SSTG - PowerPoint PPT Presentation

1 / 18
About This Presentation
Title:

SSTG

Description:

Supplies lube oil to the reduction gear and bearings. CONTROL OIL CIRCUIT ... LUBE OIL ALARM-4-5 PSIG. 62B-216-14. 20 AUG 00. SAFETY/WARNING DEVICES. SENTINEL ... – PowerPoint PPT presentation

Number of Views:602
Avg rating:3.0/5.0
Slides: 19
Provided by: steameng
Category:
Tags: sstg | lube

less

Transcript and Presenter's Notes

Title: SSTG


1
SSTG
62B-216
2
BASIC STEAM CYCLE
GENERATION PHASE
ECONOMIZER
STEAM DRUM
EXPANSION PHASE
BOILER
AUXILIARY CONDENSER
MAIN FEED PUMP
DEAERATING FEED TANK
MAIN FEED BOOSTER PUMP
AUXILIARY AIR EJECTOR CONDENSER
FEED PHASE
CONDENSATION PHASE
3
MAIN STEAM SYSTEM
4
SSTG
TURBINE
FLEXIBLE COUPLING
5
SSTG
  • TURBINE -THERMAL ENERGY TO MECHANICAL ENERGY.
  • REDUCTION GEARS -REDUCE HIGH SPEED OF TURBINE TO
    A USEFULL GENERATOR SPEED.
  • GENERATOR- CONVERTS MECHANICAL ENERGY TO
    ELECTRICAL ENERGY.

6
ELECTRICAL GENERATION
  • As the Turbine Turns, the Generator Rotor Turns
    Inside the Stator and Electrical Power Is
    Produced.
  • Nearly All SstgS Throughout the Navy Are Rated
    at
  • 450 Volts
  • 60 Hertz
  • 3 Phase

7
SPECIFICATIONS
  • TURBINE SPEED 9336 - 9956 RPM
  • GENERATOR SPEED 1200 RPM
  • GEAR TYPE FLEXIBLE COUPLING BETWEEN TURBINE AND
    RED GEAR
  • NO FLEXIBLE COUPLING BETWEEN RED. GEAR AND
    GENERATOR

SHIP DEPENDENT
8
SSTG
9
LUBE OIL CIRCUITS
  • LUBRICATING OIL CIRCUIT
  • Supplies lube oil to the reduction gear and
    bearings
  • CONTROL OIL CIRCUIT
  • Supplies oil to the constant speed governor
    control oil system.
  • TRIP OIL CIRCUIT
  • maintains the trip throttle valve open admitting
    steam to the turbine until a trip is activated.

10
SSTG
TO CONTROL OIL
E
H
TO TRIP OIL
L.O. PUMPS ATTACHED - ELECTRIC - AUTO AT 60
PSIG HAND - VANE TYPE
11
TRIP DEVICES
  • LUBE OIL TRIP
  • OVERSPEED TRIP
  • MANUAL TRIP
  • BACK PRESSURE TRIP

12
SSTG
TO CONTROL OIL
E
H
L
O
B
M
13
ALARMS
  • HIGH AIR BOX-185OF
  • GENERATOR PEDESTAL BEARING- 205OF
  • LUBE OIL ALARM-4-5 PSIG

14
SAFETY/WARNING DEVICES
  • SENTINEL VALVE 2 PSIG
  • CASING RELIEF VALVE 10 - 30 PSIG
  • LOW L/O PRESS ALARM 4 - 5 PSIG
  • HIGH BEARING TEMP 205 DEG F.
  • HIGH AIR BOX ALARM 185 DEG F.

15
START UP OF SSTG
  • ALIGN L/O SYSTEM
  • ALIGN AUX. CIR WATER
  • ALIGN AND RECIRC AUX. CONDENSATE
  • ALIGN AUX. AIR EJECTORS- AUX STEAM STOP OPEN 200
    TO 400 PSIG

16
START UP OF SSTG
  • AT 15 IN. VACUUM ALIGN AUX. EXH. AND ROLL SSTG,
    ALIGN GLAND SEAL AND OPEN COND. DISCHARGE
  • L/O COOLER OUTLET TEMPERATURE 100 DEG.F THE SSTG
    CAN BE PLACED ON THE GOVERNOR

17
PLACE ELECTRICAL LOAD ON SSTG
  • L/O COOLER TEMPERATURE 120 DEG.F
  • SSTG ON GOVERNOR FOR 25-30 MINUTES
  • BOILER IN FULL AUTOMATIC

18
SSTG 62B-216
Write a Comment