Title: Folie 1
1Acceptance Criteria for Metallic Materials in
Contact with Drinking WaterThomas
RappSection II 3.4Distribution of Drinking
Water
2Outline
- Metallic Materials in Contact with DW
- DWD Requirements
- Testing
- Acceptance Criteria
- Composition List
3Metallic Materials in Contact with DW
- Products
-
- made of materials
4Metallic Materials in Contact with DW
Stainless Steel
Galvanised Steel
Lead
Copper/ Tinned Copper
5Metallic Materials in Contact with DW
- Materials for Components
- Brass (Cu-Zn-Pb alloy)
- Gunmetal (Cu-Sn-Zn-Pb alloy)
6Metallic Materials in Contact with DW
- Metal Release depends on
- Metal Composition and Surface Characteristics
- Composition of the Drinking Water
- Design of the Installation
- Age of the Installation
- Stagnation Time
7Age of Installation
8DWD Requirements
9DWD Requirements
- Parametric Values
- Pb
- Cu
- Ni
- Sb, As, Cd
- Cr, Hg, Se
- Al, Fe, Mn, Na
Weekly Average
10DWD Requirements
- Weakly Average Value?
- No harmonised method available
- National interpretation required
- Germany UBA Sampling Recommandation
- http//www.umweltbundesamt.de/wasser-e/themen/down
loads/drinking-water/UBA-sampling-recommandation.p
df
11DWD Requirements
12DWD Requirements
13DWD Requirements
UBA Sampling Recommandation
Monitoring
Individual Investigation
Fully Flushed Sample (1 L) (S0)
Random Daytime Sample (1 L)
(2h)- 4h Stagnation
First Liter Stagnation Sample (S1)
Second Liter Stagnation Sample (S2)
14Testing Materials
15Testing
- Metals release is caused by corrosion
- long lasting process
- depends on water composition
16Testing
- Test Method EN 15664-1
- Test Waters prEN 15664-2
17Test Device
18(No Transcript)
19Testing
22 Flow periods per day (each 1 or 2 min) Flow
rate 5 l/min Total water flow 145 l/d Operation
time min. 26 weeks Sampling 8 samples after
0,5 0,5 1 1 2 4 8 and 16 h stagnation
20Testing
Hygienic Fitness
Interaction with a local water
General Hygienic Fitness
e.g. for copper pipes
21Testing
Assessment of General Hygienic Fitness
Reference Material
Material
3 Test waters acc. to prEN 15664-2
Comperative test with 1 test water
22Testing
- Test Waters for Reference Materials (prEN
15664-2)
Assessment of General Hygienic Fitness
Nr Characteristics pH HCO3- in mmol/l Cl- SO42- in mmol/l TOC in mg/l
1 very hard, neutral water 7,1- 7,5 gt 5 gt 3 gt 1,5
2 soft water, weakly acidic 6,7- 7,1 0,5- 1,3 - -
3 soft water, alkaline 8,0- 8,4 0,7- 1,3 - -
23Testing Products
24Testing
- Characteristics due to the production
- Lead film on surfaces
- Nickel on inner surfaces of chromium plated
products
25Testing
26Acceptance Criteria
27Acceptance Criteria
- 4 MS proposal Procedure for the Acceptance of
Metallic Materials Used in Contact with Drinking
Water (21. Nov 2008) - Germany DIN 50930-6 (in revision)
28Acceptance Criteria
- Metallic Corrosion Products in the Test Waters
Criteria Acceptance Level
Compliance with DWD parametric values After 3 months (formation of corrosion layers)
Acceptable Contribution to DWD parametric values 50 for Composition Elements 90 for Copper
29Acceptance Criteria
- Examples for Reference Concentrations
Parameter DWD Limit in µg/l Reference Concentration for materials in µg/l Max. Conc. after treatment in µg/l
Pb 10 5 5
Ni 20 10 10
30 31Composition List
32Composition List
- e.g. Copper-Zinc-Lead-Alloys (Brass)
- Reference Material
- Cu 57,0-59,0 Zn Rest Pb 1,9-2,1 ..
- Alloy CW617N, CW612N
- Cu 57,0-60,0 Zn Rest Pb 1,6-2,2 ..
- for products up to 10 contact surface
- Alloy CW614N, CW603N
- Cu 57,0-62,0 Zn Rest Pb 2,5-3,5 ..
- for products up to 1 contact surface
33Composition List
- Approval / Certification of Products
- Products must be made of materials on the CL
- gt Only testing of composition required
- Only for certain characteristics (nickel layers)
further testing of metals release is required
34Composition List
- Specific German Acceptance Criteria
- Use of copper pipes is restricted to certain DW
pH 7,4 or (7,0 pH lt 7,4 and TOC 1,5
g/m³)
35Thank you for your attention!Thomas
RappThomas.Rapp_at_uba.de www.umweltbundesamt.de