Title: Kein Folientitel
1SIPROTEC 4
7SA522 Distance Protection for Transmission Lines
Productmanager Distance Protection Michael
Claus EV S V 13 Nürnberg H Phone 49 911 433
8261 Fax 49 911 433 8301 Email
Michael.Claus_at_nbg6.siemens.de
2What does SIPROTEC 4 mean?
- SIPROTEC 4 is a new family of digital protection-
and control-devices - All SIPROTEC 4 relays include control-functions
and user-definable logic (PLC) - SIPROTEC 4 assists you with
- a simplified handling together with DIGSI 4
- a better adaptation to local requirements
- SIPROTEC 4 uses modern communication-technology
for system integration - SIPROTEC 4 uses a common hardware platform
37SA522Distance Protection for Transmission Lines
4SIPROTEC 7SA522 Front design
- Navigation Keys
- convenient menu operation
- 4-line back-lit display
- Measured values
- Fault data
4 freely assignable function keys with slot for
legend text
- Turning ON/OFF of functions
- Control of switchgear (plant)
14 LEDs for user assignment and slot to insert
legend text
- 9-pole
- service interface
- standard cable
- DIGSI 4
Width of housing 1/2 of 19" or 1full 19 rack
- Proven numeric keypad
- secure entry of numbers
- easy password entry
5SIPROTEC 7SA522 Terminals and Communication
Interfaces
- Open to new techniques (methods)
- electric or fibre optic (FO)
- process or 2nd remote relay interface
Width of housing1/2 of 19" or full 19"
Binary inputs 8 (16, 24) Output contacts 16
(24,32) (in full 19 rack housing)
- Remote relay interface (plan)
- electric or fibre optic (FO)
- for protection signalling
- System interface
- electric or fibre optic
- IEC60870-5-103 or Profibus FMS (approx. 12/00)
- in future DNP3.0, MODBUS and Profibus DP
4 Voltage Transformers (VT)
4 Current Transformers (CT)option with Ienormal
or Iesensitive
- Time synchronization
- GPS
- with IRIG-B and DCF-77
- Service interface
- electrical or fibre optic (FO)
- DIGSI 4 via Modem
67SA522Connection Diagram Basic Version
- Optional
- Sensitivity
- normal
- high (5mA)
77SA522Single Line Diagram
8SIPROTEC 7SA522 Scope of functions (1)
ANSI-No.
21, 21N FL 85-21
- Distance Protection
- quadrilateral and/or MHO characteristic
- full scheme measurement with sophisticated loop
selection - three phase and single phase tripping
- five independent zones and one controlled
overreach zone - all zones can be set forward/reverse/non-direction
al - with/without parallel line compensation
- special filtering for CVT transients
- special algorithm for detection and compensation
of CT saturation - Fault Locator with/without parallel line
compensation - Universal teleprotection interface (PUTT, POTT,
Blocking, Unblocking, DTT...)
17.10.97 en513all7
9SIPROTEC 7SA522 Scope of functions (2)
ANSI-No.
- High resistance earth fault protection for
earthed systems - directional and/or non-directional
- 4 stages
- definite-time and/or inverse-time characteristic
- high sensitivity (3 mA secondary)
- backup protection running in parallel to the
distance protection - Teleprotection interface for earth fault
protection (Directional comparison, Blocking,
Unblocking) - Weak infeed protection(Echo and Trip)
- Power swing blocking/out-of-step tripping
50N, 51N, 67N 85-67N WI 68
17.10.97 en513all8
10SIPROTEC 7SA522 Scope of functions (3)
ANSI-No.
50, 5150N-2, 51N-2 59 50HS 50-STUB 79 25 50BF
- Overcurrent protection DMTL/IDMTL as parallel or
emergency function - Overvoltage protection
- Fast tripping with switch-onto-fault condition
- STUB Bus Overcurrent protection
- Single and three pole multishot automatic
reclosure - Synchro-check
- Circuit-breaker failure protection
11SIPROTEC 7SA522 Scope of functions (4)
ANSI-No.
74TC 86 FR 47
- Trip Circuit Supervision
- Lock Out
- Oscillographic Fault Recording
- Voltage Phase Sequence
- Interfaces
- Time synchronization (IRIG-B, DCF77)
- User interface1 (on the front for DIGSI 4)
- User-(Service-)interface 2 (on the rear, DIGSI
4/Modem) - System interface (IEC60870-5-103/Profibus
FMS/others) - Remote relay interfaces 1 (planned for
teleprotection) - Remote relay interfaces 2 (planned for
teleprotection)
available in Version 4.2 approx. 1. Q/01
12SIPROTEC 7SA522 Quadrilateral Zone
Characteristic
13SIPROTEC 7SA522 MHO Zone Characteristic
14MHO characteristic Effect of polarization
Example 2 phase fault B-C
Symbols ZR zone setting V BC measured fault
voltage I B, I C measured fault currents k pol
polarization factor (0.15)
157SA522 - Trip time curves at SIR 1
167SA522 - Parallel-line compensation connection
and setting
177SA522 - Fault locator
187SA522 - Teleprotection Schemes
197SA522 - Phase segregated Teleprotection
2
2
L2-E
Z1
Z1B
L1-E
1
1
B
A
Z1
Z1B
- A1 trips single-phase in L1 with a
phase-segregated L1-receive-signal - Maximum of Selectivity
Note 3 binary channels for both directions are
requested or (in preparation) one serial link
207SA522 - Teleprotection with three-terminal lines
Software provides teleprotection of
three-terminal lines without additional logic
217SA522 - Echo and Tripping in case of no-infeed
or weak-infeed
Configuration
Settings
Matrix
The receive signal is derived from
and
Three-terminal schemes are supported as well
Phase segregated weak-infeed tripping
!
Note The echo signal must be marshalled in
addition to the send signal on the transmission
signal contact
17.10.97 en513ase2
227SA522High Resistance Earth Fault Protection (1)
- Earth (zero sequence) current protection, 4
stages - 3 definite-time stages
- 1 inverse-time stage IEC, logarithmic inverse or
ANSI characteristicthis stage can also be used
as a 4th definite-time stage - Directional determination with 3V0 and/or Ipol of
an earthed power transformer - Directional determination with V2 and I2
(negative sequence) - Sensitive 3I0-measurement with a dynamic from
0.005 A to 100 x In - Elimination of higher harmonics with special
digital filters - Inrush-stabilisation with I0/100Hz
- Teleprotection Directional comparison, Blocking
or Unblocking - Operation with weak infeed trip and echo
- Instantaneous trip after switch-onto-fault
237SA522 High Resistance Earth Fault Protection (2)
Definite-time characteristic
247SA522 High Resistance Earth Fault Protection (3)
Inverse-time characteristic IEC
257SA522 High Resistance Earth Fault Protection (4)
267SA522 High Resistance Earth Fault Protection (5)
277SA522 High Resistance Earth Fault Protection (6)
Tripping characteristic Logarithmic Inverse
t
T3I0pmax (P3145)
T3I0p (P3144)
3I0p(P3140)
Example t 5.8 - 1.35 ln(3I0 / 3I0p)
T3I0min (P3141)
3I0 / 3I0p
3I0p Startpoint(P3154)
287SA522 High Resistance Earth Fault Protection (6)
Filter characteristic for stages 3I0gtgtgt and 3I0gtgt
297SA522 High Resistance Earth Fault Protection (7)
Filter characteristic for stages 3I0gt and
Inverse time stage
307SA522 - STUB protection for 11/2-circuit breaker
arrangement
Release of STUB-stage with open line isolator
317SA522 - Monitoring
- Operating system monitoring
- Auxiliary voltage failure
- Measured value detection
- Buffer battery
- HardwareWatchdog
- SoftwareWatchdog
- Working memory
- Program memory
- Parameter memory
- Sampling frequency
- 1/5 Asetting
- Calibration data
- Earth current transformer sensitive/normal
- Modules (I/O Boards)
- Plausibility monitoring
- Current sum
- Current symmetry
- Open conductor
- Fuse Failure
- 1- / 2-pole failures
- 3-pole failures
- Voltage sum
- Voltage symmetry
- Voltage phase rotation
new