Title: Foliengrundrahmen
1TELECOM-LINE
2T E L E C O M - L I N E
A/Cs for Cabinet
A/Cs for Shelter
Wall-Air
Compact-Air
Tel-Air
Mini-Air
Split-Air
X-Line
Wind-Air
C1010 - Microprocessor
3WALL-AIR CVSaaxx2yyzzzz Wall mounted external ai
r conditioner
4WALL-AIR - Application
Airflow
Installation
5WALL-AIR Type 1 - Features
- C1010- Microprocessor control
- Freecooling, proportional
- Emergency ventilation with 48 VDC
- Condenser fan speed control
- Internal high humidity control / Dehumidification
- Airflow and clogged filter signal
- Auto restart after power failure
- Antifreeze thermostat
- Volt free contacts for various alarm signals
- Separate power supply for mains and DC
- Anti vandalism protection
- Refrigerant R407c
- Airfilter EU3/G3
- High efficient Scroll-Compressor
6WALL-AIR Type 1 - Options
- Casing adaption Units with 4kW to 17 kW to be
mounted at the same cut-outs and fixing points - Electrical socket connections
- Electrical heater
- Emergency ventilation with 24 VDC
- DC-power supply via A/C unit
- Various power supply with 50 Hz and 60 Hz
- Monitoring via STULZ TeleCompTrol
- Air grilles
- Humidity sensor
- Sound absorption cover
- Refrigerant R22 or R134a
- Casing made of aluminium or stainless steel
- Crankcase heater (for t(out)lt-20C)
- Protective treatment on heat exchanger coils
7WALL-AIR Type 2 - Features
- Thermostat control
- Compressor start delay
- Compressor cooling only
- Auto restart after power failure
- Antifreeze thermostat
- Anti vandalism protection
- Refrigerant R407c
- Airfilter EU3/G3
- High efficient Scroll-Compressor
8WALL-AIR Type 2 - Options
- C1010- Microprocessor control
- Electrical heater
- Airflow signal
- Clogged filter signal
- Various power supply with 50 Hz and 60 Hz
- Monitoring via STULZ TeleCompTrol (with C1010)
- Air grilles
- Sound absorption cover
- Refrigerant R22 or R134a
- Casing made of aluminium or stainless steel
- Crankcase heater (for t(out)lt-20C)
- Protective treatment on heat exchanger coils
9WALL-AIR - Cooling capacities 50Hz
50 Hz
Conditions Return air 25C/40r.F. Ambient
air 35C Values in kW
10WALL-AIR - Cooling capacities 60Hz
60 Hz
Conditions Return air 25C/40r.F. Ambient
air 35C Values in kW
11WALL-AIR - Dimensions
Height 40, 50, 60 1500 mm 80, 90 1725
mm A2, A4, A7 1910 mm B1 2000 mm
Depth 40, 50, 60 490 mm 80, 90 565
mm A2, A4, A7 600 mm B1 735 mm
Width 40, 50, 60 880 mm 80, 90 960 mm A2,
A4, A7 1170 mm B1 1460 mm
12WALL-AIR - RtR Ready to Run - Option
RtR (Ready to Run) means Only two casing sizes
from 4 kW to 17kW Same Cut-Outs and fixing points
for all units Same plug/socket configuration for
all unit sizes Realised with this
options CVS40-60 with larger casing and fixing
angles CVS80/90 with fixing angles Socket
connection field Grilles for UMTS-size Plug-kit
for site power supply
13WALL-AIR - RtR - Small and Large Size
14WALL-AIR - Power Supply
Site (Shelter, room, ...)
Main AC power supply
48 VDC
AC power supply for compressor condenser fan
48 VDC power supply for control evaporator
fan damper motor
Wall-Air / Tel-Air / Split-Air
15WALL-AIR - Power Supply WITH TRAREC
Site (Shelter, room, ...)
Main AC power supply
48 VDC
Only during emergency ventilation
Normal operation
AC power supply for compressor condenser fan
TRAREC Transformer Rectifier
48 VDC power supply for control, evaporator
fan, damper motor
Wall-Air / Tel-Air / Split-Air
16WALL-AIR - Freecooling
Compressor cooling
Freecooling
17C1010 - Microprocessor Hardware
- C1010 - Microprocessor for control Wall-Air,
Tel-Air, Split-Air - Hardware built in inside the A/C-units el.
cabinet - Keypad to be mounted inside the Shelter
- C1010 controls 1 A/C-unit
- 1 Keypad can be connected to five units
- C1010 operates also without connected keypad
- Flash-Eprom for easy software update
- Various volt free contacts to be connected to
site Monitoring systems - Inputs for remote on/off fire or smoke shutoff
and others...
18C1010 - Microprocessor Software
- Control of cooling, freecooling, heating,
dehumidification, humidification (with external
humidifier) - Multistage cooling/freecooling control with two
units - Sequencing incl. alarm start
- 2nd unit start to assist 1st unit with cooling,
freecooling, heating - Advanced high/low pressure alarm management
- Low/Max/High temperature alarm management
19TEL-AIR CVSaaxx1yyzzzz Wall mounted internal air
conditioner
20TEL-AIR - Application
Airflow
Installation
21TEL-AIR Type 1 - Features
- C1010- Microprocessor control
- Freecooling, proportional
- Emergency ventilation with 48 VDC
- Condenser fan speed control
- Internal high humidity control / Dehumidification
- Airflow and clogged filter signal
- Auto restart after power failure
- Antifreeze thermostat
- Volt free contacts for various alarm signals
- Separate power supply for mains and DC
- Refrigerant R407c
- Airfilter EU3/G3
- High efficient Scroll-Compressor
22TEL-AIR Type 1 - Options
- Electrical socket connections
- Electrical heater
- Emergency ventilation with 24 VDC
- DC-power supply via A/C unit
- Various power supply with 50 Hz and 60 Hz
- Monitoring via STULZ TeleCompTrol
- Air grilles
- Humidity sensor
- Refrigerant R22 or R134a
- Crankcase heater (for t(out)lt-20C)
- Protective treatment on heat exchanger coils
23TEL-AIR Type 2 - Features
- Thermostat control
- Compressor start delay
- Compressor cooling only
- Auto restart after power failure
- Antifreeze thermostat
- Refrigerant R407c
- Airfilter EU3/G3
- High efficient Scroll-Compressor
24TEL-AIR Type 2 - Options
- C1010- Microprocessor control
- Electrical heater
- Airflow signal
- Clogged filter signal
- Various power supply with 50 Hz and 60 Hz
- Monitoring via STULZ TeleCompTrol (with C1010)
- Air grilles
- Refrigerant R22 or R134a
- Crankcase heater (for t(out)lt-20C)
- Protective treatment on heat exchanger coils
25TEL-AIR - Cooling capacities 50Hz
50 Hz
Conditions Return air 25C/40r.F. Ambient
air 35C Values in kW
26TEL-AIR - Cooling capacities 60Hz
60 Hz
Conditions Return air 25C/40r.F. Ambient
air 35C Values in kW
27TEL-AIR - Dimensions
Height 1990 mm
Width 40, 50, 60 550 mm 80, 90, A2 800 mm
Depth 40, 50, 60 650 mm 80, 90, A2 700 mm
28TEL-AIR - Freecooling
Compressor- cooling
Free cooling
Compressor- cooling
Free cooling
Option Downflow
29SPLIT-AIR CSTaaxxHyyzzzz Split air conditioner
30SPLIT-AIR - Application
31SPLIT-AIR Type 1 - Features
- C1010- Microprocessor control
- Freecooling, proportional
- Emergency ventilation with 48 VDC
- Condenser fan speed control
- Internal high humidity control / Dehumidification
- Airflow and clogged filter signal
- Auto restart after power failure
- Antifreeze thermostat
- Volt free contacts for various alarm signals
- Separate power supply for mains and DC
- Anti vandalism protection
- Refrigerant R407c
- Airfilter EU3/G3
- High efficient Scroll-Compressor
- Indoor unit for vertical or horizontal mounting
32SPLIT-AIR Type 1 - Options
- Duct for vertical indoor unit
- Duct for horizontal indoor unit
- Mounting kit for outdoor unit
- Electrical heater
- Emergency ventilation with 24 VDC
- DC-power supply via A/C unit
- Various power supply with 50 Hz and 60 Hz
- Monitoring via STULZ TeleCompTrol
- Air grilles
- Humidity sensor
- Refrigerant R22 or R134a
- Crankcase heater (for t(out)lt-20C)
- Protective treatment on heat exchanger coils
33SPLIT-AIR Type 2 - Features
- Thermostat control
- Compressor start delay
- Compressor cooling only
- Auto restart after power failure
- Antifreeze thermostat
- Anti vandalism protection
- Refrigerant R407c
- Airfilter EU3/G3
- High efficient Scroll-Compressor
- Indoor unit for vertical or horizontal mounting
34SPLIT-AIR Type 2 - Options
- C1010- Microprocessor control
- Electrical heater
- Airflow signal
- Clogged filter signal
- Various power supply with 50 Hz and 60 Hz
- Monitoring via STULZ TeleCompTrol (with C1010)
- Mounting kit for outdoor unit
- Refrigerant R22 or R134a
- Crankcase heater (for t(out)lt-20C)
- Protective treatment on heat exchanger coils
35SPLIT-AIR - Cooling capacities 50Hz
50 Hz
Conditions Return air 25C/40r.F. Ambient
air 35C Values in kW
36SPLIT-AIR - Cooling capacities 60Hz
60 Hz
Conditions Return air 25C/40r.F. Ambient
air 35C Values in kW
37SPLIT-AIR - Dimensions
Outdoor-unit Height 40, 50 580 mm 60, 80 640
mm Width 40, 50 800 mm 60, 80 950
mm Depth 40, 50 350 mm 60, 80 400 mm
Indoor-unit without freecooling Height 40, 50
310 mm 60, 80 412 mm Width 40, 50 800 mm 60,
80 900 mm Depth 40, 50 800 mm 60, 80 1000 mm
Indoor-unit with freecooling Depth 40, 50 1050
mm 60, 80 1300 mm
38SPLIT-AIR - Freecooling
Compressor- cooling
Free cooling
Compressor- cooling
Free cooling
Vertical Installation
Horizontal Installation
39WIND-AIR CHSaaxx3yyzzzz Window air conditioner
40WIND-AIR - Application
41WIND-AIR - Features and Options
- For indoor/outdoor applications
- Cooling capacities in 4 steps from 3,8 to 8 kW
- Two unit sizes
- Various power supply available
- Thermostat control
- Refrigerant R407c, optional R134a or R22
- High and low pressure safety device
- Auto restart after power failure
- G3/EU3-Filter
- Main unit malfunction alarm
- opt. airflow and clogged filter signal
- opt. condenser fan speed control
- opt. high temp. alarm thermostat
42MINI-AIR CVCaaxx1yyzzzz Vertical
internal cabinet air conditioner
43MINI-AIR - Application
44MINI-AIR - Features and Options
- For inside cabinet installation
- Cooling capacities in 5 steps 0,75 to 4,1 kW
- Three unit sizes
- Various power supply available
- Built-in regulating thermostat
- Condenser fan speed control
- Refrigerant R134a
- High and low pressure safety device
- Capillary pipe and filter dryer
- No air filter required
- opt. electrical heater
- opt. emergency ventilation with 24 or 48 VDC
- opt. high/low temperature alarm thermostat
- opt. contact for common alarm
- opt. clevis type brackets for easy mounting
45COMPACT -AIR CVCaaxx2yyzzzz Vertical
external cabinet air conditioner
46COMPACT-AIR - Application
47COMPACT-AIR - Features and Options
- For outside cabinet installation
- Cooling capacities in 5 steps 0,75 to 4,1 kW
- Three unit sizes
- Various power supply available
- Built-in regulating thermostat
- Condenser fan speed control
- Refrigerant R134a
- High and low pressure safety device
- Capillary pipe and filter dryer
- No air filter required
- opt. Electrical heater
- opt. Emergency ventilation with 24 or 48 VDC
- opt. high/low temperature alarm thermostat
- opt. contact for common alarm
- opt. clevis type brackets for easy mounting
48X-LINE XVTaaxx3yyzzzz Cabinet air to
air exchanger
49X-LINE - Application
50X-LINE - Features and Options
- For internal/external cabinet application
- Air-Air heat exchanger
- Five unit sizes
- Exchange coefficients 60,80,100,150,200 W/K
- Various power supply available
- Optional electronic control board
- New coil technology patented by Cosmotec
- Increased coil efficiency
51X-LINE - Selection
52Model Identification Code
53Pricelist - One sheet per product
54Pricelist - Quick calculation
Unit selection
Options depending on unit size
Options independent to unit size