Title: ASHRAE Standards 34,
1PLEASE MUTE CELL PHONES
ASHRAE Standards 34, 147 and 15for Large HVAC
Systems
Julian de Bullet Director of Industry
Relations McQuay International 703-395-5054
2(No Transcript)
3What is a Refrigerant?
- 1. In a refrigerating system, the medium of heat
transfer which picks up heat by evaporating at a
low temperature and pressure, and gives up heat
on condensing at a higher temperature pressure. - 2. (Refrigerating fluid) fluid used for heat
transfer in a refrigerating system which absorbs
heat at a low temperature and low pressure of the
fluid and transfers heat at a higher temperature
and higher pressure of the fluid, usually
involving changes of state of the fluid. - Ref ASHRAE Terminology of Heating, Ventilation,
Air Conditioning, Refrigeration
4History of Refrigerants
- 1830s - Jacob Perkins - Vapor Compression (ether)
- 1851 - John Gorie - Patent for Vapor Compression
Cycle - 1859 R-717 / R-718 (Ammonia / Water)
- 1866 CO2 - Naval Applications
- 1873 - R-717 (Ammonia) Commercial Refrigeration -
Karl Linde - 1875 - R-764 (Sulfur dioxide)
- 1920s -R-600a (Isobutane) R-290 (Propane)
- 1922 - Willis Carrier - R-1130 (Dielene)
- 1926 - R-30 (Methylene Chloride)
5Challenged to Find Refrigerant
- Non-flammable
- Good Stability
- Low Toxicity
- Atmos Boiling Point between - 40 32 oF
6Common Refrigerants in 1920s
7Toxicity - Best Minds Tried to Solve
Solving Problem of Toxicity was a Large Problem
to Development of Refrigeration
1927 - Leo Szilard Albert Einstein Improved on
von Platen / Munters Absorption
Design Electromagnetic Pumping Patent
8Fluorocarbons
- CFCs, HCFCs and HFCs
- Limited Combinations
- Adding Chlorine Or Bromine Increases ODP
- Adding Fluorine Increases GWP
- Adding Hydrogen Increases Flammability And Lowers
Atmospheric Lifetime
9Enterthe 70sthe Scientists!!!!
10Montreal Protocol
- 1970s.Rowland And Molina Theory Suggests Ozone
Depletion In Upper Atmosphere - HVAC MANUFACTURERS GO CRAZY
- 1985 Antarctic Ozone Depletion Observed
- 1987 Montreal Protocol Signed
- Included Phase Outs For Specific Chemicals In
Developed Countries 1974
11Phase Outs-Developed Countries
- Montreal Protocol
- HCFC Schedule
- 1996 Cap (1989 HCFC Production Plus 2.8 Of 1989
CFC Production) - 2004 65
- 2010 35
- 2015 10
- 2020 0.5 No New Equip.
- 2030 0
- USA - EPA
- 2004 End Production R-141B
- Lower Cap For R-22 to 65
- 2010 Service Only For R-22
- 2015 10 For R-22
- 2020 End Production For R-22
- Service Only For R-123
- 2030 End Production For R-123
12Guideline 3
- Reducing Emission of Halogenated Refrigerants in
- HVAC R Systems
- First published in 1990 for CFC Refrigerants only
- Next re-published in 1996- included HCFCs
- Design Good practices included
- Compressors
- Shaft Seals
- Vibration
- Isolation Condensers Evaporators
- Piping Connections
- Valves
- Purging Devices
- Prevention of Vacuum Systems and Leak Test
Pressurization Systems - Refrigerant recovery
- MINIMIZE RELEASES OF HALOGENATED REFRIGERANTS
13Clean Air Act-1998
- EPA Published a proposed rule Fall 1997
- Reduce Emissions Rate on New Equipment?
- Fix Leaks or be FINED 25,000 per day
- Chiller Leakage rates have come down
- Negative Pressure- 15
- Positive Pressure-8
- New Chillers- World Bank- 5 or less
14Results?
- It Worked
- Over 30,000 CFC Chillers are still in service
- What about the New Refrigerants?
15ASHRAE Standard 34-2004
16ASHRAE Standard 34 History
- Describes a shorthand way of naming
refrigerants and assigning safety classifications
based on toxicity and flammability data - First Published in 1978
- Now on Continuous Maintenance
- 2004 Edition incorporates many new refrigerants,
blend compositions and tolerances.
17ASHRAE 34 SAFETY GROUPS
B3
A3 Propane Butane
High Flammability LowFlammability No
FlamePropagation
A2 R-142b, 152a
B2 Ammonia
A1 R-11, 12, 22, 114, 500, 134a
B1 R-123, SO
2
Lower Toxicity
Higher Toxicity
18Anything new?
- The Standard is under continuous maintenance..
- Many additional compositions have been added by
addenda and assigned Refrigerant Numbers..
19ASHRAE Standard 15
20ASHRAE Standard 15
- What is ASHRAE 15?
- An industry standard that specifies safe design,
construction, installation, and operation of
refrigerating systems - Establishes safeguards for life, limb, health,
and property, and prescribes safety standards
21ASHRAE Standard 15
- Requirements
- Based on 3 Classifications
- Occupancy
- Refrigerating System
- Refrigerant
22ASHRAE Standard 15
- Occupancy Classifications - Ability to Respond
to Exposure - Institutional - Assistance Required
- Public Assembly - Large Numbers
- Residential - Sleeping
- Commercial - Business Transactions
- Large Mercantile - 100 Persons or More
- Industrial Refrigerated Rooms - Access
Controlled - Mixed - Two or More in Same Building
23ASHRAE Standard 15
- Refrigerating System Classification
- High Probability - Leak Can Enter Occupied Space
- Low Probability - Leak Cannot Enter Occupied
Space
24ASHRAE Standard 15
- Restrictions on Refrigerant Use - Section 7
- Standard 15 Gives Rules based on Occupancy,
System, Refrigerant Classification - 3 kg or Less of Flammable Refrigerants may be
used in Listed Equipment
25Defining the Needs of a Machinery Room
- Considerations should include
- safety
- energy efficiency minimums
- temperature control requirements
- reliability/redundancy
- serviceability
- accommodating future expansions
- Process Safety Management
26Machinery Room Ventilation Functions
- Purges refrigerant vapor from the machinery room
in emergency situations - For Ammonia - attempts to prevent the
concentration of from reaching the lower
flammability limit - Purges to prevent concentration from exceeding
toxicity limits - A2 Refrigerants - minimizes the probability of a
deflagration - Limit excessive temperature rise due to
equipment-generated heat
27Machinery Room Ventilation Functions
- Ventilation for occupants
- Facilitates maintaining the machinery room under
negative pressure - Enhances refrigerant sensor responsiveness
28Emergency Ventilation
- A high ventilation rate that attempts to purge
refrigerant vapor from the machinery room during
a leak - Initiated by
- manual switch outside the machinery room door
- refrigerant sensor in machinery room
- reset requires manual intervention
29Non-Emergency Intermittent
- Help limit temperature rise of machinery room due
to - heat produced by motors
- heat given off by other equipment (hot gas
piping, oil separators) - heat gain through exterior walls
- Initiated by
- thermostat
30Last-Non-Emergency Continuous
- Helps maintain machinery room under negative
pressure - Provides ventilation air for room occupants
- Continual movement of air through room helps keep
refrigerant detectors responsive - Initiated by
- whenever the machinery room is operational
- during occupancy
31Ventilation Intake/Exhaust Placement
- Inlet location for exhaust fans should consider
where vapors will concentrate - Exhaust fan location should consider prevailing
weather conditions and surrounding buildings - Avoid recirculation between inlets and outlets
- Intake/exhaust locations should facilitate good
scavenging of air through machinery room
32Ventilation Operation Maintenance
- Recognize the critical importance of this safety
system - Items requiring attention on a scheduled basis
- Ventilation fan(s) air intakes operable in
all modes? - Machinery room pressure relationship is
machinery room under negative pressure? - Refrigerant detectors are the detector(s)
functioning properly - Controls check the control sequences and modes
33Electrical Shutdown for Class 2 3
- Removes all non-classified electrical equipment
from operation at high flammable refrig
concentrations - motors, motor control centers, floats, switches,
etc. - Why? It reduces likelihood of deflagrations
- All equipment remaining operational should be the
appropriate classification - ventilation fans, emergency lighting, alarms,
other equipment
34Other Safety Systems
- Eyewash and shower stations
- Passive containment for recirculators/vessels
- diking
- drain to temporary holding tank
- Tie ammonia detection and fire protection alarms
into auto paging system - Machinery room secured 24X7 with key card access
35Eye Wash Decon Showers
36Pressure Relief Valves (PRV)
- A normally closed pressure-actuated valve set to
open at a pre-determined upstream pressure
37Rupture Disks
- A means of relieving pressure by use of a member
(usually a circular disk) that physically breaks
when its design pressure is exceeded and does not
reclose.
38Three-way Valves
- Permits positive isolation of relief valve for
servicing
39Relief Piping Length Limits(ASHRAE Standard 15 -
2004)
- L equivalent length of pipe (ft)
- Cr rated capacity as stamped on relief
device (lb/min) - f friction factor
- d inside diameter of pipe (in)
- Po allowed backpressure at relief valve outlet
(psia) - P2 absolute pressure at outlet of discharge
piping (psia) - APPENDIX H
40Relief Valve OM
- Vent lines to atmosphere
- protect from moisture incursion
- be capable of draining condensate
- be capable of draining rainwater
- Inspect outlets to insure they are free from
obstructions - watch out for those hornet nests
- Do internal visual inspections of your PRVs
41Relief Valve OM
- Be sure you install the correct rating valve
- check the valve itself not just the box
- check the valve against the vessels rating
- Use caution when replacing valves on headered
systems - a PRV in service could lift
42Relief Valve OM
- If a PRV lifts
- replace it ASAP if it re-seals
- replace it immediately if it does not reseal
- IIAR 2 limits PRV service life no more than 5 yrs
- an inspection/evaluation program can allow
extension (or reduction) of the interval - recent OSHA lawsuit may change approach to PRVs
43Mechanical Room Safety Check
Location of inlet vents in relation to exhaust
outlets ?
Location of roof drains ?
Rupture disc outlet locations ?
Is there a tight seal on doors ?
Purge vents to outside ?
Are safety rupture lines the right size ?
Is access to mechanical room restricted ?
Are drain valves connected to evacuation devices ?
Are there any pit areas in the room ?
Where do the floor drains empty to ?
44Mechanical Room Per ASHRAE 15
Relief discharge shall be located not less than
20 from ventilation opening and not less than
15 above ground level (9.7.8)
All indoor machinery rooms must be vented to
the outdoors utilizing mechanical ventilation
Purge systems and relief devices must be vented
to outside (8.14)
Access to mechanical room shall be
restricted. Tight fitting doors opening outward
(self closing if the open into the
building) adequate in number to ensure freedom
of escape. No other openings that would permit
passage of escaping refrigerant (8.3)
Refrigerant sensors are located in areas
where refrigerant vapor from a leak will be
concentrated so as to provide warning at
concentration not exceeding the refrigerant
TLV-TWA
The total amount of refrigerant stored in
a machinery room in all containers not
provided with relief valves piped in accordance
with standard shall not exceed 330 lb.(11.5)
45Sample Sensor Locations
Entrance / Exits
Refrigerant Storage
Just Above floor Next to Chillers
Drains
Pits
Examples not part of standard
46Mechanical Room Per ASHRAE 15
Periodic tests of detectors, alarms ventilation
must be performed in accordance with
manufactures recommendations and/or
local jurisdiction. (10)
Mechanical room should be dimensioned for
easy access to all parts and adequate space for
service, maintenance, and operation. Clear head
room of not less than 7.25 below equipment
situated over passageways. (8.11)
No open flames that use combustion air from the
machinery room (boilers) can be located within
the mechanical as long as the combustion air is
ducted from the outside to the boiler or
shut down sensors are installed (8.12)
A change in the type of refrigerant in a system
shall not be made without the notification of the
authority having jurisdiction, the user and due
observance of safety requirements.
The refrigerant being considered shall be
evaluated for suitability (5.3)
47ASHRAE Standard 15
- Recent Changes
- No Oxygen Containing Test Gases
- Relief Valve Piping
- SCBA Not Required
48ASHRAE Standard 15
- NOT - Recent Change (Required since 1934)
- No Open Flames or Combustion Equipment with
Refrigerant Containing Equipment - Exceptions
- Ducted Combustion Air
- Refrigerant Detector Shuts Down Combustion
Process - R-744 (CO2) or R-718 (H2O)
- R-717 (ammonia) with Engine Drive
49ASHRAE SP-93
50IIAR 2
51ASHRAE Standard 147-2002
-
- Reducing the Release of Halogenated Refrigerants
from HVAC R Systems - Replaces Guideline 3
- Includes HFC Refrigerants
- New Initiatives
- ARI- Responsible Use Guideline for Minimizing
Fluorocarbon Emissions in Manufacturing
Facilities
52Ideal Application
Innovative Design Award
53Thank You