Title: Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004)
1Protection against Electric Shock (Note All the
mentioned tables in this course refer to, unless
otherwise specified, Low Voltage Electrical
Installation Handbook, by Johnny C.F. Wong,
Edition 2004)
2Introduction
- 3 Approaches
- Combined protection against both Direct
Indirect Contact - Protection against Direct Contact
- Protection against Indirect Contact
3Combined Protection against Both Direct
Indirect Contact
- By Separated Extra-Low Voltage (SELV) System
- It is extra-low voltage system without connection
to earth - By Limitation of Discharge of Energy
- The equipment incorporates means of limiting the
current which can pass through the body of a
person to a value lower than that likely to cause
danger - However, the open circuit voltage is not limited
- E.g. equipment with power source and very
high internal impedance
4Protection against Direct Contact
- By Insulation of Live Parts
- By Barriers or Enclosures
- By Obstacles
- By Placing out of Reach
- Refer to Fig. 7.5 for illustration
5Protection again Indirect Contact
- BS7671 (IEE Wiring Regulations) stipulates 5
methods of protection against indirect contact - Protection by earthed equipotential bonding and
automatic disconnection of supply (EEBADS) - Protection by Class II equipment or by insulation
equivalent - Protection by non-conducting location
- Protection by earth-free local equipotential
bonding - Protection by electrical separation
- Method 1 above is commonly adopted in HK.
6Protection again Indirect Contact
- IEC61140 classifies methods of protection into 4
types - Class 0 by basic insulation only and no
provision is made for the earthing of accessible
conductive parts - Class I by basic insulation and earthing of all
accessible conductive parts - Class II by double or reinforced insulation, and
no provision is made for the connection of a
protective conductor to the accessible conductive
parts - Class III by SELV supplies
7SELV
8Reduced Low Voltage System
55V
55V
9Reduced Low Voltage System
10EEBADS
- Earthed Equipotential Bonding Automatic
Disconnection of Supply (EEBADS) - An established practice in Hong Kong
- Earthed Equipotential Bonding
- TT - when l.v. supply is given directly by the
supply company - TN-S - allowed only when the supply transformer
is owned by the consumer - Equipotential Bonding - to create an
equipotential zone within reach, and all
equipotential zones should be bonded to each
other - Automatic Disconnection of Supply
- Purpose - to limit duration and magnitude of the
touch voltage (voltage that arises between
simultaneously accessible exposed and extraneous
conductive parts)
11EEBADS (Contd)
- Protective device can be
- overcurrent protective device (e.g. MCBs, MCCBs,
fuses, etc) - residual current device (in socket outlets and
where prospective earth fault current is
insufficient for prompt operation) - CoP requirements differ from IEE
Requirements(BS7671). We mainly focus our
discussion on CoP requirements.
12Terms for Earthing and Protective Conductors
extraneous conductive parts
exposed conductive parts
A1
A2
gas pipes, water pipes, lightning down conductor,
A/C ducts, etc
B1
B2
circuit protective conductor(cpc)
supplementary equipotential bonding
main equipotential bonding
main earthing terminal
earthing conductor
earth electrode
13EEBADS (Contd)
- Exposed conductive parts Extraneous conductive
parts (refer to Fig. No. 11(1) of CoP) - Refer to Fig. 7.7 for installation component
illustration - Earth fault loop impedance, Zs Z1 Z2 ZE
- where Zs earth fault loop impedance
- Z1 phase conductor impedance
- Z2 CPC impedance
- ZE earth fault loop impedance
external to the installation - For max. permissible Zs, please refer to CoPs
Tables 11(8) to 11(14) for different types of
protective device.
14Touch Voltage, Vt
- Refer to Fig. 7.8 for symbols and illustration
- Earth fault current, Ia Uo/(Z1Z2ZE)
- ?Vt Ia Z2 Z2
Uo/(Z1Z2ZE) - Generally, the max. disconnection time should not
exceed those indicated in fig. 7.4 for the
particular Vt involved, - E.g. Z1 0.3O, Z2 0.6O, ZE 0.5O
- Ia Uo/(Z1Z2ZE) 220 / (0.30.60.5)
157 A - Vt Ia Z2 Z2 Uo/(Z1Z2ZE) 157 x 0.6
94.2 A - From Fig. 7.4, in order to avoid danger, the
max. disconnection time is 0.34 s
15Touch voltage
Extraneous Conductive parts
16General requirement for touch voltage
- However, if the circuit complies with the
specific requirements as laid down by the IEE
Regulations or the CoP (see the following
discussion), the general requirements for touch
voltage are deemed to be complied.
17EEBADS according to COP (see Table 7.14)
- Socket Outlet Circuits
- must be protected by a residual current device
- must satisfy
- Refer to Table 7.5 or CoPs Table 11(14)
- Fixed Equipment used inside Equipotential Zone
- Disconnection time in case of earth fault within
5 sec. - Fixed Equipment Circuits outside Equipotential
Zone or inside Bathroom - Disconnection time in case of earth fault within
0.4 sec.
18EEBADS according to COP
- Installation supplied from Overhead Line System
- - must be protected by RCD and,
- Distribution circuit supplying circuits for both
Socket Outlets and Fixed Equipment - Equipotential bonding shall be provided at the
distribution board connecting it to the same
types of extraneous-conductive-parts as the man
equipotential bonding.
19Calculation of circuit impedance
- Refer to Tables 7.15 to 7.17
- For cable sizes gt 35 mm2, reactance is taken into
account - An average earth fault temperature of (70160)/2
115oC is assumed for PVC copper cables used as
CPC
20Size of Protective Conductor
- Method 1 Refer CoPs Table 11(2), or
- Method 2 Refer CoPs Tables 11(3) to 11(7)
- Method 2 By using formula,
-
- where S CSA of protective conductor
- I earth fault current
- t disconnection time
- k a factor taking account of
the resistivity, temperature coefficient and heat
capacity of the conductor material, and the
appropriate initial and final temperatures.
Values of k are given in Table 7.20
21Types of Earthing SystemsTN-S System
22Types of Earthing SystemsTT System
23Types of Earthing SystemsCombined TT TN-S
System
24Electric Shock Protection in Locations Containing
a Bath or Shower
- Is of hazardous areas
- In case of earth fault, equipment need
disconnecting within 0.4 s, except that supplied
from SELV - Local supplementary equipotential bonding is
required for those parts simultaneously
accessible with extraneous-conductive-parts
and/or other exposed-conductive-parts. - Every switch or other means of electrical control
should be inaccessible to a person using the
facilities.
25Electric Shock Protection in Locations Containing
a Bath or Shower
- Lampholder within a distance of 2.5m from the
bath or shower cubicle should be constructed of
or shrouded in an insulating material. - No stationary equipment having heating elements
which can be touched should be installed within
reach of a person using the bath or shower. - No electrical installation or equipment should be
installed in the interior of a bath tub or
shower.
26Electric Shock Protection in Locations Containing
a Bath or Shower
- Divided into 4 zones, see Fig. 7.17A B
- The provision of socket outlets can be in zone 3
location (i.e. 0.6m away from shower basin or
bath tub) and they should be protected by a RCD
with a residual operating current not exceeding
30mA
27To Bond or Not to Bond
- To bond, one has to determine if the following 2
conditions are fulfilled together - 1. the part is an extraneously-conductive-part
, - i.e. insulation to earth 22000 O ?
- 2. the part is simultaneously accessible with
exposed- conductive-parts and/or other
extraneously-conductive-parts, - i.e. separation distance 2 m ?
28Extraneous Conductive Parts ?