current device
  • must satisfy
  • Refer to Table 7.5 or CoPs Table 11(14)
  • Fixed Equipment used inside Equipotential Zone
  • Disconnection time in case of earth fault within
    5 sec.
  • Fixed Equipment Circuits outside Equipotential
    Zone or inside Bathroom
  • Disconnection time in case of earth fault within
    0.4 sec.

18
EEBADS according to COP
  • Installation supplied from Overhead Line System
  • - must be protected by RCD and,
  • Distribution circuit supplying circuits for both
    Socket Outlets and Fixed Equipment
  • Equipotential bonding shall be provided at the
    distribution board connecting it to the same
    types of extraneous-conductive-parts as the man
    equipotential bonding.

19
Calculation of circuit impedance
  • Refer to Tables 7.15 to 7.17
  • For cable sizes gt 35 mm2, reactance is taken into
    account
  • An average earth fault temperature of (70160)/2
    115oC is assumed for PVC copper cables used as
    CPC

20
Size of Protective Conductor
  • Method 1 Refer CoPs Table 11(2), or
  • Method 2 Refer CoPs Tables 11(3) to 11(7)
  • Method 2 By using formula,
  • where S CSA of protective conductor
  • I earth fault current
  • t disconnection time
  • k a factor taking account of
    the resistivity, temperature coefficient and heat
    capacity of the conductor material, and the
    appropriate initial and final temperatures.
    Values of k are given in Table 7.20

21
Types of Earthing SystemsTN-S System
22
Types of Earthing SystemsTT System
23
Types of Earthing SystemsCombined TT TN-S
System
24
Electric Shock Protection in Locations Containing
a Bath or Shower
  • Is of hazardous areas
  • In case of earth fault, equipment need
    disconnecting within 0.4 s, except that supplied
    from SELV
  • Local supplementary equipotential bonding is
    required for those parts simultaneously
    accessible with extraneous-conductive-parts
    and/or other exposed-conductive-parts.
  • Every switch or other means of electrical control
    should be inaccessible to a person using the
    facilities.

25
Electric Shock Protection in Locations Containing
a Bath or Shower
  • Lampholder within a distance of 2.5m from the
    bath or shower cubicle should be constructed of
    or shrouded in an insulating material.
  • No stationary equipment having heating elements
    which can be touched should be installed within
    reach of a person using the bath or shower.
  • No electrical installation or equipment should be
    installed in the interior of a bath tub or
    shower.

26
Electric Shock Protection in Locations Containing
a Bath or Shower
  • Divided into 4 zones, see Fig. 7.17A B
  • The provision of socket outlets can be in zone 3
    location (i.e. 0.6m away from shower basin or
    bath tub) and they should be protected by a RCD
    with a residual operating current not exceeding
    30mA

27
To Bond or Not to Bond
  • To bond, one has to determine if the following 2
    conditions are fulfilled together
  • 1. the part is an extraneously-conductive-part
    ,
  • i.e. insulation to earth 22000 O ?
  • 2. the part is simultaneously accessible with
    exposed- conductive-parts and/or other
    extraneously-conductive-parts,
  • i.e. separation distance 2 m ?

28
Extraneous Conductive Parts ?
Write a Comment
User Comments (0)
About PowerShow.com